B
HomeLibrariesCopilotSearchProjectsBookmarks
FeedbackHelp Desk
Libraries
Building Codes
Code LibraryIBC — BuildingIRC — ResidentialIFC — FireIPC — PlumbingIMC — MechanicalIFGC — Fuel GasIECC — EnergyNEC — ElectricalModel Codes
Specifications
CSI SpecificationsDOT SpecsTransit SpecsUSACE
Standards
TransportationRailroadFire SafetyAccessibilityStructural
Tools & References
DiagramsAssembliesProductsCalculatorsChecklistsPermits
PricingLog in

735DETECTORS

AZ · 2021 Standard SpecificationsBook pages View official source ↗

925 734- 3.04 Cabinet Wiring Diagrams: Each controller cabinet assembly shall have a complete set of wiring diagrams which shall show the intersection plan, signal phasing layout, and all control device connections. Two sets of the final wiring diagrams and a second original shall be required with delivery with each control cabinet assembly. The second original shall be a legible reproducible linen cloth, mylar film, or polyester film. Each controller cabinet shall be furnished with a sheet metal wiring diagram print holder. The minimum size of the print holder shall be not less than 9 inches wide by 8 inches high by 1- 1/4 inches deep, mounted inside. 734- 3.05 Cabinet Foundations: Before the concrete for cabinet foundations has set, depressions shall be made around the anchor bolts for adjustment of the cabinet leveling nuts. Cabinet foundations shall be 4 inches above ground level. 734- 4 Method of Measurement: Traffic signal contr ol cabinets and meter pedestal cabinets will be measured as a unit for each controller assembly or control cabinet furnished and installed. 734- 5 Basis of Payment: The accepted quantities of traffic signal control cabinets and meter pedestal cabinets, meas ured as provided above, will be paid for at the contract unit price each for the type controller assembly or control cabinet designated in the bidding schedule, complete in place, which price shall be full compensation for the work described and specified herein and on the plans, including service terminal boxes, cabinet mounted service enclosures, meter sockets, breaker panels, foundations, conduit, elbows, anchor bolts, clearance pad, auxiliary signal controls, external logic modules and all other compone nts necessary to provide a complete functional assembly for controlling the operation and timing of traffic control signals. 735- 1 Description: The work under this section shall co nsist of furnishing and installing traffic signal loops, preformed loop detectors, complete or partial traffic data loop and weigh- in-motion (WIM) systems, and pedestrian detectors TABLE OF CONTENTS INDEX 926 at the locations shown on the project plans and in accordance wit h the details shown on the plans and the requirements of the specifications. 735- 2 Materials: 735- 2.01 Vehicle Detectors:

(A)General:

Detectors shall conform to the minimum acceptable design and operating requirements of these specifications for detecting the presence, passage, speed, weight, and classification of vehicles. Except as specified in Subsection 735- 2.01(F) of the specifications, all materials shall be furnished by the contractor. The contractor shall submit a complete list of all required project material for approval, as specified in Subsection 730- 4 of the specifications.

(B)Loop Detectors:

The detector loop dimensions shall be as specified on the Standard Drawings . Loop detector wire shall be 14 AWG HDPE polyethylene insulated conductors conforming to IMSA 51- 7, as shown on the Standard Drawings.

(C)Lead -in Cable:

For Type SA and SB speed/classification detectors specified in Subsection 735- 3.02(D) of the specifications, lead -in cable from the pull box to the cabinet shall conform to IMSA specification 50- 2, except as modified on the Standard Drawings.

(D)Conduit:

Conduit shall be rigid nonmetallic PVC conforming to the requirements of Subsection 732- 2.02 of the specifications. Conduit shall be large enough to contain the number of wires required, but not less than the diameters shown on the Standard Drawings.

(E)Cabinets:

Traffic monitoring site cabinets for Type SA and SB speed/classification and WIM detectors shall be pole- mounted Type MPD control cabinets as shown on the Standard Drawings, and as specified in Subsection 734- 2.03 of the specifications, except that no pre- wiring for AC or DC electric, police panel, or provisions for fan or light shall be required. Warranties shall comply with Subsection 106.13 of the specifications. TABLE OF CONTENTS INDEX 927

(F)Department Furnished Materials:

When required, the Department will furnish detectors for speed/classification systems (piezoelectric sensors -Class 2) and weigh- in-motion systems (piezoelectric sensors– Class1, or quartz piezoelectri c sensors) with pre- attached lead -in cables. For such installations, the Department will also furnish the piezo grout sealant for the sensor portion of speed/classification and weigh- in-motion detectors. The contractor shall furnish all other sealants. The contractor shall notify the Traffic Monitoring Team of the Multimodal Planning Division (MPD) at (602) 712- 8598 a minimum of 15 working days prior to scheduled installation of the Department -furnished piezoelectric sensors. The required sensors and gr out will be provided at the Department’s central Phoenix location, at 2501 W. Georgia, Phoenix, AZ 85017, or at the appropriate District Office, as specified by the Department at the time of contact. 735- 2.02 Pedestrian Push -Button Detectors: The pedestrian detector shall be a push -button switch mounted i nside an approved push -button housing , as shown on the Standard Drawings. Pedestrian push- button signs shall be made with porcelain enameled 20 gage sheet steel, 9 inches by 12 inches in size. Corners of the sign shall be finished round for safety and neat appearance. Each hole shall be provided with a brass grommet. Instructions on the signs shall be black enameled letters or symbols on a white enamel background. The legend shall be as shown on the plans or as specified in the Special Provisions. 735- 2.03 Blank : 735- 2.04 Saw Cut Sealant: Saw cut sealants shall be a fle xible encapsulant intended for sealing and protecting vehicle detector loop wires installed in saw cuts.

