IBC Design 721.1(1) 1-1.3

4-Hour Fire Rated Steel columns and all of primary trusses — Carbonate, lightweight and sand-lightweight aggregate…

IBC Table 721.1(1), Item 1-1.3 (Steel columns and all of primary trusses): protection by Carbonate, lightweight and sand-lightweight aggregate concrete, members 12" x 12" or greater (not including sandstone, granite and siliceous gravel). Minimum insulating material thickness — 4-hr: 1-1/2" · 3-hr: 1" · 2-hr: 1" · 1-hr: 1". Prescriptive protection from the adopted building code — see table footnotes for conditions.

Carbonate, lightweight and sand-lightweight aggregate concrete, members 12" x 12" or greater (not including sandstone, granite and siliceous gravel).

The rest of 4-Hour Fire Rated Steel columns and all of primary trusse… is for members