B
HomeLibrariesCopilotSearchProjectsBookmarks
FeedbackHelp Desk
Libraries
Building Codes
Code LibraryIBC — BuildingIRC — ResidentialIFC — FireIPC — PlumbingIMC — MechanicalIFGC — Fuel GasIECC — EnergyNEC — ElectricalModel Codes
Specifications
CSI SpecificationsDOT SpecsTransit SpecsUSACE
Standards
TransportationRailroadFire SafetyAccessibilityStructural
Tools & References
DiagramsAssembliesProductsCalculatorsChecklistsPermits
PricingLog in
Home / Assemblies / UL U310
UL U3104-hr Fire RatingWallLoad-BearingSTC 58
Steel StudMulti-Layer GypsumResilient ChannelLoad-Bearing WallHigh STCDesign

Steel Stud Wall — 3 layers 5/8" Type X on resilient channels

UL-listed 4-hour fire-rated steel stud wall assembly. 6" steel studs at 16" o.c., 3 layers of 5/8" Type X gypsum board each side on resilient channels.

Cross-Section Diagram

1234567810.63"WALL ASSEMBLYSECTION · NOT TO SCALE8 LAYERSsee legend for ① ② ③
Legend
15/8" Type X gypsum board(5/8")
25/8" Type X gypsum board(5/8")
35/8" Type X gypsum board(5/8")
4Resilient channels at 24" o.c.(7/8")
56" steel studs at 16" o.c.(6.0")
65/8" Type X gypsum board(5/8")
75/8" Type X gypsum board(5/8")
85/8" Type X gypsum board(5/8")

Specifications

Fire Rating
4-Hour
STC Rating
STC 58
Load Bearing
Yes
Total Thickness
10.625"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
U310
Assembly Type
Wall
Test Standard
UL 263
Construction Group
Light Frame
Number of Layers
8 layers

Applicable Codes

IBC 2024 Table 722.1IBC 2021 §722IBC 2021 Table 722.1

Construction Summary

6" steel studs at 16" o.c., 3 layers of 5/8" Type X gypsum board each side on resilient channels

Material Layers

LayerMaterialThickness
15/8" Type X gypsum board5/8"
25/8" Type X gypsum board5/8"
35/8" Type X gypsum board5/8"
4Resilient channels at 24" o.c.7/8"
56" steel studs at 16" o.c.6.0"
65/8" Type X gypsum board5/8"
75/8" Type X gypsum board5/8"
85/8" Type X gypsum board5/8"

Important Notice

This assembly listing is for reference only. Always verify against the current UL Product iQ database before specifying in construction documents. Material substitutions may void the fire rating. Consult with a qualified fire protection engineer for project-specific requirements.