Home / Assemblies / UL D145
UL D1454-hr Fire RatingFloor/CeilingLoad-BearingSTC 47
Steel JoistMulti-Layer GypsumFiberglass BattDesign

Steel Joist Floor/Ceiling — 4 layers 5/8" Type X gypsum board

UL-listed 4-hour fire-rated steel joist floor/ceiling assembly. C-channel steel joists at 16" o.c. with R-19 fiberglass batt, 4 layers of 5/8" Type X gypsum board ceiling.

Cross-Section Diagram

12345678FLOOR/CEILING ASSEMBLYSECTION · NOT TO SCALE8 LAYERSsee legend for ① ② ③
Legend
1Floor covering(varies)
23" concrete on steel deck(3")
3C-channel steel joists at 16" o.c.(10.0")
4R-19 fiberglass batt
55/8" Type X gypsum board(5/8")
65/8" Type X gypsum board(5/8")
75/8" Type X gypsum board(5/8")
85/8" Type X gypsum board(5/8")

Specifications

Fire Rating
4-Hour
STC Rating
STC 47
Load Bearing
Yes
Total Thickness
14"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
D145
Assembly Type
Floor/Ceiling
Test Standard
UL 263
Construction Group
Non-Combustible
Number of Layers
8 layers

Applicable Codes

IBC 2021 §722IBC 2024 §722

Construction Summary

C-channel steel joists at 16" o.c. with R-19 fiberglass batt, 4 layers of 5/8" Type X gypsum board ceiling

Material Layers

LayerMaterialThickness
1Floor coveringvaries
23" concrete on steel deck3"
3C-channel steel joists at 16" o.c.10.0"
4R-19 fiberglass batt
55/8" Type X gypsum board5/8"
65/8" Type X gypsum board5/8"
75/8" Type X gypsum board5/8"
85/8" Type X gypsum board5/8"