B
HomeLibrariesCopilotSearchProjectsBookmarks
FeedbackHelp Desk
Libraries
Building Codes
Code LibraryIBC — BuildingIRC — ResidentialIFC — FireIPC — PlumbingIMC — MechanicalIFGC — Fuel GasIECC — EnergyNEC — ElectricalModel Codes
Specifications
CSI SpecificationsDOT SpecsTransit SpecsUSACE
Standards
TransportationRailroadFire SafetyAccessibilityStructural
Tools & References
DiagramsAssembliesProductsCalculatorsChecklistsPermits
PricingLog in
Division X — Electrical Work

87ELECTRICAL SYSTEMS

CA · 2024 Standard SpecificationsBook pages 12131253View official source ↗

87 ELECTRICAL SYSTEMS

87-1 General

87-1.01 General

87-1.01A Summary

Section 87 -1 includes general specifications for constructing and installing electrical systems. The Department deducts the cost for maintenance performed by the Department on new or portions of existing systems modified under the Contract.

87-1.01B Definitions

Reser ved

87-1.01C Submittals

Submit a digital file for geographic information system mapping for:

1.Conduit
2.Pull boxes
3.Cabinets
4.Service equipment enclosures
5.Standards The digital file must consist of:
1.Longitudinal and latitude coordinates, und er the WGS84 reference coordinate system. The coordinates must be in decimal format having 6 significant figures after the decimal point. Coordinates must be read at the center of pull boxes, cabinet, standards, and service equipment enclosures; and on top of conduit at 20 -foot intervals before backfill.
2.Type, depth and size for conduits.
3.Type for pull boxes, standards, cabinets, and service equipment enclosures.

87-1.01D Quality Assurance

87-1.01D(1) General

Reserved

87-1.01D(2) Quality Control

87-1.01D(2)(a) General

Before shipping the material to the job site, submit to METS test samples of:

1.Accessible pedestrian signals
2.LED countdown pedestrian signal face modules
3.LED signal modules
4.Luminaires Submit a sample size as shown in the following table: Electrical Material Sampling Contract quantity Test sample size 1–8 1 9–15 2 16–25 3 26–90 5 91–150 8 151–280 13 281–500 20 501–1,200 32 SECTION 87 ELECTRICAL SYSTEMS Before starting operation of an electrical system, perform conductor and system grounding tests in the presence of the Engineer. Conductor test consists of testing each conductor and the conductors in cables for:
1.Continuity.
2.Insulation resistance at 500 V(dc) between the circuit and ground. A minimum insulation resistance of 100 MΩ on circuits must be attained . Start the operational test of the system on any day except Friday or the day before a holiday. The operational test for signals must start from 9:00 a.m. to 2:00 p.m. Notify the Engineer 48 hours before starting the test. An operational test consists of a minimum of 5 business days of continuous, satisfactory operation of the system. If the system fails, correct the problem and retest the system. A shutdown of the system caused by traffic, a power interruption, or unsatisfactory performance of Department -furnished materials does not constitute discontinuity of the test.

87-1.01D(2)(b) Electronic Markers

Electronic marker test consists of placing the electronic marker in the pull box, temporarily marking the pull box location with a utility flag, and using a compatible electronic marker locator to perform the following location test in the presence of the Engineer:

1.Within a 10 foot radius of the electronic marker, slowly move the locator toward the marker to determine the exact location of the pull box .
2.Repeat the test at four different points at 90 degre e from each other on a horizontal plane, away from the marker location, as shown. Take the average of the four points to determine the detected location of the pull box.
3.Detected location of the pull box must be within 0.5 feet of the actual location.

87-1.01D(2)(c) Battery Backup System

Notify the Engineer 48 hours before testing the battery backup system . Test the battery backup system in the presence of the Engineer by turning off the service power to the electrical system to be powered by the battery backup system . The electrical system must remain in full continuous operation for 30 minutes. If the test fails, correct the probl em and retest the system. After successful completion of the test, turn on the service power for the electrical system.

87-1.01D(2)(d) Piezoelectric Axle Sensors

Piezoelectric axle sensors test consists of:

1.Demonstrating for each sensor: 1.1. Capacitance is within 20 percent of the value shown on the sensor's data sheet 1.2. Dissipation factor is less than 0.04 nF when measured in the 20 nF range 1.3. Resistance is greater than 20 Megaoh ms
2.Collecting a minimum of 100 vehicle records for each lane and demonstrating: 2.1. Volume is within ±3 percent accuracy 2.2. Vehicle classification is within 95 percent accuracy by type

87-1.02 Materials

Not Used

87-1.03 Construction

87-1.03A Gene ral

The Engineer determines the final locations of electrical systems. Verify the locations of electrical systems and the depths of existing detectors, conduits, and pull boxes. Notify the Engineer before performing work on the existing system. You may shu t down the system for alteration or removal. SECTION 87 ELECTRICAL SYSTEMS Where an existing Department underground facility is shown within 10 feet of any excavation, locate and field mark the facility before performing work that could damage or interfere with the existing facility. If a mandrel is used, it must be sized per the manufacture r's requirements. If an existing facility is within 2 feet of an excavation, determine the exact location of the facility by excavating with hand tools before using any power -operated or power -driven excavating or boring equipment. A vacuum excavator may be used if authorized. Notify the Engineer immediately if an existing facility is damaged by your activities:

1.Damaged existing traffic signal systems must be repaired or replaced within 24 hours. I f the system cannot be fixed within 24 hours or it is located on a structure, provide a temporary system until the system can be fixed.
2.Damaged existing lighting systems must be repaired or replaced by nightfall. If the system cannot be fixed by nightfa ll, provide a temporary system until the system can be fixed. If existing underground conduit is to be incorporated into a new system, clean it with a mandrel or cylindrical wire brush and blow it clean with compressed air. Limit the shutdown of traffic signal systems to normal working hours. Notify the local traffic enforcement agency before shutting down the signal. Place temporary W3 -1 and R1 -1 signs in each direction to direct traffic through the intersection during shutdown of the signal. Pla ce two R1 -1 signs for 2 -lane approaches. The signs must comply with part 2 of the California MUTCD . Cover signal faces when the system is shut down overnight. Cover temporary W3 -1 and R1 -1 signs when the system is turned on. If you work on an existing ligh ting system and the roadway is to remain open to traffic, ensure the system is in operation by nightfall. Replace detectors you damage within 72 hours, or the Department replaces them and deducts the cost. Work performed on an existing system not described is change order work. Do not use electrical power from existing highway facilities unless authorized. Maintain a minimum 48 -inch clearance for a pedestrian pathway when placing equipment. Except for service installation or work on service equipment enclos ures, do not work above ground until all materials are on hand to complete the electrical work at each location. Bond all metal components to form a continuous grounded system as specified in NEC. Ground metallic equipment mounted less than 8 feet above th e ground surface on a wood pole. If you damage any portion of a concrete curb, sidewalk, curb ramp, driveway, or gutter depression, replace the entire section between contraction or expansion joints under section 73. Apply equipment identification characte rs. Orient louvers, visors, and signal faces such that they are clearly visible to approaching traffic from the direction being controlled. Test loops and the detector lead -in cable circuit for continuity, ground, and insulation resistance at the controlle r cabinet before connecting detector lead -in cable to the terminal block. Perform an operational test of the systems. Before starting the operational test for systems that impact traffic, the system must be ready for operation, and all signs, pavement deli neation, and pavement markings must be in place at that location. Collect the geographic information system mapping data. SECTION 87 ELECTRICAL SYSTEMS

87-1.03B Conduit Installation

87-1.03B(1) General

The installation of conduit includes installing caps, bushings, and pull tape and terminating the conduit in pull boxes, foundations, poles, or a structure. Limit the number of bends in a conduit run to no more than 360 degrees between pull points. Use conduit to enclose conductors except where they are inst alled overhead or inside standards or posts. You may use a larger size conduit than specified for the entire length between termination points. Do not use a reducing coupling. Extend an existing conduit using the same material. Terminate conduits of differ ent materials in a pull box. Install conduit of a minimum size :

