Occupant Load & Egress Width Calculator

Occupant load per IBC Table 1004.5, then the egress width and exit count that load requires under IBC 1005.3 and Table 1006.2.1. Add a row per space — a mixed-function floor is calculated space by space, each rounded up on its own, then summed.

Spaces

Sets the single-exit threshold in Table 1006.2.1

903.3.1.1/903.3.1.2 and907.5.2.2 — sprinklers alone don’t qualify

Results

Business areas4,500 sq ft gross ÷ 150 = 30.00, rounded up30
Assembly without fixed seats — Unconcentrated (tables and chairs)900 sq ft net ÷ 15 = 60.00, rounded up60
Total occupant load90

Stairway width

27 in

90 × 0.3 in — IBC 1005.3.1

Doors & corridors

18 in

90 × 0.2 in — IBC 1005.3.2

Exits required

2

One exit allowed to 49 occupants

Reference only. This covers the base calculation. It does not apply fixed-seating provisions (1004.6), concentrated business use (1004.8), multiple-story convergence, smoke-protected assembly seating, minimum component widths, or the effect of losing one exit. Verify with the adopted code edition and your building department.