Home / Assemblies / UL U158
UL U1582-hr Fire RatingWallLoad-BearingSTC 63
Wood StudMulti-Layer GypsumFiberglass BattResilient ChannelLoad-Bearing WallHigh STCDesign

Wood Stud Wall — 2 layers 1/2" Type X on resilient channels

UL-listed 2-hour fire-rated wood stud wall assembly. 2x6 wood studs at 16" o.c. with R-13 fiberglass batt, 2 layers of 1/2" Type X gypsum board each side on resilient channels.

Cross-Section Diagram

12345679.88"WALL ASSEMBLYSECTION · NOT TO SCALE7 LAYERSsee legend for ① ② ③
Legend
11/2" Type X gypsum board(1/2")
21/2" Type X gypsum board(1/2")
3Resilient channels at 24" o.c.(7/8")
42x6 wood studs at 16" o.c.(5.5")
5R-13 fiberglass batt
61/2" Type X gypsum board(1/2")
71/2" Type X gypsum board(1/2")

Specifications

Fire Rating
2-Hour
STC Rating
STC 63
Load Bearing
Yes
Total Thickness
8.375"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
U158
Assembly Type
Wall
Test Standard
ASTM E119
Construction Group
Light Frame
Number of Layers
7 layers

Applicable Codes

IRC R302.1

Construction Summary

2x6 wood studs at 16" o.c. with R-13 fiberglass batt, 2 layers of 1/2" Type X gypsum board each side on resilient channels

Material Layers

LayerMaterialThickness
11/2" Type X gypsum board1/2"
21/2" Type X gypsum board1/2"
3Resilient channels at 24" o.c.7/8"
42x6 wood studs at 16" o.c.5.5"
5R-13 fiberglass batt
61/2" Type X gypsum board1/2"
71/2" Type X gypsum board1/2"