IBC Design 721.1(1) 2-2.1
2-Hour Fire Rated Webs or flanges of steel beams and girders — Cement plaster on metal lath attached to 3/4" cold-rolled…
IBC Table 721.1(1), Item 2-2.1 (Webs or flanges of steel beams and girders): protection by Cement plaster on metal lath attached to 3/4" cold-rolled channels with 0.04" (No. 18 B.W. gage) wire ties spaced 3" to 6" on center. Plaster mixed 1:2-1/2 by volume, cement to sand. Minimum insulating material thickness — 2-hr: 2-1/2" · 1-hr: 7/8". Prescriptive protection from the adopted building code — see table footnotes for conditions.
Cement plaster on metal lath attached to 3/4" cold-rolled channels with 0.04" (No. 18 B.W. gage) wire ties spaced 3" to 6" on center. Plaster mixed 1:2-1/2 by volume, cement to sand.