Home / Assemblies / UL U201
UL U2011.5-hr Fire RatingWallSTC 44
Steel StudGypsum BoardFiberglass BattPartitionDesign

Steel Stud Wall — single layer 1/2" Type X

UL-listed 1.5-hour fire-rated steel stud wall assembly. 3-5/8" steel studs at 24" o.c. with R-19 fiberglass batt, single layer of 1/2" Type X gypsum board each side.

Cross-Section Diagram

12346.13"WALL ASSEMBLYSECTION · NOT TO SCALE4 LAYERSsee legend for ① ② ③
Legend
11/2" Type X gypsum board(1/2")
23-5/8" steel studs at 24" o.c.(3.625")
3R-19 fiberglass batt
41/2" Type X gypsum board(1/2")

Specifications

Fire Rating
1.5-Hour
STC Rating
STC 44
Load Bearing
No
Total Thickness
4.625"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
U201
Assembly Type
Wall
Test Standard
CAN/ULC-S101
Construction Group
Light Frame
Number of Layers
4 layers

Applicable Codes

IBC 2021 Table 722.1

Construction Summary

3-5/8" steel studs at 24" o.c. with R-19 fiberglass batt, single layer of 1/2" Type X gypsum board each side

Material Layers

LayerMaterialThickness
11/2" Type X gypsum board1/2"
23-5/8" steel studs at 24" o.c.3.625"
3R-19 fiberglass batt
41/2" Type X gypsum board1/2"