Home / Products / Div 26 05 19 — 26 05 19 / Copper 600/1000V XLPE-insulated Type XHHW-2 tray cable, PVC jacket (Type TC-ER)
Div 26 05 19 · 26 05 19
Copper 600/1000V XLPE-insulated Type XHHW-2 tray cable, PVC jacket (Type TC-ER)
Southwire · SPEC 45052
BuildSpec summary written from the manufacturer spec sheet retrieved 2026-09-24. Conductor is bare copper, 7-strand Class B compressed, built to ASTM B3 and ASTM B8. Insulation is XLPE at 30 mils carrying a VW-1 flame rating. Jacket is PVC at 45-80 mils depending on conductor count. Emergency overload 130 degrees C; short circuit 250 degrees C. The sheet states suitability for Class I, II and III Division 2 hazardous locations by reference to NEC Articles 501 and 502. No marketing copy is reproduced and no document is rehosted.
✓ Verified 2026-09-24
Certifications & Standards
Attributes — product claims, not third-party certifications
Type XHHW-2Type TC-ERcable tray ratedsunlight resistantdirect burialsilicone freeVW-1
Sustainability
No sustainability metrics on file for this product.
Applies to Code Sections
Code sections where this product or product category is relevant. Click through to the viewer for full text and commentary.
insulated wire and cablepower and control tray cablewet and dry locationsdirect burial