IBC Design 721.1(3) 17-1.1

3-Hour Fire Rated Perlite concrete slab proportioned 1:6 (Portland… — Perlite gypsum plaster on metal lath wire…

IBC Table 721.1(3), Item 17-1.1: Perlite concrete slab proportioned 1:6 (Portland cement to perlite aggregate) on a 9/16"-deep steel deck supported by steel joists 4' on center. Class A or B roof covering on top.. Ceiling: Perlite gypsum plaster on metal lath wire tied to 3/4" furring channels attached with 0.065" (No. 16 B.W. gage) wire ties to lower chord of joists. Minimum slab thickness — 3-hr: 2" · 2-hr: 2". Minimum ceiling thickness — 3-hr: 7/8" · 2-hr: 3/4". Prescriptive assembly from the adopted building code — see table footnotes for conditions.

Perlite concrete slab proportioned 1:6 (Portland cement to perlite aggregate) on a 9/16"-deep steel deck supported by steel joists 4' on center. Class A or B roof covering on top.. Ceiling: Perlite gypsum plaster on metal lath wire tied to 3/4" furring channels attached with 0.065" (No. 16 B.W.…

The full text is for BuildSpec members

Read the complete section, search across every adopted code, run the calculators and ask Copilot — free for 14 days, no card required.