Stair Code Requirements — Rise, Run, Width & Headroom
Residential stairs are governed by four numbers most builders can recite: 7-3/4, 10, 36, and 6-8. Miss the uniformity tolerance, though, and a stair that meets all four still fails.
Worth knowing
- The commercial (IBC) standard is stricter — 7 in. max rise, 11 in. min tread — which is why "code stairs" answers online conflict.
- Spiral stairs have their own allowances: 26 in. clear width, 6-3/4 in. tread at the 12-in. walkline, 9-1/2 in. max rise (R311.7.10.1).
- The 3/8-in. uniformity rule is the most common stair failure — check the first and last riser after flooring changes.
- Winder treads need 10 in. at the 12-in. walkline and 6 in. minimum at any point.
Common questions
What does the code say about maximum riser height for Stairs?
7-3/4 in., measured vertically between nosings. (IRC R311.7.5.1)
What does the code say about minimum tread depth for Stairs?
10 in., measured nosing to nosing. (IRC R311.7.5.2)
What does the code say about uniformity for Stairs?
Largest riser or tread may not exceed the smallest by more than 3/8 in.. (IRC R311.7.5.1, R311.7.5.2)
Adopted edition by state
Base-code year from BuildSpec’s adoption records. States often amend the base code, and your city or county may differ, so confirm with your building department.
Related sections and guides
This guide is BuildSpec’s own summary, not code text. It cites the 2021 International Residential Code and the 2023 National Electrical Code as model standards. The IRC 2021 text itself is in the Code Library for signed-in members; BuildSpec publishes no NEC text, which is at nfpa.org.Neither is an adoption record: your state may be on a different edition with amendments — check your jurisdiction page or get an Address Report.