IBC Design 721.1(1) 4-1.1

4-Hour Fire Rated Bonded or unbonded post-tensioned tendons in prestressed concrete — Carbonate, lightweight, sand-lightweight and siliceous.…

IBC Table 721.1(1), Item 4-1.1 (Bonded or unbonded post-tensioned tendons in prestressed concrete): protection by Carbonate, lightweight, sand-lightweight and siliceous. Unrestrained members: Beams and girders-- greater than 12" wide Minimum insulating material thickness — 4-hr: 3" · 3-hr: 2-1/2" · 2-hr: 2" · 1-hr: 1-1/2". Prescriptive protection from the adopted building code — see table footnotes for conditions.

Carbonate, lightweight, sand-lightweight and siliceous. Unrestrained members: Beams and girders-- greater than 12" wide

The rest of 4-Hour Fire Rated Bonded or unbonded post-tensioned tendo… is for members