(A)Two -Part Epoxy Filler Sealant :

Two -part epoxy joint filler sealant shall be a 100- percent solids, flexible, two-component, solvent free, epoxy resin/hardener system for use as a saw cut sealant in asphaltic concrete pavements and Portland cement concrete pavements. Materials shall comply with the requirements of Subsection 1015- 1 of the specifications. TABLE OF CONTENTS INDEX 928 The epoxy system shall be specifically designed for the intended application according to the product literature provided by the manufacturer. The epoxy system shall be of sufficient strength and hardness to withstand stress and abrasion from vehicular traffic, while remaining flexible enough to provide stress relief under thermal movement and protect the loop wire from moisture penetration. It shall also be moisture insensitive to allow effective application to damp pavements. No standing water is permitted on the surfaces to which the epoxy system is to be applied. The epoxy system shall be designed to enable vehicular traffic to pass over properly filled saw cuts immediately after installation without tracking or stringing of the material. Properly installed and cured epoxy systems shall exhibit resistance to the effects of weather, motor oi ls, gasoline, anti -freeze solution, brake fluid, deicing chemicals, and salt in such a manner that the performance of the vehicle detector loop wire is not adversely affected. The epoxy system shall be designed for roadway installation when the surface tem perature is a minimum of 40 degrees F and rising. The cured epoxy system shall be temperature stable and exhibit no degradation in performance throughout the ambient pavement temperature ranges experienced within the State of Arizona. The components of the epoxy system shall have a minimum shelf life of 12 months in original unopened, undamaged containers, when stored in a cool dry environment, as recommended by the manufacturer. The epoxy system shall meet the following requirements: Property Test Method Requirements Mixing Ratio; Part A to Part B - 1 to 1 by volume Viscosity, centipoises ASTM D2393 4000 to 8000 Pot Life, minutes ASTM C881 12 to 20 Cure Time, minutes ASTM C679 60 maximum, Tack Free Hardness (Shore D) ASTM D2240 35 to 65 Tensile Elongation, % ASTM D638 50 minimum Water Absorption, % (24 hrs) ASTM D570 1 maximum 3% Salt Water Absorption, % (24 hrs) - 0.03 to 0.20 Oil Absorption, % (24 hrs) ASTM D471 0.01 to 0.02 Gasoline Absorption, % (24 hrs) - 0.05 to 0.90 TABLE OF CONTENTS INDEX 929

(B)One -Part Elastomeric Sealant:

One -part elastomeric sealant may be used to seal saw cuts in Portland cement concrete pavement and lean concrete base. The sealant shall provide compressive yield strength to withstand normal vehicular traffic as well as sufficient flexibility to withstand normal movement in concrete pavements, while protecting the loop wire from moisture penetration. The encapsulant shall be a one- part elastomeric compound requiring no mixing, measuring or application of heat prior to or during its installation. The encapsulant shall, within its stated shelf life in original undamaged packaging, cure only in the presence of moisture. The rate of cure will, therefore, depend upon temperature and relative humidity at the time of installation. Cool dry weather will slow curing whereas warm, humid weather will accelerate curing. The encapsulant shall be designed to enable vehicular traffic to pass over the properly filled saw cut immediately after installation without tracking or stringing of the material. The encapsulant shall form a surface skin allowing exposure to vehicular traffic within 30 minutes at 75 degrees F and completely cure to a tough, rubber -like consistency in two to seven days after installation. Properly installed and cured encapsulant shall exhibit resistance to effects of weather, vehicular abrasion, motor oils, gasoline, anti -freeze solution, brake fluid, deicing chemicals and salt normally encountered, in such a manner that the performance of the vehicle detector loop wire is not adversely affected. The cured encapsulant shall be temperature stable and exhibit no degradation in performance throughout the ambient pavement temperature ranges experienced within the State of Arizona. The encapsulant shall exhibit minimal shrinkage during or after its installation, and in no manner affect the performance characteristics of the material. The encapsulant shall be designed to permit clean- up of material and application equipment , prior to curing of the encapsulant, with a suitable non- flammable solvent. Should any encapsulant material be allowed to cure in the application nozzle, it shall be able to be pulled out as a solid plug. The encapsulant shall have a minimum 12- month shelf life in undamaged original containers when stored in a cool, dry environment. TABLE OF CONTENTS INDEX 930 The encapsulant shall be designed for roadway installation when the surface temperature is between 40 and 140 degrees F. The encapsulant shall have the following physical properties in its uncured and cured states. Uncured (Wet) Encapsulant Property Requirement Test Procedures Weight 10.1 ± 0.3 pounds/gallon A. Weight/Gallon Total Solids by Weight 75 – 85% B. Determination of Non -Volatile Content Viscosity 10,000 - 85,000 centipoise C. Dynamic Viscosity Drying Time Touch: 24 hrs. maximum Complete: 30 hrs. max. D. Tack- Free Time

