Home / Assemblies / UL L112
UL L1121-hr Fire RatingRoof/CeilingLoad-Bearing
Wood JoistDesign

Wood Truss Roof/Ceiling — single layer 5/8" Type X gypsum board

UL-listed 1-hour fire-rated wood truss roof/ceiling assembly. Wood trusses at 16" o.c. with R-49 blown cellulose, single layer of 5/8" Type X gypsum board ceiling, 1/2" plywood sheathing.

Cross-Section Diagram

12345ROOF/CEILING ASSEMBLYSECTION · NOT TO SCALE5 LAYERSsee legend for ① ② ③
Legend
1Roof covering(varies)
21/2" plywood sheathing(1/2")
3Wood trusses at 16" o.c.(12"-24")
4R-49 blown cellulose
55/8" Type X gypsum board(5/8")

Specifications

Fire Rating
1-Hour
Load Bearing
Yes
Total Thickness
14.62"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
L112
Assembly Type
Roof/Ceiling
Test Standard
CAN/ULC-S101
Construction Group
Light Frame
Number of Layers
5 layers

Applicable Codes

IBC 2021 §722IRC R302.1

Construction Summary

Wood trusses at 16" o.c. with R-49 blown cellulose, single layer of 5/8" Type X gypsum board ceiling, 1/2" plywood sheathing

Material Layers

LayerMaterialThickness
1Roof coveringvaries
21/2" plywood sheathing1/2"
3Wood trusses at 16" o.c.12"-24"
4R-49 blown cellulose
55/8" Type X gypsum board5/8"

Important Notice

This assembly listing is for reference only. Always verify against the current UL Product iQ database before specifying in construction documents. Material substitutions may void the fire rating. Consult with a qualified fire protection engineer for project-specific requirements.