IBC Design 721.1(1) 1-7.2

2-Hour Fire Rated Steel columns and all of primary trusses — Three layers of 5/8" Type X gypsum wallboard.First and…

IBC Table 721.1(1), Item 1-7.2 (Steel columns and all of primary trusses): protection by Three layers of 5/8" Type X gypsum wallboard.First and second layer held in place by 1/8" diameter by 1-3/8" long ring shank nails with 5/16" diameter heads spaced 24" on center at corners. Middle layer also secured with metal straps at mid-height and 18" from each end, and by metal corner bead at each corner held by the metal straps. Third layer attached to corner bead with 1" long gypsum wallboard screws spaced 12" on center. Minimum insulating material thickness — 2-hr: 1-7/8". Prescriptive protection from the adopted building code — see table footnotes for conditions.

Three layers of 5/8" Type X gypsum wallboard.First and second layer held in place by 1/8" diameter by 1-3/8" long ring shank nails with 5/16" diameter heads spaced 24" on center at corners. Middle layer also secured with metal straps at mid-height and 18" from each end, and by metal corner bead at…

The full text is for BuildSpec members

Read the complete section, search across every adopted code, run the calculators and ask Copilot — free for 14 days, no card required.

  • Layer-by-layer components with thicknesses
  • Cross-section diagram
  • Applicable code sections and test standard
  • 6 related assemblies