Cured Encapsulant Property Requirement Test Procedure Hardness

(Indentation)65 - 85 E. Rex hardness

Tensile Strength 500 psi minimum F. Tensile & Elongation Elongation 300% minimum

(C)Hot Applied Rubberized Sealant:

Hot applied rubberized sealant may be used to seal saw cuts in asphaltic concrete and in lean concrete base. It shall be suitable for use as a sealant for traffic loop saw cuts and be non- tracking under traffic. At application temperatures, the traffic loop sealant shall be a thin, free flowing fluid which penetrates saw cuts and self -levels permitting uniform application. The sealant shall be melted and applied to pavements using a pressure feed melter unit. Pour pot application is not acceptable. The sealant shall be a relatively stiff sealant but shall remain flexible at low pavement surface temperatures. The test results shall conform to the following specifications for the loop detector sealant. Test Specification Penetration: 125 °F, 50g, 5s 50 maximum Penetration: 77 °F, 100g, 5s 10 - 25 Softening Point: 210 °F minimum Ductility: 77 °F 15 cm minimum Mandrel Bend: 0 °F, 90 ° Arc, 10s, 3/4 inch diameter Pass 2 of 3 Recommended Pour Temp: 380 °F Safe Heating Temp: 420 °F Brookfield Viscosity: 400 °F 7,500 centipoise max. Unit Weight: 8.5 pounds per gallon Coverage; 1/2 by 1/2 inch crack 11.0 pounds per 100 feet

TABLE OF CONTENTS INDEX 931 735- 3 Construction Requirements: 735- 3.01 Detector Installation:

(A)General:

Detectors shall be installed as shown on the project plans, as shown in the Standard Drawings, and as directed by the Engineer. The installation of the detectors shall be such t hat the operation shall not be affected by temperature changes, water, ice, rain, snow, chemicals, or electromagnetic noise. Vehicle detectors shall be installed prior to any chip seal or friction course for asphaltic concrete pavements, and prior to any f riction course for Portland cement concrete pavements.

(B)Saw Cut Sealants:

Saw cuts shall be sealed as specified in the Standard Drawings, with the following exceptions:

(1)Two -part epoxy filler sealant shall be used instead of

pre-mixed emulsified crack filler sealant ; and

(2)Department -furnished piezo grout shall be used to seal

the piezo sensor portion of speed/classification and weigh -in-motion detectors. Before the sealant sets up, the surplus sealant shall be removed from the road surface without the use of solvents. Sand blotter shall be applied as directed by the Engineer.

(C)Splices:

Except for piezoelectric or quartz piezoelectric sensors, detector sensor conductors shall run continuous and unspliced to the adjacent pull box. Lead- in cables from the controller cabinet shall be spliced to the detector sensor conductors in the pull box. Splicing of the lead- in cables between the controller cabinet and pull box wi ll not be allowed. Piezoelectric sensor and quartz piezoelectric sensor lead- in cables used in speed/classification detectors and weigh- in-motion detectors shall run continuous and unspliced through the pull box to the controller cabinet. Splicing of the lead- in cables will not be allowed. Wire splices in the pull box shall be soldered using resin- core solder with 60 percent tin and 40 percent lead. The splices shall be sealed as specified in the Standard Drawings. A weather proof bond shall form with a dielectric strength of 500 volts per mil, and water absorption shall TABLE OF CONTENTS INDEX 932 be less than 6.5 percent. The detector lead- in cable shield shall only be grounded on one end in the control cabinet.

(D)Detector Loop Field Tests:

Detector loop field tests shall be in accordance with the Standard Drawings. Any loop that fails to meet the specified requirements or cannot be tuned to the Engineer's satisfaction shall be replaced at no additional cost to the Department. For the traffic data detectors specified in Subsection 735 -3.02 of the specifications, the contractor shall submit complete test results to the Engineer electronically within two weeks of completion of the second test. In addition to the electronic submission, the Engineer may request up to three hard copies. The test results shall identify the project number and detector location. For pull boxes used with data detector systems, the contractor shall provide GPS latitude and longitude coordinates, ± 5 feet, for each installed pull box. Such GPS information shall be transmitted along with the test data required above for all pull boxes installed with each tested data detector loop system. 735- 3.02 Traffic Data Detectors:

(A)General:

Counter (Type C), speed/classification (Types SA and SB), and weigh- in-motion (WIM) detector syst ems shall be installed in accordance with the Standard Drawings and as specified herein. The contractor shall use a 3/4- inch wide saw blade to cut the channel for piezoelectric sensors in pavement. Multiple passes using a thinner blade will not be accepta ble. When new conduit is required under any existing pavement, the contractor shall install conduit beneath the roadway using horizontal directional drilling methods approved by the Engineer. Pull boxes shall be as shown on the Standard Drawings. As specified above in Subsection 735- 3.01(D) of the specifications, the contractor shall provide GPS latitude and longitude coordinates, ± 5 feet, for all pull boxes installed with each traffic data detector loop system. TABLE OF CONTENTS INDEX 933

(B)Installation of Piezoelectric Sensors:

The contractor shall install the Department -furnished piezoelectric or quartz piezoelectric sensors, and piezo grout, as specified herein and shown on the plans. A traffic signal technician from the Department must be present during all elements of the piezoelectric sensor installation (to the point where the pre- attached lead- in cable begins), including layout, groove saw -cutting, sensor placement, and application of piezo grout. The contractor shall notify the Engineer at least 15 working days prior to its scheduled installation of any piezoelectric sensors. Any piezoelectric sensor installation work performed without full time inspection by the Department’s traffic signal technician may not be eligible for payment. Lead- in runs of cable from all piezoelectric sensors and quartz piezoelectric sensors to the controller cabinet shall be continuous; splices will not be acceptable.

