Home / Assemblies / UL U101
UL U1011-hr Fire RatingWallLoad-BearingSTC 55
Wood StudGypsum BoardFiberglass BattResilient ChannelLoad-Bearing WallHigh STCDesign

Wood Stud Wall — single layer 1/2" Type X on resilient channels

UL-listed 1-hour fire-rated wood stud wall assembly. 2x4 wood studs at 16" o.c. with R-13 fiberglass batt, single layer of 1/2" Type X gypsum board each side on resilient channels.

Cross-Section Diagram

123456.88"WALL ASSEMBLYSECTION · NOT TO SCALE5 LAYERSsee legend for ① ② ③
Legend
11/2" Type X gypsum board(1/2")
2Resilient channels at 24" o.c.(7/8")
32x4 wood studs at 16" o.c.(3.5")
4R-13 fiberglass batt
51/2" Type X gypsum board(1/2")

Specifications

Fire Rating
1-Hour
STC Rating
STC 55
Load Bearing
Yes
Total Thickness
5.375"
Source / Publisher
UL (Underwriters Laboratories)
Design Number
U101
Assembly Type
Wall
Test Standard
ASTM E119
Construction Group
Light Frame
Number of Layers
5 layers

Applicable Codes

IBC 2024 Table 722.1IBC 2021 §722IBC 2021 Table 722.1

Construction Summary

2x4 wood studs at 16" o.c. with R-13 fiberglass batt, single layer of 1/2" Type X gypsum board each side on resilient channels

Material Layers

LayerMaterialThickness
11/2" Type X gypsum board1/2"
2Resilient channels at 24" o.c.7/8"
32x4 wood studs at 16" o.c.3.5"
4R-13 fiberglass batt
51/2" Type X gypsum board1/2"

Important Notice