UL U3144-hr Fire RatingWallSTC 51
Steel StudMulti-Layer GypsumResilient ChannelPartitionDesign
Steel Stud Wall — 4 layers 5/8" Type C on resilient channels
UL-listed 4-hour fire-rated steel stud wall assembly. 6" steel studs at 16" o.c., 4 layers of 5/8" Type C gypsum board each side on resilient channels.
Cross-Section Diagram
Legend
15/8" Type C gypsum board(5/8")
25/8" Type C gypsum board(5/8")
35/8" Type C gypsum board(5/8")
45/8" Type C gypsum board(5/8")
5Resilient channels at 24" o.c.(7/8")
66" steel studs at 16" o.c.(6.0")
75/8" Type C gypsum board(5/8")
85/8" Type C gypsum board(5/8")
95/8" Type C gypsum board(5/8")
105/8" Type C gypsum board(5/8")
Specifications
Fire Rating
4-Hour
STC Rating
STC 51
Load Bearing
No
Total Thickness
11.875"
Applicable Codes
IBC 2021 Table 722.1IBC 2024 §722
Construction Summary
6" steel studs at 16" o.c., 4 layers of 5/8" Type C gypsum board each side on resilient channels
Material Layers