1.1-1/2 inches from adjacent pull box to: 1.1. Electrolier . 1.2. Type 2 post .
2.2 inches from adja cent pull box to: 2.1. Signal standard . 2.2. Overhead sign .
3.3 inches from adja cent pull box to: 3.1. Service equipment enclosure . 3.2. Controller cabinet. Install two co nduits.
4.1-1/2 inches when not specified . Make conduit cuts square and true. Thread metal conduit with standard conduit -threading dies. Ream the ends of shop -cut and field -cut conduit to remove burrs and rough edges. Do not use slip joints or running threads to couple metal conduit. If a standard coupling cannot be used, use a threaded union coupling. Tigh ten couplings for metal conduit to maintain a good electrical connection. Use Type 1 conduit:
1.On exposed surfaces unless otherwise shown
2.In concrete structures
3.Between a structure and the nearest pull box Cut Type 2 conduit with pipe cutters; do not use hacksaws. Tighten conduit into couplings or fittings using strap wrenches or approved groove joint pliers. Apply 2 coats of unthinned primer and paint all metal conduit :
1.Exposed threads
2.Field -cut threads, before installing conduit couplings
3.Damaged surfaces Do not remove shop -installed conduit couplings. Repair damaged Type 2 conduit and coupling coating by:
1.Clean ing the conduit or coupling and paint ing it with 1 coat of rubber -resin -based adhesive under the manufacturer's instructions . Wrap the damaged area with at least 1 layer of 2 -inch-wide, 20 mils - minimum -thickness, PVC tape under ASTM D1000 with a minimum tape overlap of 1/2 inch .
2.Painting damaged spots of 1/4 inch or less in diameter with a brushing -type compound supplied by the conduit manufacturer . SECTION 87 ELECTRICAL SYSTEMS Cut Type 3 conduit with tools that do not deform the conduit. Use solvent weld connections. If factory bends are not used, bend the conduit to a radius no less than 6 times its inside diameter without crimping or flattening it. C omply with the bending requirements shown in the following table: Conduit -Bending Requirements Type Requirement 1 Use equipment and methods under the conduit manufacturer's instructions. 2 Use a standard bending tool designed for use on thermoplastic -coated conduit. The conduit must be free of burrs and pits. 3 Use equipment and methods under the conduit manufacturer's instructions. Do not expose the conduit to a direct flame. 5 Use equipment and methods under the conduit manufacturer's instructions. Do not install new conduit through foundations. Install conduit terminating in a standard or pedestal from 2 to 3 inches above the foundation. Slope the conduit toward the handhole open ing. Terminate conduit installed through the bottom of a nonmetallic pull box 2 inches above the bottom and 2 inches from the wall closest to the direction of the run. Cap the ends of conduit for future use or until installation of conductors or cables. Cap the t hread ed ends of metal conduit with standard pipe caps. Install a plastic cap on all other types of conduit. Install threaded bushings on metal conduits and bond them using a jumper. Install nonmetallic bushings or end bells on other types of conduit . Install pull tape in conduit or innerducts to remain empty , with at least 2 feet of slack at each end. Attach the tape's ends to the conduit.

87-1.03B(2) Conduit Installation for Structures

87-1.03B(2)(a) General

Paint exposed Type 1 conduit on painted, stained, or colored structures . Comply with section 59 -3 except the final coat of paint must match the structure. Install galvanized steel hangers, steel brackets, and other fittings to support conduit i n or on a wall or bridge structure . Cast into concrete or pass -through openings conduit installed inside box girders. Size openings to fit the conduit and fittings, and remove lost deck material. Do not install conduit through drainage openings. Install co nduit parallel or at right angles to girders. Install expansion fitting s on structures with only longitudinal movement. Size the fittings for the longitudinal movement of the structure . The p iston inside expansion fittings must be positioned so the piston expands the full movement of the bridge without damaging the fitting. Install deflection fitting s on structures with only transverse movement. Size the fittings for the transverse movements of the structure. All block outs for deflection fittings must have clearance or be sized for the physical size and the maximum rated movement of the fittings without touching concrete or structural elements. Install multiple expansion, and deflection, or combination expansion -deflection fittings in series on structures w ith longitudinal and transverse movement. Size the fittings for the longitudinal and transverse movements of the structure . The total movement of the multiple fittings must be greater than the structure movement range. Fill expansion and deflection fitting pockets with resilient weatherproof compound. Install expansion and deflection fittings parallel to superstructure girders. SECTION 87 ELECTRICAL SYSTEMS

87-1.03B(2)(b) New Structures

Seal and make watertight the conduits which lead to soffits, wall -mounted luminaires, other lights, and fixtures located below the pull box grade. If you place a conduit through the side of a nonmetallic pull box, terminate the conduit 2 inches from the wall and 2 inches above the bottom. Slop e the conduit toward the top of the box. For ease of installation and if authorized, you may use Type 4 conduit instead of Type 1 conduit for the final 2 feet of conduit entering a pull box in a reinforced concrete structure. For conduit installed inside o f bridge structures, you must:

1.Install precast concrete cradles.
2.Bond precast concrete cradles with one of the following: 2.1. Epoxy adhesive for bonding freshly mixed concrete to hardened concrete 2.2. Rapid -set epoxy adhesive for pavement markers 2.3. Standard -set epoxy adhesive for pavement markers
3.Use a pipe sleeve or form an opening for a conduit through a bridge structure. The sleeve or opening through a prestressed member or conventionally reinforced precast member must be: 3.1. Oriented tra nsverse to the member 3.2. Located through the web 3.3. No more than 4 inches in diameter
4.Wrap the conduit with 2 layers of asphalt felt building paper and securely tape or wire the paper in place for a conduit passing through a bridge abutment wall. Fi ll the space around the conduit with mortar under section 51 -1, except the proportion of sand to cement must be 3 to 1. Fill the space around the conduits after prestressing is completed. Mark the location of conduit end s with a 3 -inch tall "Y" for all co nduits installed in structures or terminating at curbs. Mark the "Y" on the face of a curb, gutter or wall , directly above the conduit , and above grade line.

87-1.03B(2)(c) Existing Structures

Install surface -mounted conduit :

1.Straight and true to: 1.1. The horizontal alignment of structures 1.2. The vertical alignment of walls
2.Parallel to the walls when mounted on ceilings or similar surfaces Support conduit at maximum 5 -foot intervals with galvanized, malleable -iron, condui t clamps, and clamp backs secured with expansion anchorage devices. Use the largest diameter of galvanized, threaded studs that will pass through the mounting hole in the conduit clamp.

87-1.03B(3) Conduit Installation Underground

87-1.03B(3)(a) General

Notify the Engineer at least 4 business days before starting horizontal directional drilling method or jack and drill method . Install conduit to a depth of:

1.18 inches, minimum, under sidewalk and curbed paved med ian areas
2.42 inches, minimum, below the bottom of the rail of railroad tracks
3.30 inches, minimum, everywhere else below grade Install Type 1 or Type 2 conduit with explosion -proof sealing fittings , within the limits of hazardous locations as specifi ed in NEC for Class I, division 1 . Install a minimum 1 -1/2-inch diameter Type 1 or Type 2 conduit under railroad tracks. You may lay conduit on existing pavement within a new curbed median constructed on top. Install conduit under pavement by either the horizontal directional drill ing method or jack and drill method. SECTION 87 ELECTRICAL SYSTEMS Place conduit couplings at a minimum of 6 inches from the face of a foundation.

87-1.03B(3)( b) Conduit in Trenches

87-1.03B(3)(b)(i) General

Backfill trench with:

1.A minimum of 2 inches of sand bedding before installing the conduit
2.18 inches of slurry c oncrete over the conduit
3.Native material over the slurry cement Use slurry concrete under section 19 -3.02E except, the size of the aggregate must be 3/8 inch or smaller. Place warning tape in the trench 6 inches below finished grade. Grade the trench surface to match the existing grade.

