IBC Design 721.1(3) 6-4.1
2-Hour Fire Rated Steel joists constructed with a poured reinforced… — Ceiling of 5/8" Type X wallboard, 7/8" deep…
IBC Table 721.1(3), Item 6-4.1: Steel joists constructed with a poured reinforced concrete slab on metal lath forms or steel form units.. Ceiling: Ceiling of 5/8" Type X wallboard, 7/8" deep by 2-5/8" by 0.021 inch (No. 25 carbon sheet steel gage) hat-shaped furring channels 12" on center with 1"-long No. 6 wallboard screws at 8" on center. Channels wire tied to bottom chord of joists with doubled 0.049 inch (No. 18 B.W. gage) wire or suspended below joists on wire hangers. Minimum slab thickness — 2-hr: 2-1/2". Minimum ceiling thickness — 2-hr: 5/8". Prescriptive assembly from the adopted building code — see table footnotes for conditions.
Steel joists constructed with a poured reinforced concrete slab on metal lath forms or steel form units.. Ceiling: Ceiling of 5/8" Type X wallboard, 7/8" deep by 2-5/8" by 0.021 inch (No. 25 carbon sheet steel gage) hat-shaped furring channels 12" on center with 1"-long No. 6 wallboard screws at 8"…