Occupant load per IBC Table 1004.5, then the egress width and exit count that load requires under IBC 1005.3 and Table 1006.2.1. Add a row per space — a mixed-function floor is calculated space by space, each rounded up on its own, then summed.
Business areas4,500 sq ft gross ÷ 150 = 30.00, rounded up
30
Assembly without fixed seats — Unconcentrated (tables and chairs)900 sq ft net ÷ 15 = 60.00, rounded up
60
Total occupant load
90
Stairway width
27 in
90 × 0.3 in — IBC 1005.3.1
Doors & corridors
18 in
90 × 0.2 in — IBC 1005.3.2
Exits required
2
One exit allowed to 49 occupants
Reference only. This covers the base calculation. It does not apply fixed-seating provisions (1004.6), concentrated business use (1004.8), multiple-story convergence, smoke-protected assembly seating, minimum component widths, or the effect of losing one exit. Verify with the adopted code edition and your building department.