87-1.03B(3)( b)(ii) High Density Polyethylene Conduit Installation

For swee ps, maintain a conduit bend radius of a minimum 10 times the outside diameter of the conduit. Conduits must not protrude more than 2 inches inside the pull box and vaults, and must enter at an angle less than 20 degrees from either the vertical or horizontal axis. Demonstrate a minimum of 2 test fusions to the Engineer prior to performing fusion operations on HDPE conduit to be installed. Join HDPE conduit using electro fusion couplings under the manufa cturer 's instructions . Do not expose conduit to direct flame. The electro fusion must be performed by a person certified by the conduit manufacturer. Slurry concrete must be pigmented to match color no. 21105 of AMS -STD-595. Blow out all conduits with compressed air until all foreign material is removed, before installing innerducts . Install innerducts as one continuous unit between vaults. Innerducts may be interrupted inside pull boxes located between vaults and cabinets. Lubricate innerducts per manu facturer's instructions during installation. Seal the ends of conduit after cables or pull tape are installed.

87-1.03B(3)(b)(iii) Trench-In-Pavement Method

Install conduit in a trench approximatel y 2 inches wider than the outside diameter of the conduit but not exceeding 6 inches in width. Dig the trench by hand to the required depth at pull boxes. Backfill the trench with slurry cement to the top of the pavement's surface by the end of each workda y. When work includes resurfacing the roadway, complete the trenching before the final pavement layer is applied. When work does not include resurfacing the roadway, within 3 day s after trenching:

1.Cold plane under section 39 -3, a minimum 2 feet wide are a along the trench
2.Clean the cold planed area and apply a tack coat
3.Place HMA Type A under section 39 -2

87-1.03B(3)(c) Horizontal Directional Drilling Method

Install a conduit to a minimum depth of 4 feet and maximum depth of 6 feet. If you must install a conduit less than 4 feet in depth or greater than 6 feet in depth, the installation must be authorized. The diameter of the bore hole must be no larger than 1.5 times the outs ide diameter of the conduit. Water -based mineral slurry or wetting solution may be used to lubricate the boring tool and stabilize the soil surrounding the boring path. SECTION 87 ELECTRICAL SYSTEMS Dispos e of residue per section 13 -4.03D. The horizontal directional drilling equipment must have directional control of the boring tool and have an electronic boring tool location detection system. During operation, the equipment must be able to determine the location of the tool both horizontally and vertically. Use a mandrel to prove the c onduit is free and clear of dirt, rocks, and other debris after installation.

87-1.03B(3)(d) Jack and Drill Method

Keep the jacking or drilling pit 2 feet away from the edge of pavement except when instal ling conduit under rail -road tracks. Construct the jacking or drilling pit a minimum of 13 feet from the centerline of the track to the closest side of the pit. Do not weaken the pavement or soften the subgrade with excessive use of water. Cover the jacking pit with planking if left overnight. If an obstruction is encountered, obtain authorization to cut small holes in the pavement to locate or remove the obstruction. You may install Type 2 or Type 3 con duit under the pavement if a hole larger than the conduit's diameter is predrilled. The predrilled hole must be less than one and half the conduit's diameter. Remove the conduit used for drilling or jacking and install new conduit for the completed work.

87-1.03C Installation of Pull Boxes

87-1.03C(1) General

Install pull boxes no more than 200 feet apart. Place the cover on the box when not working in it.

87-1.03C(2) Roadway Pull Boxes

87-1.03C(2)(a) General

You may instal l larger pull boxes than specified or shown and additional pull boxes to facilitate the work except in structures. Where a roadway pull box is adjacent to a post or standard, place the pull box within 5 feet from the post or standard on the downstream side of traffic when practical . Install a pull box on a minimum 6 -inch deep bed of crushed rock and grout it before installing conductors. The grout must be from 0.5 to 1 inch thick and sloped toward the drain hole. Place a layer of roofing paper between the g rout and the crushed rock sump. Make a 1 -inch drain hole through the grout at the center of the pull box. Set the pull box such that the top is 1 -1/4 inches above the surrounding grade in unpaved areas and leveled with the finished grade in sidewalks and o ther paved areas. Grout around conduits that are installed through the sides of the pull box. Bond and ground the metallic conduit before installing conductors and cables in the conduit. Bond metallic conduits in a nonmetallic pull box using bonding bushin gs and bonding jumpers. Do not install pull boxes in concrete pads, curb ramps, or driveways. Reconstruct the sump of a pull box if disturbed by your activities. If the sump was grouted, remove and replace the grout.

87-1.03C(2)(b) Nontraffic Pull Boxes

For a buried nontraffic pull box , install the electronic marker and set the box such that the top is from 6 to 8 inches below the surrounding grade. Place a 20 -mil-thick plastic sheet made of HDPE or PVC virgin compounds to prevent water from entering the box. When a pull box is in a structure, modify the base as required. SECTION 87 ELECTRICAL SYSTEMS Place mortar between a nontraffic pull box and a pull box extension. Where a nontraffic pull box is in the vicinity of a curb in an unpaved area, place the box adjacent to the back of the curb if practical. If you replace the cover on a nontraffic pull box, anchor it to the box. Perform the electronic marker test.

87-1.03C(2)(c) Traffic Pull Boxes

Place minor concrete around and under a traffic pull box as shown . Bolt the steel cover to the box when not working in it . Bond the steel cover to the conduit with a minimum 3 -foot-long jumper and bolt it down after installing the conductors and cables.

87-1.03C(2)(d) Tamper-Resistant Pull Boxes

Install the tamper -resistant pull boxes under the manufacturer 's instructions.

87-1.03C(3) Structure Pull Boxes

Install structure pull boxes parallel to the structure. After removing the knockouts, flatten the surrounding area. Bond conduit to a structure pull box using locknuts on the inside and outside of the box. Cover pull boxes with a 1/4 -inch plywo od during pouring of PCC. For a no. 9 pull box, the upper edge of the plywood must fit against the lower edge of the rain tight hood. Install no. 7 pull box with bottom flanges flush with the bottom of the box girder. Place top and bottom covers and seal t he pull box during PCC pouring. For no. 9 and 9A pull boxes:

1.Form a 1:1 chamfer around the cover
2.Use the drain hole in the center if the box is horizontal and the low end drain hole if the box is inclined
3.Mounted in a sloping parapet, drill a 1/2 -inch elongated drain hole in the center if the box is horizontal or the low end if the box is inclined

87-1.03D Battery Backup System Cabinets

Install the battery backup system cabinet to the right side of the controller cabinet. If installation on the right side is not possible, obtain authorization for installation on the left side. Construct access opening between controller cabinet and battery backup cabinet using:

1.2-inch nylon -insulated, steel chase nipple
2.2-inch steel sealing locknut
3.2-inch nylon -insulated, steel bushing Remove the jumper between the terminals labeled BBS-1 and UBS-1 and the jumper between the terminals labeled BBS-2 and UBS-2 in the 7 -position terminal block in the controller cabinet before connecting the electronics assembly. Install the electronics assembly and batteries in the battery backup system cabinet . Obtain authorization for installat ion of the electronics assembly in the controller cabinet.

87-1.03E Excavating and Backfilling for Electrical Systems

87-1.03E(1) General

Notify the Engineer at least 72 hours before starting excavation activities. Dispose of surplus excavated material. Restrict closures for excavation on a street or highway to 1 lane at a time unless otherwise specified. 1 SECTION 87 ELECTRICAL SYSTEMS

87-1.03E(2) Trenching

Do not trench until conduit or direct burial cables are on-site and ready for installation . Place excavated material in a location that will not interfere with traffic or surface drainage. Compact native material backfill to a minimum relative compaction of:

1.95 percent when placed within the hinge points and in areas where pavement is to be constructed
2.90 percent when placed outside the hinge points and not under pavement Restore the sidewalks, pavement, and landscaping at a location before starting excavatio n at another location.

87-1.03E(3) Concrete Pads, Foundations, and Pedestals

Construct concrete pads, foundations , and pedestals under section 56 -3. Construct a pad in front of a Type III service equipment enclosure. The pad must be 24 inches in length, 4 inches in thickness, and must match the width of the foundation. In unpaved areas, place the top of the foundation 6 inches above the surrounding grade, excep t place the top:

1.1 foot 6 inches above the grade for 336L S cabinets
2.1 foot 8 inches above the grade for Type C telephone demarcation cabinets
3.2 inches above the grade for Type III service equipment enclosures The pad must be 2 inches above the surrounding grade in unpaved areas. In or adjacent to paved areas, place the top of the foundation 4 inches above the surrounding grade, except place the top:
1.1 foot 6 inches above the grade for 336L S cabinets
2.1 foot 8 inches above the grade for Type C telephone demarcation cabinets
3.Level with the finished grade for Type III service equipment enclosures The concrete pad must be level with the finished grade in paved areas.

