Home / Assemblies / UL D105
UL D1051.5-hr Fire RatingFloor/CeilingLoad-BearingSTC 35
Steel JoistFiberglass BattDesign

Steel Joist Floor/Ceiling — single layer Spray-applied fireproofing

UL-listed 1.5-hour fire-rated steel joist floor/ceiling assembly. Open-web steel joists at 24" o.c. with R-19 fiberglass batt, single layer of Spray-applied fireproofing ceiling.

Cross-Section Diagram

12345FLOOR/CEILING ASSEMBLYSECTION · NOT TO SCALE5 LAYERSsee legend for ① ② ③
Legend
1Floor covering(varies)
22" concrete on steel deck(2")
3Open-web steel joists at 24" o.c.(14.0")
4R-19 fiberglass batt
5Spray-applied fireproofing(1-1/2")

Specifications

Fire Rating
1.5-Hour
STC Rating
STC 35
Load Bearing
Yes
Total Thickness
17"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
D105
Assembly Type
Floor/Ceiling
Test Standard
UL 263
Construction Group
Non-Combustible
Number of Layers
5 layers

Applicable Codes

IBC 2021 Table 722.1IBC 2021 §722IBC 2024 Table 722.1

Construction Summary

Open-web steel joists at 24" o.c. with R-19 fiberglass batt, single layer of Spray-applied fireproofing ceiling

Material Layers

LayerMaterialThickness
1Floor coveringvaries
22" concrete on steel deck2"
3Open-web steel joists at 24" o.c.14.0"
4R-19 fiberglass batt
5Spray-applied fireproofing1-1/2"

Important Notice