Home / Assemblies / UL D119
UL D1194-hr Fire RatingFloor/CeilingLoad-BearingSTC 40
Steel JoistGypsum BoardFiberglass BattDesign

Steel Joist Floor/Ceiling — 3 layers 5/8" Type C gypsum board

UL-listed 4-hour fire-rated steel joist floor/ceiling assembly. Open-web steel joists at 24" o.c. with R-19 fiberglass batt, 3 layers of 5/8" Type C gypsum board ceiling.

Cross-Section Diagram

1234567FLOOR/CEILING ASSEMBLYSECTION · NOT TO SCALE7 LAYERSsee legend for ① ② ③
Legend
1Floor covering(varies)
22-1/2" lightweight concrete on steel deck(2-1/2")
3Open-web steel joists at 24" o.c.(14.0")
4R-19 fiberglass batt
55/8" Type C gypsum board(5/8")
65/8" Type C gypsum board(5/8")
75/8" Type C gypsum board(5/8")

Specifications

Fire Rating
4-Hour
STC Rating
STC 40
Load Bearing
Yes
Total Thickness
17.38"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
D119
Assembly Type
Floor/Ceiling
Test Standard
UL 263
Construction Group
Non-Combustible
Number of Layers
7 layers

Applicable Codes

NFPA 5000IBC 2024 §722

Construction Summary

Open-web steel joists at 24" o.c. with R-19 fiberglass batt, 3 layers of 5/8" Type C gypsum board ceiling

Material Layers

LayerMaterialThickness
1Floor coveringvaries
22-1/2" lightweight concrete on steel deck2-1/2"
3Open-web steel joists at 24" o.c.14.0"
4R-19 fiberglass batt
55/8" Type C gypsum board5/8"
65/8" Type C gypsum board5/8"
75/8" Type C gypsum board5/8"

Important Notice

This assembly listing is for reference only. Always verify against the current UL Product iQ database before specifying in construction documents. Material substitutions may void the fire rating. Consult with a qualified fire protection engineer for project-specific requirements.