87-1.03F Conductors and Cable s Installations

87-1.03F(1) General

The installation of conductors and cables includes splicing conductors and attaching the terminals and connectors to the conductors. Clean the conduit , install conduit bushings, and pull all conductors and cables as a unit. If new conductors or cables are to be added in an existing conduit: Remove the content

2.Clean the conduit
3.Pull both old and new conductors and cables as a unit Provide conductor and cable slack to comply with the requirements shown in the f ollowing table: Conductor and Cable Slack Requirements Location Slack (feet) Signal standard 1 Lighting standard 1 Signal and lighting standard 1 Pull box 3 Splice 3 Controller cabinet 6 Standards with slip base 0 SECTION 87 ELECTRICAL SYSTEMS Wrap conductors and secure cables to the end of the conduit in a pull box. Seal the ends of conduits with a sealing compound after installing conductors or cables. Neatly arrange conductors and cables inside pull boxes and cabinets. Tie the conductors and cables together with self -clinching nylon cable ties or enclose them in a plastic tubing or raceway. Identify conductors and cables by direct labeling, tags, or bands fastened in such a way that they will not move. Use mechanical methods for labeling. Provide band symbol identificat ion on each conductor or each group of conductors comprising a signal phase in each pull box and near the end of terminated conductors. Tape the ends of unused conductors and cables in pull boxes to form a watertight seal. Do not connect the push -button or accessible pedestrian signal neutral conductor to the signal neutral conductor. Install a tracer wire.

87-1.03F(2) Cables

87-1.03F(2)(a) General

Reserved

87-1.03F(2)(b) Communication Cables

87-1.03F(2)(b)(i) General

Terminate the ends of the communica tion cables as shown.

87-1.03F(2)(b)(ii) Category 5E and 6 Cables

Do not splice category 5E and 6 cables .

87-1.03F(2)(b)(iii) Telephone Cables

Do not splice telephone cables between the telephone demarcation point and the contr oller cabinet.

87-1.03F(2)(c) Copper Cables

87-1.03F(2)(c)(i) General

Reserved

87-1.03F(2)(c)(ii) Detector Lead -in Cables

Install a Type B or C detector lead -in cable in conduit. Seal the ends of the lead -in cable before installing it in the conduit to prevent moisture from entering the cable. Splice loop conductors for each direction of travel for the same phase, terminati ng in the same pull box, to a separate lead -in cable running from the pull box adjacent to the loop detector to a sensor unit mounted in the controller cabinet. Install the lead -in cable without splices except at the pull box when connecting to loop wire. Verify in the presence of the Engineer that the loops are operational before making the final splices between loop conductors and the lead -in cable. Identify and tag each lead -in cable with the detector designation at the cabinet and pull box adjacent to the loops.

87-1.03F(2)(c)(iii) Conductors Signal Cables

Do not splice signal cables. Provide identification at the ends of terminated conductors in a cable as shown. Provide identification for each cable in each pull box showing the signal standard to which it is connected. Connect conductors in a 12 -conductor cable as shown in the following table: SECTION 87 ELECTRICAL SYSTEMS 12CSC Color Code and Functional Connection Color code Termination Phase Red Red signal 2, 4, 6, or 8 Yellow Yellow signal 2, 4, 6, or 8 Brown Green signal 2, 4, 6, or 8 Red/black stripe Red signal 1, 3, 5, or 7 Yellow/black stripe Yellow signal 1, 3, 5, or 7 Brown/black stripe Green signal 1, 3, 5, or 7 Black/red stripe Spare or as required for red or DONT WALK -- Black/white stripe Spare or as required for yellow -- Black Spare or as required for green or WALK -- Red/white stripe Pedestrian signal DONT WALK -- Brown/white stripe Pedestrian signal WALK -- White Terminal block Neutral Use the neutral conductor only with the phases associated with that cable. Do not intermix neutral conductors from different cables except at the signal controller.

87-1.03F(2)(c)(iv) Signal Interconnect Cable s

Do not splice the cable unless authorized. If splices are authorized, insulate the conductor splices with heat -shrink tubing and overlap the insulation at least 0.6 inch. Cover the splice area of the cable with heat -shrink tubi ng and overlap the cable jacket at least 1 -1/2 inches. Provide a minimum of 3 feet of slack at each splice.

87-1.03F(2)(c)(v) Railroad Preemption Cable s

Do not splice railroad preemption cable from controller cabinet to r ailroad cabinet. Terminate individual conductors with ferrule connectors in the controller cabinet. Provide identification on both ends of the cable and connect the cable end in the controller cabinet as shown in the following table: Color Code and Functional Connection Conductor no. Color code Controller cabinet field terminal connections Conductor identification 1 Black Not Used Spare 2 White Not Used Spare 3 Red FT8-A145 Health Status DC+ 4 Green Not Used Spare 5 Orange FT7-A134 Simultaneous DC- 6 Blue FT7-A131 Advance DC- 7 White/black strip e Not Used Spare 8 Red/black strip e FT8-A144 Gate Down /Island 9 Green/black strip e Field Terminal FT 8-A142 Advance Pedestrian Preemption 10 Orange/black strip e FT7-A135 Simultaneous Primary 11 Blue/black strip e FT7-A132 Advance Primary 12 Black/white strip e Not Used Spare 13 Red/white strip e FT8-A143 Gate Down /Island DC- 14 Green/white strip e FT8-A141 Advance Pedestrian Preemption DC- 15 Blue/white strip e FT7-A133 Advance Secondary 16 Black/red strip e Not Used Spare 17 White/red strip e FT8-A146 Health Status DC- 18 Orange/red strip e FT7-A136 Simultaneous Secondary Keep all exposed conductors the same length and individually insulate spare conductors against each other. SECTION 87 ELECTRICAL SYSTEMS Provide a minimum 6 feet of slack in the pull box adjacent to the railroad cabinet. Connect the cable end in the railroad cabinet as directed by the railroad agency r epresentative.

87-1.03F(3) Conductors

87-1.03F(3)(a) General

Do not run conductors to a terminal block on a standard unless they are to be connected to a signal head mounted on that standard. Provide 3 spare conductors in all conduits containing ramp metering and traffic signal conductors. Install a separate conductor for each terminal of a push button assembly and accessible pedestrian signal.

87-1.03F(3)(b) Reserved

87-1.03F(3)(c) Copper Conductors

87-1.03F(3)(c)(i) General

Install a minimum no. 8 grounding copper conductor in conduit and connect it to all -metal components. Where conductors from different service points occupy the same conduit or standard, enclose the conductors from one of the services in flexible or rigid metal conduit.

87-1.03F(3)(c)(ii) Inductive Loop Conductors

Install a Type 1 or 2 inductive loop conductor except use Type 2 for Type E and F loop detectors. Install the conductor without splices except at the pull bo x.

87-1.03F(4) Manual Installation Method

Use an inert lubricant for placing conductors and cables in conduit . Pull the conductors and cables into the conduit by hand using pull tape.

87-1.03F(5) Direct Burial Aluminum Cable Installation Method

Install direct burial aluminum cable at a minimum 30 inches below grade in unpaved areas or at a minimum 18 inches below finished grade in paved areas. Do not splice the direct burial aluminum cable between pull boxes and enclosures. Fill trench with slu rry cement backfill to between 4 to 6 inches below finished grade under section 19 - 3.02E. Fill the remaining trench to finished grade with native material. In paved area, fill the remaining trench to finished grade with the same material of the paved area.

