Home / Assemblies / UL W162
UL W1624-hr Fire RatingFloor/CeilingLoad-BearingSTC 58
Wood JoistMulti-Layer GypsumFiberglass BattHigh STCDesign

Wood Joist Floor/Ceiling — 4 layers 5/8" Type X gypsum board

UL-listed 4-hour fire-rated wood joist floor/ceiling assembly. TJI wood I-joists at 24" o.c. with R-38 fiberglass batt, 4 layers of 5/8" Type X gypsum board ceiling.

Cross-Section Diagram

12345678FLOOR/CEILING ASSEMBLYSECTION · NOT TO SCALE8 LAYERSsee legend for ① ② ③
Legend
1Floor covering(varies)
23/4" OSB subfloor(3/4")
3TJI wood I-joists at 24" o.c.(11.875")
4R-38 fiberglass batt
55/8" Type X gypsum board(5/8")
65/8" Type X gypsum board(5/8")
75/8" Type X gypsum board(5/8")
85/8" Type X gypsum board(5/8")

Specifications

Fire Rating
4-Hour
STC Rating
STC 58
Load Bearing
Yes
Total Thickness
15.88"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
W162
Assembly Type
Floor/Ceiling
Test Standard
ASTM E119
Construction Group
Light Frame
Number of Layers
8 layers

Applicable Codes

NFPA 5000IBC 2021 Table 722.1

Construction Summary

TJI wood I-joists at 24" o.c. with R-38 fiberglass batt, 4 layers of 5/8" Type X gypsum board ceiling

Material Layers

LayerMaterialThickness
1Floor coveringvaries
23/4" OSB subfloor3/4"
3TJI wood I-joists at 24" o.c.11.875"
4R-38 fiberglass batt
55/8" Type X gypsum board5/8"
65/8" Type X gypsum board5/8"
75/8" Type X gypsum board5/8"
85/8" Type X gypsum board5/8"

Important Notice

This assembly listing is for reference only. Always verify against the current UL Product iQ database before specifying in construction documents. Material substitutions may void the fire rating. Consult with a qualified fire protection engineer for project-specific requirements.