UL U3361.5-hr Fire RatingWallSTC 47
Steel StudGypsum BoardFiberglass BattPartitionDesign
Shaft Wall — single layer 5/8" Type X
UL-listed 1.5-hour fire-rated shaft wall assembly. 3-5/8" CT studs at 24" o.c. with R-11 fiberglass batt, single layer of 5/8" Type X gypsum board each side.
Cross-Section Diagram
Legend
15/8" Type X gypsum board(5/8")
23-5/8" CT studs at 24" o.c.(3.625")
3R-11 fiberglass batt
45/8" Type X gypsum board(5/8")
Specifications
Fire Rating
1.5-Hour
STC Rating
STC 47
Load Bearing
No
Total Thickness
4.875"
Applicable Codes
IRC R302.1IBC 2024 §722IBC 2024 Table 722.1
Construction Summary
3-5/8" CT studs at 24" o.c. with R-11 fiberglass batt, single layer of 5/8" Type X gypsum board each side
Material Layers
Important Notice
This assembly listing is for reference only. Always verify against the current UL Product iQ database before specifying in construction documents. Material substitutions may void the fire rating. Consult with a qualified fire protection engineer for project-specific requirements.