87-1.03G Equipment Identification Ch aracters

The Engineer provides you with a list of the equipment identification characters . Stencil the characters or apply the reflective self -adhesive labels to a clean surface. Treat the edges of s elf-adhesive characters with an edge sealant. Place the characters on the side facing traffic on:

1.Front doors of cabinets and service equipment enclosures
2.Wood poles, fastened with 1 -1/4-inch aluminum nails, for pole mounted enclosures
3.Adjacent bent or abutment at approximately the same station as an illuminated sign or soffit luminaire
4.Underside of the structure adjacent to the illuminated sign or soffit luminaire if no bent or abutment exists nearby
5.Posts of overhead signs
6.Standards Before placing new characters on existing or relocated equipment , remove the existing characters . SECTION 87 ELECTRICAL SYSTEMS

87-1.03H Conductor and Cables Splices

87-1.03H(1) General

You may splice :

1.Grounded conductors in a pull box
2.Accessible pedestrian signal and push b utton conductors in a pull box
3.Ungrounded signal conductors in a pull box if signals are modified
4.Ungrounded signal conductors to a terminal compartment or a signal head on a standard with conducto rs of the same phase in the pull box adjacent to the standard
5.Ungrounded lighting circuit conductors in a pull box if lighting circuits are modified Solder all copper conductor splices using the hot iron, pouring, or dipping method. Do not perform open - flame soldering. Do not solder aluminum conductors.

87-1.03H(2) Splice Insulation Methods

Insulate splices in a multiconductor cable to form a watertight joint and to prevent moisture absorption by the cable. Use heat -shrink tubing or Method B to insulat e a splice. Use heat -shrink tubing as follows:

1.Cover the splice area completely with an electrical insulating coating and allow it to dry.
2.Place mastic around each condu ctor before placing them inside the tubing. Use the type of mastic specified in the tubing manufacturer's instructions.
3.Heat the area under the manufacturer's instructions. Do not perform open -flame heating. After contraction, each end of the heat -shrin k tubing or the open end of the tubing's end cap must overlap the conductor insulation at least 1 -1/2 inches.
4.Cover the entire splice with an electrical insulating coating and allow it to dry. Use Method B as follows:
1.Cover the splice area completely with an electrical insulating coating and allow it to dry.
2.Apply 3 layers of half -lapped, PVC electrical tape.
3.Apply 2 layers of butyl -rubber, stretchable t ape with liner.
4.Apply 3 layers of half -lapped, PVC, pressure -sensitive, adhesive tape.
5.Cover the entire splice with an electrical insulating coating and allow it to dry.

87-1.03I Connectors and Terminals

Apply connectors and terminals to cables and conductors using a crimping compression tool under the manufacturer's instructions. The tool must prevent opening of the handles until the crimp is completed. Install crimp -style terminal lugs on stranded con ductors smaller than no. 14. Solder no. 8 and smaller copper conductors to connectors and terminal lugs.

87-1.03J Standards, Poles, Pedestals, and Posts

Install standards, poles, pedestals, and posts under section 56 -3. Ground standards with a handhole by attaching a bonding jumper from the bolt or lug inside the standard to a metal conduit or to the grounding wire in the adjacent pull box. The bonding jumper must be visible when the handhole cov er is removed. Ground standards without a handhole or standards with a slip base by attaching a bonding jumper to all anchor bolts using ground clamp s and connecting it to a metal conduit or to the grounding wire in the adjacent pull box. The bonding jumpe r must be visible after mortar has been placed on the foundation.

87-1.03K Piezoelectric Axle Sensors

Obtain authorization for exact locations for installation of the piezoelectric axle sensors . SECTION 87 ELECTRICAL SYSTEMS Cut slots fo r axle sensors and screened transmission cables under section 87 -1.03V(2). Install piezoelectric axle sensors in slots. Fill the slot with epoxy grout under section 95 -1.02H. Ensure t he grout does not exceed 165 degrees F while curing. Do not reopen the la ne to traffic until the epoxy sets. Perform the conductor test. Connect the field wiring to the terminal blocks in the controller cabinet. Perform the piezoelectric axle sensor test. Perform the operational test. Failure of the system to record and store d ata as required for an accumulated time exceeding 3 hours during the 5 -day period is cause for the operational test to be rejected and repeated.

87-1.03L Utility Service

87-1.03L(1) General

Install the service equipment early enough to allow the utility to complete its work before completion of the electrical work. At least 15 days before permanent electrical and telecommunication service is required, request the service connections for permanent installations. The Department arranges with the utilities for completion of the connections and pays all costs and fees required by the utilities.

87-1.03L(2) Electric Service

87-1.03L(2)(a) General

If service equipment is to be installed on a utility -owned pole, furnish and install the conduit, conductors, pull boxes, and other necessary material to complete the service installation. The service utility decides the position of the riser and equipment on the pole.

87-1.03L(2)(b) Electric Service for Irrigation

Establishing electric service for irrigation includes installing conduit, conductors, and pull boxes and making connections from the service point to the ir rigation controllers.

87-1.03L(2)(c) Electric Service for Booster Pumps

Establishing electric service for a booster pump includes installing conduit, conductors, and pull boxes and making connections f rom the service point to the booster pump enclosure.

87-1.03L(3) Telecommunications Service

Establishing telecommunication service includes installing conduit, conductors, and pull boxes and making connect ions from the service point to the telephone demarcation cabinet.

87-1.03M Photoelectric Controls

Mount the photoelectric unit on the top of the pole for Type I, II, and III photoelectric controls . Use mounting brackets where pole -top mounting is not possible. Orient the p hotoelectric unit to face north. Mount the enclosure at a height of 6 feet above finished grade on the same standard as the photoelectric unit. Install a minimum 100 VA, 480/120 V(ac) transform er in the contactor enclosure to provide 120 V(ac) for the photoelectric control unit when switching 480 V(ac), 60 Hz circuits.

87-1.03N Fused Splice Connectors

Install a fuse splice connector with a fuse in eac h ungrounded conductor for luminaires, except for overhead sign luminaires. The connector must be located in the pull box adjacent to the luminaires. If the pull box for the roadway luminaire is tamper resistant, install a fuse splice connector with 10 A f use in the pull box and an additional fuse splice connector with a 5 A fuse in the handhole. Install a fuse splice connector with a fuse on primary side of transformer. SECTION 87 ELECTRICAL SYSTEMS Crimp the connector terminals onto the ungrounded conductors using a tool under the man ufacturer's instructions. Insulate the terminals and make them watertight.

87-1.03O Grounding Electrodes

Install a grounding electrode for each cabinet, service equipment enclosure, and transformer. Attach a ground ing conductor to the electrode using either a ground clamp or exothermic weld. Connect the other end of the conductor to the cabinet, service equipment enclosure, and transformer.

87-1.03P Service Equipment Enclosures

Installing a service equipment enclos ure includes constructing the foundation and pad and installing conduit, adjacent pull boxes, and grounding electrode. Locate the foundation such that the minimum clearance around the front and back of the e nclosure complies with NEC, article 110.26, "Spaces About Electrical Equipment, (600 V, nominal or less)." Apply a sealing compound between the foundation and the enclosure before installing the enclosure . Bond and ground metal conduit as specified in NEC and by the service utility except the grounding electrode conductor must be no. 6 or larger. If circuit breakers and components do not have a description on engraved phenolic nameplates, install them using stainless steel rivets or screws under section 86 -1.02P(2).

87-1.03Q Cabinets

87-1.03Q(1) General

Installing a cabinet includes constructing the foundation and pad and installing conduit, adjacent pull boxes, and grounding electrode. Apply a mastic or caulki ng compound before installing the cabinet on the foundation to seal the openings. Connect the field wiring to the terminal blocks in the cabinet. Neatly arrange and lace or enclose the conductors in plastic tubing or raceway. Terminate the conductors with properly sized captive or spring spade terminals. Apply a crimp -style connector and solder them. Install and solder a spade -type terminal on no. 12 and smaller field conductors and a spade -type or ring - type terminal on conductors larger than no. 12.

87-1.03Q(2) Department -Furnished Controller Cabinets

Arrange for the delivery of Department -furnished controller cabinets .

87-1.03Q(3) Reserved

87-1.03Q(4) Telephone Demarcation Cabinets

Installing a telephone demarcation cabinet includes installing conduit, cable, and pull boxes to the controller cabinet. Install the cabinet with the back toward the nearest lane of traffic.

87-1.03R Signal Heads

87-1.03R(1) General

Installing a signal head includes mounting the heads on standards and mast arms, installing backplates and visors, and wiring conductors to the terminal blocks. Keep the heads covered or direct th em away from traffic until the system is ready for operation.

