Home / Assemblies / UL U264
UL U2644-hr Fire RatingWallSTC 58
Steel StudMulti-Layer GypsumFiberglass BattResilient ChannelPartitionHigh STCDesign

Steel Stud Wall — 3 layers 1/2" Type X on resilient channels

UL-listed 4-hour fire-rated steel stud wall assembly. 2-1/2" steel studs at 24" o.c. with R-19 fiberglass batt, 3 layers of 1/2" Type X gypsum board each side on resilient channels.

Cross-Section Diagram

1234567897.88"WALL ASSEMBLYSECTION · NOT TO SCALE9 LAYERSsee legend for ① ② ③
Legend
11/2" Type X gypsum board(1/2")
21/2" Type X gypsum board(1/2")
31/2" Type X gypsum board(1/2")
4Resilient channels at 24" o.c.(7/8")
52-1/2" steel studs at 24" o.c.(2.5")
6R-19 fiberglass batt
71/2" Type X gypsum board(1/2")
81/2" Type X gypsum board(1/2")
91/2" Type X gypsum board(1/2")

Specifications

Fire Rating
4-Hour
STC Rating
STC 58
Load Bearing
No
Total Thickness
6.375"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
U264
Assembly Type
Wall
Test Standard
UL 263
Construction Group
Light Frame
Number of Layers
9 layers

Applicable Codes

IBC 2021 Table 722.1IBC 2024 Table 722.1

Construction Summary

2-1/2" steel studs at 24" o.c. with R-19 fiberglass batt, 3 layers of 1/2" Type X gypsum board each side on resilient channels

Material Layers

LayerMaterialThickness
11/2" Type X gypsum board1/2"
21/2" Type X gypsum board1/2"
31/2" Type X gypsum board1/2"
4Resilient channels at 24" o.c.7/8"
52-1/2" steel studs at 24" o.c.2.5"
6R-19 fiberglass batt
71/2" Type X gypsum board1/2"
81/2" Type X gypsum board1/2"
91/2" Type X gypsum board1/2"