B
HomeLibrariesCopilotSearchProjectsBookmarks
FeedbackHelp Desk
Libraries
Building Codes
Code LibraryIBC — BuildingIRC — ResidentialIFC — FireIPC — PlumbingIMC — MechanicalIFGC — Fuel GasIECC — EnergyNEC — ElectricalModel Codes
Specifications
CSI SpecificationsDOT SpecsTransit SpecsUSACE
Standards
TransportationRailroadFire SafetyAccessibilityStructural
Tools & References
DiagramsAssembliesProductsCalculatorsChecklistsPermits
PricingLog in
Home / Assemblies / UL U342
UL U3423-hr Fire RatingWallSTC 59
Steel StudMulti-Layer GypsumFiberglass BattPartitionHigh STCDesign

Shaft Wall — 2 layers 5/8" Type X

UL-listed 3-hour fire-rated shaft wall assembly. 3-5/8" CT studs at 24" o.c. with R-11 fiberglass batt, 2 layers of 5/8" Type X gypsum board each side.

Cross-Section Diagram

1234567.63"WALL ASSEMBLYSECTION · NOT TO SCALE6 LAYERSsee legend for ① ② ③
Legend
15/8" Type X gypsum board(5/8")
25/8" Type X gypsum board(5/8")
33-5/8" CT studs at 24" o.c.(3.625")
4R-11 fiberglass batt
55/8" Type X gypsum board(5/8")
65/8" Type X gypsum board(5/8")

Specifications

Fire Rating
3-Hour
STC Rating
STC 59
Load Bearing
No
Total Thickness
6.125"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
U342
Assembly Type
Wall
Test Standard
UL 263
Construction Group
Concrete/Masonry
Number of Layers
6 layers

Applicable Codes

IBC 2021 §722IBC 2021 Table 722.1

Construction Summary

3-5/8" CT studs at 24" o.c. with R-11 fiberglass batt, 2 layers of 5/8" Type X gypsum board each side

Material Layers

LayerMaterialThickness
15/8" Type X gypsum board5/8"
25/8" Type X gypsum board5/8"
33-5/8" CT studs at 24" o.c.3.625"
4R-11 fiberglass batt
55/8" Type X gypsum board5/8"
65/8" Type X gypsum board5/8"

Important Notice

This assembly listing is for reference only. Always verify against the current UL Product iQ database before specifying in construction documents. Material substitutions may void the fire rating. Consult with a qualified fire protection engineer for project-specific requirements.