87-1.03R(2) Signal Faces

Use the same brand and material for the signal faces at each location. Program the programmable visibility signal faces und er the manufacturer's instructions. The indication must be visible only in those areas or lanes to be controlled. SECTION 87 ELECTRICAL SYSTEMS

87-1.03R(3) Backplates

Install backplates using at least six 10 -24 or 10 -32 self -tapping and locki ng stainless steel machine screws and flat washers. If a plastic backplate requires field assembly, attach each joint using at least four no.10 machine screws. Each machine screw must have an integral or captive flat washer, a hexagonal head slotted for a standard screwdriver, and either a locking nut with an integral or captive flat washer or a nut, flat washer, and lock washer. Machine screws, nuts, and washers must be stainless steel or steel with a zinc or black oxide finish. If a metal backplate has 2 or more sections, fasten the sections with rivets or aluminum bolts peened after assembly to avoid loosening. Install the backplate such that the background light is not visible between the backplate and the signal face or between sections.

87-1.03R(4) Si gnal Mounting Assemblies

Install a signal mounting assembly such that its members are arranged symmetrically and plumb or level. Orient each mounting assembly to allow maximum horizontal clearance t o the adjacent roadway. For a bracket -mounted assembly, bolt the terminal compartment or pole plate to the pole or standard. In addition to the terminal compartment mounting, attach the upper pipe fitting of Type SV -1-T with 5 sections or a SV -2-TD to the standard or pole using the mounting detail for signal heads without a terminal compartment. Use a 4 -1/2-inch slip fitter and set screws to mount an assembly on a post top. After installing the assembly, clean and paint the exposed threads of the galvan ized conduit brackets and bracket areas damaged by the wrench or vise jaws. Use a wire brush to clean and apply 2 coats of unthinned, organic zinc -rich primer. Do not use an aerosol can to apply the primer. Install the conductors in the terminal compartmen t and secure the cover.

87-1.03S Pedestrian Signal Heads

Installing a pedestrian signal head includes mounting the heads on standards and wiring conductors to the terminal blocks. Install the pedestrian signal m ounting assembly under section 87 -1.03R(4). Use the same brand and material for the pedestrian signal faces at each location. Install a pedestrian signal face such that its members are arranged symmetrically and plumb or level.

87-1.03T Accessible Pedestr ian Signals

Install accessible pedestrian signals of the same manufacturer at each location . Do not install APS components inside the controller cabinet. Identify conductors on both ends of the signal inte rface cable. Label each conductor according to their function under the manufacturer's instructions. Connect the signal interface cable to the terminal blocks in the APS and pedestrian signal head . Attach the accessible pedestrian signal to the standard with hex screws by drilling and tapping. Drill a 1 - inch diameter hole on the standard for the signal interface cable. Install the 9 by 12 inches R10 -3j (CA) sign using the adapter plate provided by the APS manufacturer. Point the arrow on the accessible pedestrian signal in the crossing direction. Cut Type 2 post 2 inches above the R10 series sign. Furnish the equipment and hardware to set up and calibrate the accessible pedestrian signal. SECTION 87 ELECTRICAL SYSTEMS Arrange to have a manufacturer's representative at the job site to program the accessible pedestrian signal with an audible message or tone.

87-1.03U Push Button Assemblies

Install the push button assembly and the R10 series sign on the crosswalk side of the stand ard. Attach the sign to the assembly for Type B assemblies. Attach the sign to the standard using 2 straps and saddle brackets for Type C assemblies. You may use straps and saddle brackets to secure the push button to the standard. Cut Type 2 post 2 inches above the R10 series sign.

87-1.03V Detectors

87-1.03V(1) General

Installing a detector includes installing inductive loop conductors, sealant, conduit, and pull boxes. Center the detectors in the traffic lanes. Do not splice the detector conductor.

87-1.03V(2) Inductive Loop Detectors

Mark the location of the inductive loop detectors such that the distance between the side of the loop and a lead-in saw cut from an adjacent detector is at least 2 feet. The distance between lead -in saw cuts must be at least 6 inches. Saw cut the slots under section 13-4.03E(7). The bottoms of the slots must be smooth with no sharp edges. For Type E detector loops, saw the slots such that the sides are vertical. Wash the slots clean using water and blow dry them with compressed air to remove all moisture and debris. Identify the start of the conductor. Waterproof the ends of a Type 2 loop conductor before installing it in the conduit to prevent moisture from entering the cable. Install the loop conductor in the slots and lead -in saw cuts using a 3/16 -to 1/4 -inch-thick wood paddle. Hold the conductors in place at the bottom of the slot with wood paddles during placement of the sealant. Wind adjacent loops on the same sensor unit channel in opposite directions. Twist the conductors for each loop into a pair consisting o f a minimum of 2 turns per foot before placing them in the lead -in saw cut and the conduit leading to the pull box. Do not install more than 2 twisted pairs of conductors per lead -in saw cut. Test each loop for continuity, circuit resistance, and insulatio n resistance before filling the slots with sealant. Remove excess sealant from the adjacent road surface before it sets. Do not use solvents to remove the excess. Identify the loop conductor pair in the pull box, marking the start with the letter S and the end with the letter F. Band conductors in pairs by lane in the pull box adjacent to the loops and in the cabinet. Identify each pair with the detector designation and loop number. Install the conductors in a compacted layer of HMA immediately below the up permost layer if more than one layer will be placed. Install the loop conductors before placing the uppermost layer of HMA. Fill the slot with a sealant flush to the surface. Install the conductors in the existing pavement if one layer of HMA is to be plac ed. Install the loop conductors before placing the layer of HMA. Fill the slot with a sealant flush to the surface. SECTION 87 ELECTRICAL SYSTEMS

87-1.03V(3) Preformed Inductive Loop Detectors

Install a preformed inductive loop detector consisting of 4 turns in the loop and a lead -in conductor pair twisted at least 2 turns per foot all encased in conduit and sealed to prevent water penetration. The detector must be 6 -foot square unless shown otherwise. Construct the loop detector u sing a minimum 3/8 -inch Schedule 40 or Schedule 80 PVC or polypropylene conduit and no. 16 or larger conductor with Type THWN insulation. In new roadways, place the detector in the base course with the top of the conduit flush with the top of the base. Cov er with HMA or concrete pavement. Protect the detector from damage before and during pavement placement. In new reinforced concrete bridge decks, secure the detector to the top of the uppermost layer of reinforcing steel using nylon wire ties. Hold the det ector parallel to the bridge deck using PVC or polypropylene spacers where necessary. Place conduit for lead -in conductors between the uppermost 2 layers of reinforcing steel. Do not install detectors in existing bridge decks unless authorized. Install a d etector in existing pavement before placement of concrete or HMA as follows:

1.Saw cut slots at least 1 -1/4 inches wide into the pavement.
2.Place the detector in the slots. The top of the conduit must be at least 2 inches below the top of the pavement.
3.Test each loop circuit for continuity, circuit resistance, and insulation resistance.
4.Fill saw cuts with elastomeric or hot melt rubberized asphalt sealant for asphalt concrete pavement and with epoxy sealant or hot melt rubberized asphalt sealant for concrete pavement.

87-1.03W Sealants

87-1.03W(1) General

Reserved

87-1.03W(2) Elastomeric Sealant

Apply an elastomeric sealant with a pressure feed applicator.

87-1.03W(3) Asphaltic Emulsion Sealant

Asphaltic emulsion sealant must:

1.Be used for filling slots in asphalt concrete pavement of a maximum width of 5/8 inch
2.Not be used on concrete pavement or where the slope causes the material to run from the slot
3.Be thinned under the manufacturer's instructions
4.Be placed when the air temperature is at least 45 degrees F

87-1.03W(4) Hot -Melt Rubberized Asphalt Sealant

Melt the sealant in a jacketed, double -boiler -type, melting unit. The temperature of the heat transfer medium must not exceed 475 degrees F. Apply the sealant with a pressure feed applicator or a pour pot when the surface temperature of the pavement is greater than 40 deg rees F.