(C)Traffic Counter Detectors:

A complete new traffic counter system (Type C) shall include all loops and pull boxes for the specific location for both directions of traffic, as shown on the Standard Drawings. A divided roadway shall require a pull box on each shoulder. Loop detector traffic counter systems shall include all necessary conduits from edge of pav ement to the roadside pull box(es). The contractor shall provide a trench and install conduit from the edge of pavement to the pull box. Wiring, conduit, and pull box installation shall be in accordance with Subsections 732- 3.01 and 732- 3.02 of the specif ications. When a full replacement of an existing traffic counter system is indicated on the plans and bidding schedule, the contractor shall remove the existing facilities, and furnish and install new loops, pull boxes, and conduit. The total number of loo ps for each complete traffic counter system specified above (new or full replacement) shall be the number of loops required for all traffic lanes in both travel directions at the specified location.

(D)Speed/Classification Detectors:

A complete new speed/cla ssification system (Type SA or Type SB) shall include all loops, pull boxes, control cabinet, A -pole, pole foundation, the necessary conduits under the roadway and from pull boxes to control cabinets, and Department -furnished piezoelectric sensors with att ached lead- in cables, all as shown on the Standard Drawings. When shown on the plans, an additional control cabinet, pull box, A -pole, and pole foundation shall be required. TABLE OF CONTENTS INDEX 934 The contractor shall provide trenches and install conduits from the edge of pavem ent to the pull box and from the pull box to the control cabinet. Wiring, conduit, and pull box installation shall be in accordance with Subsections 732- 3.01 and 732- 3.02 of the specifications. Installation of Department -furnished piezoelectric sensors shall be in accordance with Subsection 735- 3.02(B) of the specifications. The cabinet(s) shall be grounded in accordance with the requirements of Subsections 732- 3.03 and 734- 3.03 of the specifications. The contractor shall keep the ground wire from the cabinet ground bus bar to the ground rod assembly or array as short as possible. When a full replacement of an existing speed/classification system is indicated on the plans and bidding schedule, the contractor shall remove the existing facilities, and fur nish and install new loops and pull boxes, a new control cabinet, A -pole and foundation, all necessary conduits under the roadway and from pull boxes to control cabinets, and Department -furnished piezoelectric sensors with attached lead- in cables. When shown on the plans, an additional control cabinet, pull - box, A -pole, and pole foundation shall be required. When a partial replacement of an existing speed/classification system is indicated on the plans and bidding schedule, the contractor shall furnish and install new loops and pull boxes, and new Department -furnished piezoelectric sensors with attached lead- in cables. The contractor shall use the existing cabinet(s), A -pole(s) and foundation(s), and all conduit connections under the roadway and from pull boxes to the cabinet. The total number of loops for each complete speed/classification system specified above (new, full replacement, or partial replacement) shall be the number of loops required for all traffic lanes in both travel directions at a specified location.

(E)Weigh -in-Motion (WIM) Detectors:

