IBC Design 721.1(3) 6-1.1
2-Hour Fire Rated Steel joists constructed with a poured reinforced… — Gypsum plaster on metal lath attached to…
IBC Table 721.1(3), Item 6-1.1: Steel joists constructed with a poured reinforced concrete slab on metal lath forms or steel form units.. Ceiling: Gypsum plaster on metal lath attached to the bottom cord with single No. 16 gage or doubled No. 18 gage wire ties spaced 6" on center. Plaster mixed 1:2 for scratch coat, 1:3 for brown coat, by weight, gypsum-to-sand aggregate for 2-hour system. For 3-hour system plaster is neat. Minimum slab thickness — 2-hr: 2-1/2" · 1-hr: 2-1/4". Minimum ceiling thickness — 2-hr: 3/4" · 1-hr: 5/8". Prescriptive assembly from the adopted building code — see table footnotes for conditions.
Steel joists constructed with a poured reinforced concrete slab on metal lath forms or steel form units.. Ceiling: Gypsum plaster on metal lath attached to the bottom cord with single No. 16 gage or doubled No. 18 gage wire ties spaced 6" on center. Plaster mixed 1:2 for scratch coat, 1:3 for brown…
The rest of 2-Hour Fire Rated Steel joists constructed with a poured… is for members