87-1.03X Reserved

87-1.03Y Transformers

Installing a transformer includes placing the transformer inside a pull box, a cabinet, or an enclosure. Use a submersible type transformer inside pull boxes. Wire the trans former for the appropriate voltage. Ground the secondary circuit of the transformer as specified in the NEC. SECTION 87 ELECTRICAL SYSTEMS

87-1.03Z Reserved

87-1.04 Payment

Not Used

87-2 Lighting Systems

87-2.01 General

87-2.01A Summary

Section 87 -2 includes specifications for constructing lighting systems . Lighting system includes:

1.Foundations
2.Pull boxes
3.Conduit
4.Conductors
5.Standards
6.Luminaires
7.Service equipment enclosure
8.Photoelectric control
9.Fuse splice con nectors
10.High mast lighting assemblies The components of a lighting system are shown on the project plans.

87-2.01B Definitions

Reserved

87-2.01C Submittals

Submit a certificate of compliance and test data for the high mast lighting luminaires.

87-2.01D Quality Assurance

Reserved

87-2.02 Materials

87-2.02A General

Reserved

87-2.02B High Mast Lighting Assemblies

A high mast lighting assembly includes the foundation, pole, lowering device system, luminaires, and control pedestal. Each luminaire in a high mast lighting assembly must include a housing, an optical system, and a ballast. The housing must be made of aluminum. A painted or powder -coated housing for a high mast lighting luminaire must be able to withstand a 1,000 - hour salt spray test as specified in ASTM B117. The optical system, consisting of the reflector, refractor or lens, lamp socket, and lamp, must be in a sealed chamber. The chamber must be sealed by a gasket between the reflector and refractor or lens and a gasket between the reflector and lamp socket. The chamber must have a separate filter or filtering gasket for flow of air. An asymmetrical luminaire m ust have a refractor or reflector that is rotatable 360 degrees around a vertical axis to orient the distribution of light. The luminaire must have a slip fitter for mounting on a 2 -inch horizontal pipe tenon and must be adjustable ±3 degrees from the axis of the tenon. SECTION 87 ELECTRICAL SYSTEMS The reflector must have a specular surface made of silvered glass or aluminum protected by either an anodized finish or a silicate film. The reflector must be shaped such that a minimum of light is reflected through the arc tube of the lamp. The refractor and lens must be made of heat -resistant glass. The lamp socket must be a porcelain -enclosed, mogul -multiple type. The shell must contain integral lamp grips to ensure electrical contact under conditions of normal vibrations. The socket must be rated for 1,500 W, 600 V(ac) and 4,000 V(ac) pulse for a 400 W lamp and 5,000 V(ac) pulse for a 1,000 W lamp. The luminaire must have a dual fuse holder for 2 fuses rated at 5 A, 480 V(ac). The fuses must be 13/32 inch by 1 -1/2 inches, standard midget f errule type with a nontime -delay feature. The lamps must be vertical burning, protected from undue vibration, and prevented from backing out of the socket by a stainless steel clamp attached to the luminaire. A 1,000 W metal halide lamp must have an initia l output of 100,000 lumens and an average rated life of 12,000 hours based on 10 hours per start. A 400 W high -pressure sodium lamp must have an initial output of 50,000 lumens. A 1,000 W high - pressure sodium lamp must have an initial output of 140,000 lum ens. The ballast for the luminaire must be a regulator type and have a core and coils, capacitors, and starting aid. Ballast must be:

1.Mounted within a weatherproof housing that integrally attaches to the top of a luminaire support bracket and lamp suppo rt assembly
2.Readily removable without removing the luminaire from the bracket arm
3.Electrically connected to the optical assembly by a prewired quick disconnect The ballast for a metal halide luminaire must comply with luminaire manufacturer's specif ications. The wattage regulation spread at any lamp voltage, from nominal through the life of the lamp, must vary no more than 22 percent for a 1,000 W lamp and a ±10 percent input voltage variation. The ballast's starting line current must be less than it s operating current.

87-2.02C Soffit and Wall -Mounted Luminaires

87-2.02C(1) General

Soffit and wall -mounted luminaires must be weatherproof and corrosion resistant. Each luminaire must include a 70 W high -pressure sodium lamp with a minimum average rated life of 24,000 hours. The lamp socket must be positioned such that the light center of the lamp is located within 1/2 inch of the designed light center of the luminaire. Luminaire wiring must be SFF -2. Flush -mounted soffit luminaire must have:

1.Metal body with two 1 -inch-minimum conduit hubs and a means of anchoring the body into the concrete
2.Prismatic refractor made of heat -resistant polycarbonate: 2.1. Mounted in a door frame 2.2. With the street side identified
3.Aluminum reflector with a specular anodized finish
4.Ballast located either wit hin the housing or in a ceiling pull box if shown
5.Lamp socket The door frame assembly must be hinged, gasketed, and secured to the luminaire body with at least 3 machine screws. SECTION 87 ELECTRICAL SYSTEMS A pendant soffit luminaire must be enclosed and gasketed and have an aluminum finish. Luminaire must have:
1.Aluminum reflector with a specular anodized finish
2.Refractor made of heat -resistant polycarbonate
3.Optical assembly that is hinged and latched for lamp access and a device to prevent dropping
4.Ballast designed for operation in a raintight enclosure
5.Galvanized metal box with a gasketed cover, 2 captive screws, and 2 chains to prevent dropping and for luminaire mounting Wall-mounted luminaire mus t have:
1.Cast metal body
2.Prismatic refractor: 2.1. Made of glass 2.2. Mounted in a door frame
3.Aluminum reflector with a specular anodized finish
4.Integral ballast
5.Lamp socket
6.Gasket between the refractor and the body
7.At least 2 mounting bolts of minimum 5/16 -inch diameter A cast aluminum body of a luminaire to be cast into or mounted against concrete must have a thick coat of alkali -resistant bituminous paint on all surfaces to be in contact with the concrete.

87-2.02C(2) High -Pressure Sodium Lamp Ballasts

87-2.02C(2)(a) General

A high -pressure sodium lamp ballast must operate the lamp for its rated wattage. Starting aids for a ballast must be interchangeable between ballasts of the same wattage and manufacturer without adjustment. The ballast must be provided with a heat -generating component to serve as a heat sink. The capacitor must be placed at the maximum practicable distance from the heat -generating components or thermally shielded to limit the case temperature to 75 degrees C. The transformer and inductor must be resin impregnated for protection against moisture. Capacitors, except for those in starting aids, must be metal cased a nd hermetically sealed. The ballast must have a power factor of 90 percent or greater. For the nominal input voltage and lamp voltage, the ballast design center must not vary more than 7.5 percent from the rated lamp wattage.

87-2.02C(2)(b) Regulator -Type Ballasts

A regulator -type ballast must be designed such that a capacitance variance of ±6 percent does not cause more than ±8 percent variation in the lamp wattage regulation. The ballast must have a current crest factor not exceeding 1.8 for an input voltage variation of ±10 percent. The lamp wattage regulation spread for a lag -type ballast must not vary by more than 18 percent for ±10 percent inpu t voltage variations. The primary and secondary windings must be electrically isolated. The lamp wattage regulation spread for a constant -wattage, autoregulator, lead -type ballast must not vary by more than 30 percent for ±10 percent input voltage variatio ns.

87-2.02C(2)(c) Nonregulator -Type Ballasts

A nonregulator -type ballast must have a current crest factor not exceeding 1.8 for an input volta ge variation of ±5 percent. SECTION 87 ELECTRICAL SYSTEMS The lamp wattage regulation spread for an autotransformer or high reactance type ballast must not vary by more than 25 percent for ±5 percent input voltage variations.

87-2.03 Construction

87-2.03A General

Set the foundations for standards such that the mast arm is perpendicular to the centerline of the roadway. Tighten the cap screws of the luminaire's clamping bracket to 10 ft -lb for roadway luminaires. Label the month and year of the installation inside the luminaire housing 's door. Perform the conductor and operational tests for the system.

87-2.03B High Mast Lighting Assemblies

Mount and connect the luminaires to the accessory support ring. Aim the asymmetrical luminaire to orient the distribution of light.

