4-Hour Fire Rated Carbonate aggregate concrete — Slab (ceiling not required). Minimum cover…
IBC Table 721.1(3), Item 2-1.1: Carbonate aggregate concrete. Ceiling: Slab (ceiling not required). Minimum cover over nonprestressed reinforcement shall be not less than 3/4". Minimum slab thickness — 4-hr: 6.6" · 3-hr: 5.7" · 2-hr: 4.6" · 1-hr: 3.2". Prescriptive assembly from the adopted building code — see table footnotes for conditions.
Carbonate aggregate concrete; ceiling: Slab (ceiling not required). Minimum cover over nonprestressed reinforcement shall be not less than 3/4".
The rest of 4-Hour Fire Rated Carbonate aggregate concrete — Slab (ce… is for members