A complete new weigh- in-motion (WIM) system shall include all loops, pull boxes, control cabinet, A -pole, pole foundation, the necessary conduits under the roadway and from pull boxes to control cabinets, and Department -furnished sensors (piezoelectric or quartz piezoelectric as shown on the plans) with attached lead- in cables, all as shown on the Standard Drawings. When shown on the plans, an additional control cabinet, pull box, A -pole, and pole foundation shall be required. The contractor shall provide trenches and install conduits from the edge of pavement to the pull box and from the pull box to the control cabinet. Wiring, conduit, and pull box installation shall be in accordance with Subsections 732- 3.01 and 732- 3.02 of the specifications. Installation of Department -furnished piezoelectric sensors shall be in accordance with Subsection 735- 3.02(B) of the specifications. TABLE OF CONTENTS INDEX 935 The cabinet(s) shall be grounded in accordance with the requirements of Subsections 732- 3.03 and 734- 3.03 of the specifications. The contractor shall keep the ground wire from the cabinet ground bus bar to the ground rod assembly or array as short as possible. When a full replacement of an existing new WIM system is indicated on the plans and bidding schedule, the contractor shall remove the existing facilities, and furnish and install new loops and pull boxes, a new control cabinet, A -pole and foundation, all necessary conduits under the roadway and from pull boxes to control cabinets, and Department - furnished piezoelectric sensors with attached lead- in cables. When shown on the plans, an additional control cabinet, pull -box, A -pole, and pole foundation shall be required. When a partial replacement of an existing WIM system is indicated on the plans and bidding schedule, the contractor shall furnish and install new loops and pull boxes, and new Department -furnished piezoelectric sensors with attached lead- in cables. The contractor shall use the existing cabinet(s), A -pole(s) and foundation(s), and all conduit connections under the roadway and from pull boxes to the cabinet. The total number of sensors for each complete new WIM system specified above (new, full replacement, or partial replacement) shall be the number of sensors required for all traffic lanes in both travel directions at a specified location. 735- 3.03 Traffic Signal Detectors: Traffic signal detectors shall be as shown on the Standard Drawings, and shall include the specified loop, wiring, and conduit required to terminate the wiring in the pull box. The contractor shall provide a trench and install conduit from the edge of pavement to the pull box. Wiring, conduit, and pull box installation shall be in accordance with Subsections 732- 3.01 and 732- 3.02 of the specifications. 735- 3.04 Preformed Traffic Detectors: Preformed loop detectors for ramp metering and counting shall comply with the Standard Drawings, and shall include the specified loop, wiring, and conduit required to terminate the wiring in the pull box. Preformed loop detectors in Portland cement concrete pavement shall comply with the Standard Drawings, and shall include the specified loop, wiring, and conduit required to terminate the wiring in the pull box. The contractor shall provide a trench and inst all conduit from the edge of pavement to the pull box. Wiring, conduit, and pull box installation shall be in accordance with Subsections 732- 3.01 and 732- 3.02 of the specifications. TABLE OF CONTENTS INDEX 936 Preformed loop detectors in bridge deck shall comply with the Standard Drawings, and shall include the specified loop, wiring, and conduit required to terminate the wiring in the junction box. 735- 4 Method of Measurement: Traffic signal detectors, preformed loop detectors, and pedestrian detectors will be measured as a unit for each type of detector furnished and installed. Traffic data detectors, consisting of counter loop detectors (Type C), speed/classification detectors (Type SA or Type SB), and weigh- in- motion (WIM) detectors will be measured as a complete system for each type of traffic data detector furnished and installed, including all loops required for both directions of traffic. Speed/classification detectors, regardless of type, and weigh- in-motion detectors will be measured as a new system, full system replacement, or partial replacement, as specified herein and indicated on the bidding schedule. Counter detectors will be measured as a new system or full system replacement, as specified herein and indicated on the bidding schedule. Speed/classification and weigh- in-motion detectors that include two cabinets, A -poles, and pole foundations (two- cabinet systems) will also be measured as a complete new system, including all loops in both directions of traffic, regardless of the distance between both directions of traffic. 735- 5 Basis of Payment: Traffic signal detectors, preformed loop detectors, and pedestrian detectors, measured as provided above, will be paid for at the co ntract unit price each for the type detector designated in the bidding schedule, complete in place, which price shall be full compensation for the work described and specified herein and on the plans. Traffic data detectors, measured as provided above, wil l be paid for at the contract unit price for each complete type of data detector system designated in the bidding schedule, complete- in-place, regardless of the number of loops, including all conduit, wiring, pull boxes and, when specified, cabinets, poles, and pole foundations, which price shall be full compensation for the work described and specified herein and on the plans. No measurement or payment will be made for horizontal directional drilling, the cost being considered as included in contract items. TABLE OF CONTENTS INDEX 937 SECTION 736 HIGHWAY LIGHTING : 736- 1 Description: The work under this section shall consist of furnishing and installing or modifying highway lighting systems at the locations shown on the project plans and in accordance with the details shown on the plans and the requirements of these specifications. The work as described above shall include furnishing and installing all materials and equipment designated on the project plans necessary for the installation of future systems. 736- 2 Materials: 736- 2.01 Highway Lighting Materials: Highway lighting materials shall be Light Emitting Diode (LED), conforming to the requirements of this section and be of the type and size specified. The LED shall have a nominal Correlated Color Temperature (CCT) equal to 3,000 degrees K ± 300 degrees K, or as specified in the project plans. LED luminaires shall be listed by a National Recognized Laboratory (NTRL) as defined by US Department of Labor. The testing laboratory must be listed by OSHA in its scope of recognition for the applicable tests being conducted as required by this specification. A list of recognized testing labs for products sold in the United States may be found on the US Department of Labor website at http://www.osha.gov.

(A)Requirements :

Each luminaire shall be furnished with an instruction sheet which clearly shows installation procedures and instructions for adjusting the luminaire. Each luminaire should meet the following requirements:

(1)Listed by NTRL as being in compliance with Underwriters

Laboratories (UL) 1598 and suitable for use in wet locations;

(2)Sha ll have an International Electro- Technical

Commission (IEC) 529 Ingress Protection (IP) 65 or greater for the optical assemblies of the luminaire;

(3)Comply with Electro Magnetic Interference (EMI)

requirements as defined by FCC47 Sub Part 15; CISPR15, CISPR2 2 Class A (120 volt minimum), EN61000- 3-2, -3-3, -4-4, -4-5; TABLE OF CONTENTS INDEX 938

(4)Shall be tested according to the most current version of

Illuminating Engineering Society of North America

(IENSA)LM -79;
(5)Shall have lumen maintenance measured in accordance

with the most current version of IESNA LM -80;

(6)Shall have long term lumen maintenance documented according to most current version of IESNA TM -21; and
(7)Shall have LM -79, LM -80 and in- situ temperature testing

conducted by US Department of Energy Lighting Facts Program LED Lighting Facts approved testing laboratories.

