Home / Assemblies / UL U294
UL U2941-hr Fire RatingWallSTC 57
Steel StudGypsum BoardMineral WoolResilient ChannelPartitionHigh STCDesign

Steel Stud Wall — single layer 1/2" Type X on resilient channels

UL-listed 1-hour fire-rated steel stud wall assembly. 6" steel studs at 16" o.c. with R-15 mineral wool batt, single layer of 1/2" Type X gypsum board each side on resilient channels.

Cross-Section Diagram

123459.38"WALL ASSEMBLYSECTION · NOT TO SCALE5 LAYERSsee legend for ① ② ③
Legend
11/2" Type X gypsum board(1/2")
2Resilient channels at 24" o.c.(7/8")
36" steel studs at 16" o.c.(6.0")
4R-15 mineral wool batt
51/2" Type X gypsum board(1/2")

Specifications

Fire Rating
1-Hour
STC Rating
STC 57
Load Bearing
No
Total Thickness
7.875"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
U294
Assembly Type
Wall
Test Standard
UL 263
Construction Group
Light Frame
Number of Layers
5 layers

Applicable Codes

IBC 2021 §722IRC R302.1

Construction Summary

6" steel studs at 16" o.c. with R-15 mineral wool batt, single layer of 1/2" Type X gypsum board each side on resilient channels

Material Layers

LayerMaterialThickness
11/2" Type X gypsum board1/2"
2Resilient channels at 24" o.c.7/8"
36" steel studs at 16" o.c.6.0"
4R-15 mineral wool batt
51/2" Type X gypsum board1/2"

Important Notice