UL U2674-hr Fire RatingWallSTC 58
Steel StudMulti-Layer GypsumFiberglass BattPartitionHigh STCDesign
Steel Stud Wall — 4 layers 1/2" Type X
UL-listed 4-hour fire-rated steel stud wall assembly. 2-1/2" steel studs at 24" o.c. with R-13 fiberglass batt, 4 layers of 1/2" Type X gypsum board each side.
Cross-Section Diagram
Legend
11/2" Type X gypsum board(1/2")
21/2" Type X gypsum board(1/2")
31/2" Type X gypsum board(1/2")
41/2" Type X gypsum board(1/2")
52-1/2" steel studs at 24" o.c.(2.5")
6R-13 fiberglass batt
71/2" Type X gypsum board(1/2")
81/2" Type X gypsum board(1/2")
91/2" Type X gypsum board(1/2")
101/2" Type X gypsum board(1/2")
Specifications
Fire Rating
4-Hour
STC Rating
STC 58
Load Bearing
No
Total Thickness
6.5"
Applicable Codes
IBC 2021 §722IBC 2024 Table 722.1
Construction Summary
2-1/2" steel studs at 24" o.c. with R-13 fiberglass batt, 4 layers of 1/2" Type X gypsum board each side
Material Layers
Important Notice
This assembly listing is for reference only. Always verify against the current UL Product iQ database before specifying in construction documents. Material substitutions may void the fire rating. Consult with a qualified fire protection engineer for project-specific requirements.