(B)Lumin aire Housing:

The luminaire housing shall be made of cast aluminum grade A383, A380 or A360, and painted to increase corrosion resistance; the color of the paint shall be gray unless specified otherwise. The luminaire housing shall serve as a passive heatsink for the LED array; no fans shall be allowed. All cast aluminum parts shall be subjected to the following tests:

(1)1000 hours salt spray fog exposure in accordance with

ASTM B117; and

(2)Corrosion Resistance Performance test in accordance

with ASTM D1654. The luminaire housing shall be compliant with American National Standard (ANSI) IEEE C136.31, Table 2 Roadway Lighting Equipment - Luminaire Vibration for both normal applications and bridge and overpass applications. Luminaire housing shall be rated IP65 per ANSI C136.37. The luminaire housing shall be designed to allow water shedding. A passive cooling method shall be employed to manage thermal output of LED light engine and power supply. The luminaire housing shall have a label that states operating voltage, wattage and current range. The label must be clearly visible on the inside of the housing. The luminaire housing shall have a National Electrical Manufacturers Association (NEMA) standard decal with black lettering identifying wattage and light type compliant with ANSI C136.15- 2015. Each luminaire shall be furnished with an instruction sheet which clearly shows installation procedures and instructions for proper luminair e aiming adjustments and maintenance instructions. TABLE OF CONTENTS INDEX 939

(C)Electrical Requirements :

The luminaire shall fully operate in a temperature range - 40 degrees C to 40 degrees C ( -40 degrees F to 104 degrees F). The LED engine which is composed of LED modules, optical system, electronic driver and heatsink shall have a minimum expected life of 100,000 hours at 25 degrees C and 70 percent of initial lumen output (L70) as calculated according to TM21- 11. The luminaire shall have an integral dimming electronic driver that will operate for the following voltage ranges, as specified in the project plans:

(1)120 to 240 VAC (rms) ± 10 percent at 60 hertz or the voltage option of 480 VAC (rms) ± 10 percent at 60 hertz,

as specified in the project plans;

(2)The electronic driver shall have the following :
(a)A power factor of .90 or greater at full load;
(b)A total harmonic distortion of 20 percent or less at full load. ANSI C82.77, Harmonic Emission Limits;
(c)Thermal overload protection;
(d)10 kA overload/overcurrent protection;
(e)A shielded and replaceable 20 kV surge protective

device, compliant with ANSI C62.41 Category C; and

(f)NRTL certified dimming driver that is terminated with

quick disconnect wire harnesses. Wire nut termination is not acceptable.

(D)LED Performance Requirements:

The luminaire shall have a minimum luminaire efficacy of 115 lumens/watt at 3,000 degrees K CCT. The luminaire shall meet the chromaticity requirements as follows:

(1)The colors shall conform to the following color regions

based on the 1931 CIE chromaticity diagram ; and

(2)The luminaire shall have a minimum Color Rendering Index (CRI) of 70. Chromaticity as stated above must be

confirmed by an Independent test lab or shown on the LM 79 test report. TABLE OF CONTENTS INDEX 940

(E)Optical Requirements:

The luminaire shall have a completely sealed optical system with an IEC IP rating of 65 or better. The luminaire shall have a light distribution pattern at the road surface that has an evenly dispersed appearance. The luminaire shall not have a perceptible light level flicker to the unaided eye over the voltage range as specified in the Electrical Requirements.

(F)Warranty:

The entire LED unit including auxiliary equipment shall have a factory warranty of five years against defects in workmanship or materials. The warranty shall cover repair or complete replacement.

(G)Light Level Calculations:

The light level calculations shall be performed in accordance with current adopted Roadway Lighting Design Guide by the D epartment or latest IES RP -8, and must be documented through lighting design software using the Light Loss Factor (LLF) equation below: LLF =LLD x LDD x LATF Where: LLD (Lamp Lumen Depreciation Factor) = the specified percentage of LED lumen maintenance at 70,000 hours at 25 degrees C (77 degrees F) from the TM -21 Report LDD (Luminaire Dirt Depreciation) = 0.90 LATF = LED Ambient Temperature Factor The LLD and LATF factors shall correspond to 40 degrees C. The TM -21 Report must show the drive current used for the submitted luminaire. Product submittal shall be accompanied by IESNA TM -21 compliant test reports from a CALiPER qualified or NVLAP accredited testing laboratory for the specific model being submitted. 736- 2.02 Horizontally Mounted LED Luminaries: Horizontally mounted LED luminaries shall meet the requirements of Subsection 736-2.01 of the specifications and as specified herein. The luminaries shall be LED type 15L, 25L, or 40L as specified. Products listed on the Approved Products List (APL) are available on the internet from the ADOT Research Center through its Product Evaluation Program. Luminaries not currently on the APL may be considered, but must be TABLE OF CONTENTS INDEX 941 submitted to and reviewed by the Engineer prior to approval for use on the project. The contractor shall allow sufficient time for review and approval. Based on Type V optical distribution and CCT of 3,000 degrees K: Type 15L is intended to define an LED fixture with lumen output equal or greater than 13000 lum ens but less than type 25L. Type 25L is intended to define an LED fixture with lumen output equal or greater than 21000 lumens but less than type 40L. Type 40L is intended to define an LED fixture with lumen output equal or greater than 29000 lumens .

