UL U2603-hr Fire RatingWallLoad-BearingSTC 63
Steel StudMulti-Layer GypsumMineral WoolResilient ChannelLoad-Bearing WallHigh STCDesign
Steel Stud Wall — 3 layers 5/8" Type C on resilient channels
UL-listed 3-hour fire-rated steel stud wall assembly. 2-1/2" steel studs at 24" o.c. with R-15 mineral wool batt, 3 layers of 5/8" Type C gypsum board each side on resilient channels.
Cross-Section Diagram
Legend
15/8" Type C gypsum board(5/8")
25/8" Type C gypsum board(5/8")
35/8" Type C gypsum board(5/8")
4Resilient channels at 24" o.c.(7/8")
52-1/2" steel studs at 24" o.c.(2.5")
6R-15 mineral wool batt
75/8" Type C gypsum board(5/8")
85/8" Type C gypsum board(5/8")
95/8" Type C gypsum board(5/8")
Specifications
Fire Rating
3-Hour
STC Rating
STC 63
Load Bearing
Yes
Total Thickness
7.125"
Applicable Codes
IBC 2021 Table 722.1IRC R302.1
Construction Summary
2-1/2" steel studs at 24" o.c. with R-15 mineral wool batt, 3 layers of 5/8" Type C gypsum board each side on resilient channels
Material Layers
Important Notice
This assembly listing is for reference only. Always verify against the current UL Product iQ database before specifying in construction documents. Material substitutions may void the fire rating. Consult with a qualified fire protection engineer for project-specific requirements.