Home / Assemblies / UL U167
UL U1674-hr Fire RatingWallLoad-BearingSTC 50
Wood StudMulti-Layer GypsumFiberglass BattLoad-Bearing WallDesign

Wood Stud Wall — 3 layers 1/2" Type X

UL-listed 4-hour fire-rated wood stud wall assembly. 2x6 wood studs at 16" o.c. with R-19 fiberglass batt, 3 layers of 1/2" Type X gypsum board each side.

Cross-Section Diagram

1234567810.00"WALL ASSEMBLYSECTION · NOT TO SCALE8 LAYERSsee legend for ① ② ③
Legend
11/2" Type X gypsum board(1/2")
21/2" Type X gypsum board(1/2")
31/2" Type X gypsum board(1/2")
42x6 wood studs at 16" o.c.(5.5")
5R-19 fiberglass batt
61/2" Type X gypsum board(1/2")
71/2" Type X gypsum board(1/2")
81/2" Type X gypsum board(1/2")

Specifications

Fire Rating
4-Hour
STC Rating
STC 50
Load Bearing
Yes
Total Thickness
8.5"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
U167
Assembly Type
Wall
Test Standard
CAN/ULC-S101
Construction Group
Light Frame
Number of Layers
8 layers

Applicable Codes

IBC 2021 §722IBC 2024 Table 722.1IRC R302.1

Construction Summary

2x6 wood studs at 16" o.c. with R-19 fiberglass batt, 3 layers of 1/2" Type X gypsum board each side

Material Layers

LayerMaterialThickness
11/2" Type X gypsum board1/2"
21/2" Type X gypsum board1/2"
31/2" Type X gypsum board1/2"
42x6 wood studs at 16" o.c.5.5"
5R-19 fiberglass batt
61/2" Type X gypsum board1/2"
71/2" Type X gypsum board1/2"
81/2" Type X gypsum board1/2"