(A)Luminaire Housing:

The luminaire housing shall have a slip fitter type mounting on nominal 1½ inch (1⅔ inch outside diameter) to 2 inch (2⅜ inch outside diameter) by minimum 4 inch pipe (Tenon); provided with stainless or zinc plated clamps fixed by four 2 inch by ⅜ inch zinc plated hexagonal bolts with spring washers. The housing shall include integral bubble level indicator and enable luminaire tilt adjustment of ± 5 degrees in 2.5 degree increments. The luminaire housing shall allow tool less entr y with a hinged, removable door that opens downward to allow access to electronic components and terminal block. The door shall be secured to prevent accidental opening or dropping. The maximum weights for each type when fully assembled shall be as follows:

(1)Type 15L shall not weigh more than 30 pounds;
(2)Type 25L shall not weigh more than 40 pounds; and
(3)Type 40L shall not weigh more than 45 pounds.

The luminaire housing shall have an Effective Projected Area (EPA) of no more than 1.5 square feet (when viewed from either side or either end). The luminaire housing shall be equipped with a seven- pin photo- electric control receptacle (PECR) conforming to ANSI Standard C136.10, and shall be provided with a shorting cap. TABLE OF CONTENTS INDEX 942

(B)Electrical Requirements:

The terminal block shall be 3- station, tunnel lug terminal board that will accommodate American Wire Gauge (AWG) #6 thru #12.

(C)Optical Requirements:

The luminaire shall have an IESNA Backlight, Up light and Glare (BUG) rating as follows:

(1)Backlight rating shall not exceed 3;
(2)Up light rating shall not exceed 0; and
(3)Glare rating shall not exceed:
(a)3 for Type 15L and 25L; and
(b)4 for Type 40L.

736- 2.03 High Mast LED Luminaries: High mast LED luminaries shall meet the requirements of Subsection 2.01 of the specifications and as specified herein. The luminaries shall be LED, specifically engineered and designed by the manufacturer for high mast lighting applications. Luminaries must be submitted to and reviewed by the Engineer prior to approval for use on the project. The contractor shall allow sufficient time for review and approval.

(A)Luminaire Housing:

The luminaire housing shall have a slip fitter type mounting on nominal 1½ inch (1⅔ inch outside diameter) to 2 inch (2⅜ inch outside diameter) by minimum 4 inch pipe (Tenon); provided with stainless or zinc plated clamps fixed by four 2 inch by ⅜ inch zinc plated hexagonal bolts with spring washers. The housing shall include integral bubble level indicator and enable luminaire tilt adjustment of ± 5 degrees i n 2.5 degrees increments. The luminaire housing shall have a hinged, removable door. The maximum weight for the high mast fixture when fully assembled shall not exceed 60 pounds. The luminaire housing shall have an EPA of no more than 2.1 square feet (when viewed from either side or either end). TABLE OF CONTENTS INDEX 943 The luminaire housing shall be equipped with a seven- pin PECR conforming to ANSI Standard C136.10, and shall be provided with a shorting cap.

(B)Electrical Requirements:

The terminal block shall be 3- station, tunnel lug terminal board that will accommodate AWG #6 thru #12.

(C)Optical Requirements:

The luminaire shall have an IESNA Up light rating of zero. The luminaire shall have a rotatable optics assembly to enable proper light distribution alignment. Optional 90 degree, 120 degree, and 180 degree shields shall be available for the luminaire upon request. 736- 2.04 Vertically Mounted LED Luminaries: Vertically mounted LED luminaries shall meet the requirements of Subsection 736-2.01 of the specifications and as specified herein. Vertically mounted luminaire shall be a pole- top-type fixture and shall be mounted with a vertical slip fitter, designed to illuminate roadways from offsets of up to 50 feet.

(A)Luminaire Housing:

The luminaire housing shall have a hinged, removable door. The maximum weight for the high mast fixture when fully assembled shall not exceed 55 pounds. The luminaire housing shall have a maximum EPA of no more than 3.5 square feet when tilted 45 degrees. The luminaire housing shall be equipped with a seven- pin PECR conforming to ANSI Standard C136.10, and shall be provided with a shorting cap.

(B)Mounting:

The luminaire housing shall have a slip fitter mounting on nominal 1- 1/2 inch (1- 2/3 inch outside diameter) to 2- 1/2 inch (2- 7/8 inch outside diameter) by 5 inch pipe (Tenon); provided with stainless or zinc plated clamps fixed by four 2 inch by 3/8 inch zinc plated hexagonal bolts with spring washers. TABLE OF CONTENTS INDEX 944 The slip fitter mounting shall be equipped with a swivel joint support that enables tilting the fixture from 0 degrees to 45 degrees supplied with tilt angle indicator to enable correct aiming.

(C)Electrical Requirements:

The terminal block shall be 3- station, tunnel lug terminal board that will accommodate AWG #6 thru #12.

