Home / Assemblies / UL N152
UL N1523-hr Fire RatingColumnLoad-Bearing
Design

Concrete Column — Spray-applied fireproofing

UL-listed 3-hour fire-rated concrete column assembly. Cast-in-place concrete column with Spray-applied fireproofing, 3-hour fire rating.

Cross-Section Diagram

12COLUMN PROTECTIONSECTION · NOT TO SCALE2 LAYERSsee legend for ① ② ③
Legend
1Cast-in-place concrete column(15")
2Spray-applied fireproofing(1.84")

Specifications

Fire Rating
3-Hour
Load Bearing
Yes
Total Thickness
18.68"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
N152
Assembly Type
Column
Test Standard
UL 263
Construction Group
Concrete/Masonry
Number of Layers
2 layers

Applicable Codes

NFPA 5000IBC 2024 §722

Construction Summary

Cast-in-place concrete column with Spray-applied fireproofing, 3-hour fire rating

Material Layers

LayerMaterialThickness
1Cast-in-place concrete column15"
2Spray-applied fireproofing1.84"

Important Notice

This assembly listing is for reference only. Always verify against the current UL Product iQ database before specifying in construction documents. Material substitutions may void the fire rating. Consult with a qualified fire protection engineer for project-specific requirements.