(D)Optical Requirements:

At horizontal position, 0 degree tilt angle, the luminaire shall have zero up light. Optional shields shall be available for the luminaire upon request; the shields shall be mountable to sides, front and back of the fixture. 736- 2.05 Underde ck Diode LED Luminaries: Underdeck diode LED luminaries shall meet the requirements of Subsection 736-2.01 of the specifications and as specified herein. The luminaries shall be LED, specifically engineered and designed by the manufacturer for ceiling or w all mount type applications for underdeck lighting that is purposed to operate during dark hours. Luminaries shall be submitted to and reviewed by the Engineer prior to approval for use on the project. The contractor shall allow sufficient time for review and approval.

(A)Luminaire Housing:

The luminaire housing shall have glass lens and hinged, removable door that opens downward to allow access to electronic components and terminal block. The door shall be secured to prevent accidental opening or dropping. The underdeck luminaire housing shall be painted bronze or dark bronze. Maximum luminaire weight shall not exceed 50 pounds.

(B)Mounting:

The luminaire housing shall be designed to mount directly on a wall or ceiling for surface wiring or over a recessed outlet box for embedded wiring. All mounting hardware shall be made from corrosion resistant material. Grommets shall be installed for all cable entry holes.

(C)Electrical Requirements:

The terminal block shall be 3- station, tunnel lug terminal board that will accommodate AWG #6 thru #12. TABLE OF CONTENTS INDEX 945 736- 2.06 Lighting Controls

(A)Photo Electric Controls

The photo electric controls, hereinafter referred to as PEC, shall comply with the electrical requirements specified in the standard drawings. The nominal dimensions shall be as shown on the standard drawings. The operating temperature range shall be from - 40 to +158 degrees F with zero to 100 percent relati ve humidity. A time delay shall be incorporated into the circuit to prevent the lights from being turned off at night by transient lights which might be focused on the control. The PEC shall be a conventional glass faced, hermetically sealed cell. A swit ch to permit manual operation of the lighting circuit shall be provided for each PEC. The PEC shall work in conjunction with an external auxiliary load relay for handling the required lighting loads unless specified otherwise. The PEC shall have a built -in lightning arrester and inrush current protection. The encapsulated surge protector shall have a spark- over value of 2 kilovolts and shall interrupt up to 10 kiloamperes of follow - through current without affecting the operating characteristics. Voltage R ating : 120 to 277 volts AC, 60 hertz Load Rating: 8 A LED Turn on: 1.5, ±0.5 foot candles. Turn off: 2.25 foot candles Time delay: 2 to 5 Seconds Fail Mode: ON Power Consumption: Less than 0.65 W Water ingress protection: NEMA 3, raintight Life rated at full load: No less than 10,000 On- Off operations. Regulatory Listings shall include: ANSI C131.10 and RoHS compliant ; UL 773 certified; and Tested to NEMA 410 LED Load Standards.

(B)Auxiliary Contactor

Unless otherwise specified, an auxiliary contactor shall be used in conjunction with a PEC to control the required lighting loads. The contactor shall have contacts rated to switch the specified lighting loads and shall be normally open. The contactor shall be single -pole or double- pole as required. The contactor shall be installed as shown on the plans. TABLE OF CONTENTS INDEX 946

(C)Manual -Off-Photo Switch:

A manual -off-photo switch shall be installed, as shown on the Standard Drawing to manually activate the contactor to turn the lights on or off. The switch shall be the toggle- type having double- pole, double- throw contacts with the center position being the "off" position, and be rated at 10 amperes at 250 volts A.C. The switch shall be manually activated in the up position and shall be activated by the PEC in the down position. 736- 2.07 Load Center Cabinets: Load Center cabinets, including pole mounted cabinets shall have photoelectric controls and shall also include a concrete foundation, conduit stub- outs, meter socket, rigid metal conduit riser, cabinet housing, panel, br eakers, contactor, selection switch, fuses, dry transformer, internal wiring and other incidentals in accordance with the project plans and these specifications. The load center cabinet housing shall be of NEMA 3 R weather resistant construction and UL 508 listed. The cabinet and doors shall be made from ⅛ inch thick, 5052 -H32 aluminum with mill finish. All exterior cabinets shall have continuous welding and be free of burrs. The cabinet top shall be sloped to prevent water accumulation; and shall be constructed to allow proper ventilation and be equipped with a washable or replaceable air filter. Doors shall be attached using continuous hinges, equipped Corbin locks, and keyed #2 with two keys. Doors shall also be equipped with two position door stops, three- point door latch with rollers for top and bottom strikes and pad -lockable handles. Circuit breakers shall be molded case, thermal magnetic, bolt -on or plug - in type and shall be U.L. listed. Load center cabinets shall have a dead front panel to isolate all live electrical circuitry. The panel shall be fabricated from aluminum sheeting and shall be painted the same as the cabinet. The dead front panels shall be hinged on one side and securely fastened on the other with bolts. Switches, breakers and other components shall have openings to operate from the front panel. 736- 3 Construction Requirements: Each LED light shall be installed as a complete unit. The contractor shall maintain full nighttime operation of the existing lighting system during the duration of the construction project , unless otherwise approved by the Engineer . 736- 4 Method of Measurement: Luminaires will be measured as a unit for each luminaire furnished, installed, and operational . TABLE OF CONTENTS INDEX

Source: Arizona Standard Specifications for Road and Bridge Construction, 2021 Edition. Pages of 1,296.