87-2.03C Soffit and Wall -Mounted Luminaires

For a flush -mounted soffit luminaire :

1.Prevent concrete from getting into the housing during pouring of the concrete for the structure
2.Install the luminaire with the axis vertical and the street side of the refractor oriented as indicated
3.Locate the lumi naire to provide a minimum 2 -foot clearance from the inside surface of the girders and 1-foot clearance from the near face of the diaphragm
4.Install the bridge soffit and ceiling pull box over the same lane For a pendant soffit luminaire :
1.Cast in place the inserts for the no. 8 pull box during concrete placement for a new structure
2.Drill holes for expansion anchors to support the no. 8 pull box on exi sting structures
3.Bond the suspension conduit and luminaire to the pull box For a wall -mounted luminaire , provide:
1.Extension junction box or ring on a ne w structure
2.4 external mounting taps on an existing structure Place the soffits or wall -mounted luminaires in operation as soon as practicable after the falsework has been removed from the structure. If the Engineer orders soffit or wall -mounted lumina ires to be activated before permanent power service is available, installing and removing the temporary power service is change order work.

87-2.04 Payment

Not Used

87-3 Sign Illumination Systems

87-3.01 General

Section 87 -3 includes specifications for constructing sign illumination systems . Sign illumination system includes:

1.Foundations
2.Pull boxes
3.Conduit
4.Conductors
5.Overhead sign luminaires
6.Service equipment enclosure
7.Photoelectric control SECTION 87 ELECTRICAL SYSTEMS The components of a sign illumination system are shown on the project plans.

87-3.02 Materials

Not Used

87-3.03 Construction

Perform the conductor test. Install overhead sign luminaires under the manufacturer's instructions. Do not modify the sign structure or mounting channels. Perform the operational tests for the system.

87-3.04 Payment

Not Used

87-4 Signal and Lighting Systems

87-4.01 General

Section 87 -4 includes specifications for constructing signal and lighting systems . Signal and lighting system includes:

1.Foundations
2.Pull boxes
3.Conduit
4.Conductors and cables
5.Standards
6.Signal heads
7.Service equipment enclosure
8.Department -furnished controller assembly
9.Detectors
10.Telephone demarcation cabinet
11.Accessible pedestrian signals
12.Push button assemblies
13.Pedestrian signal heads
14.Luminaires
15.Photoelectric control
16.Fuse splice connectors
17.Battery backup system
18.Flashing beacons
19.Flashing beacon en closure The components of a signal and lighting system are shown on the project plans.

87-4.02 Materials

87-4.02A General

Reserved

87-4.02B Railroad Preemption

A wire jumper for railroad preemption must be:

1.Stranded
2.No. 14 AWG
3.White with red s tripes

87-4.03 Construction

87-4.03A General

Set the foundation for a standard such that the mast arm is perpendicular to the centerline of the roadway. SECTION 87 ELECTRICAL SYSTEMS Tighten the cap screws of the roadway luminaire's clamping bracket to 10 ft -lb. Label the month and year of the installation inside the luminaire housing's door. Perform the conductor and operational tests for the system.

87-4.03B Railroad Preemption

Connect the C16 harness plug to the C16 socket on the Output File no. 2LX in the controller cabinet. Connect the terminated conductors of the C16 harness to terminal block TB9 on input panel no.1 in the controller cabinet as shown in the following table: Input Panel No. 1 Connections Pin Label TB9 1 J-12D 4 2 J-12J 5 3 J-13D 7 4 J-13J 8 5 J-14D 10 6 J-14J 11 Terminate wire jumpers with spade connectors on both ends. Connect three wire jumpers approximately 4 feet in length as show in the following table: Jumper Connections Jumper Bus TB9 1 DC- 6 2 DC- 9 3 DC- 12 Connect three wire jumpers approximately 2 inches in length as show in the following table: Jumper Connections Jumper Terminal Block Pin Pin 1 TB-12 5 7 2 TB-13 5 7 3 TB-14 5 7

87-4.04 Payment

Not Used

87-5 Ramp Metering Systems

87-5.01 General

Section 87 -5 includes specifications for constructing ramp metering systems . Ramp metering system includes:

1.Foundations
2.Pull boxes
3.Conduit
4.Conductors
5.Standards
6.Signal heads
7.Service equipment enclosure
8.Department -furnished controller assembly
9.Detectors
10.Flashing beacons SECTION 87 ELECTRICAL SYSTEMS The components of a ramp metering system are shown on the project plans.

87-5.02 Materials

Not Used

87-5.03 Construction

Connect the field wiring to the terminal blocks in the controller cabin et. The Engineer provides you a list of field conductor terminations for each controller cabinet. Perform the conductor and operational tests for the system.

87-5.04 Payment

Not Used

87-6 Traffic Monitoring Station Systems

87-6.01 General

Section 87 -6 includes specifications for constructing traffic monitoring station systems . Traffic monitoring station system includes:

1.Foundations
2.Pull boxes
3.Conduit
4.Cables
5.Conductors
6.Service equipment enclosure
7.Controller cabinet
8.Detectors
9.Telephone demarcation cabinet The components of a traffic monitoring station system are shown on the project plans.

87-6.02 Materials

Not Used

87-6.03 Construction

Connect the field wiring to the terminal blocks in the controller cabinet. The Engineer provides you a list of field conductor terminations for the controller cabinet. Perform the conductor and operational tests for the system.

87-6.04 Payment

Not Used

87-7 Flashing Beacon Systems

87-7.01 Gene Ral

Section 87 -7 includes specifications for constructing flashing beacon systems . Flashing beacon system includes:

1.Foundations
2.Pull boxes
3.Conduit
4.Conductors
5.Standards
6.Service equipment enclosure
7.Signal heads
8.Flashing beacon enclosure The components of a flashing beacon system are shown on the project plans. SECTION 87 ELECTRICAL SYSTEMS The flash rate for the flashing beacon must comply with chapter 4L, "Flashing Beacons," of the California MUTCD . The flashing beacon must allow alternating flashing wig -wag operation. The flashing beacon enclosure must have a separate flasher unit installed.

87-7.02 Materials

Not Used

87-7.03 Construction

Perform the conductor and operational tests for the system.

87-7.04 Payment

Not Used

87-8 Pedestrian Hybrid Beacon Systems

87-8.01 General

87-8.01A Summary

Section 87 -8 includes specifications for constructing pedestrian hybrid beacon system s. A pedestrian hybrid beacon system includes:

1.Found ations
2.Pull boxes
3.Conduit
4.Conductors and cables
5.Standards
6.Pedestrian hybrid beacon face
7.Pedestrian signal heads
8.Service equipment enclosure
9.Department -furnished controller assembly
10.Accessible pedestrian signals
11.Push button assemblies
12.Luminaires
13.Fuse splice connectors
14.Battery backup system The components of a pedestrian hybrid beacon system are shown on the project plans.

87-8.01B Definitions

Reserved

87-8.01C Submittals

Reserved

87-8.01D Quality Assura nce

87-8.01D(1) General

Reserved

87-8.01D(2) Quality Control

Verify the sequence for the pedestrian hybrid beacon system per California MUTCD , Chapter 4F, Figure 4F-3 "Sequence for a Pedestrian Hybrid Beacon" during the operational test. Test the battery backup system.

87-8.02 Materials

87-8.02A General

The pedestrian hybrid beacon system must comply with California MUTCD , Chapter 4F. SECTION 87 ELECTRICAL SYSTEMS

87-8.02B Pedestrian Hybrid Beacon Face

A pedestrian hybrid beacon face consists of two red indications on the top and one yellow indication on the bottom .

87-8.03 Construction

Install pedestrian hybrid beacon system under section 87 -4.03A. Install battery backup system.

87-8.04 Payment

Not Us ed

87-9 87-11 Reserved

87-12 Changeable Message Sign Systems

87-12.01 General

Section 87 -12 includes specifications for constructing changeable message sign systems . Changeable message sign system includes:

1.Foundations
2.Pull boxes
3.Conduit
4.Conductors and cables
5.Service equipment enclosure
6.Department -furnished controller cabinet
7.Department -furnished changeable message sign
8.Department -furnished wiring harness
9.Sign disconnect The components o f a changeable message sign system are shown on the project plans.

87-12.02 Materials

Not Used

87-12.03 Construction

Install changeable message sign on sign structure under section 56 -2. Connect the field wiring to the terminal blocks in the sign assembl y and controller cabinet. The Engineer provides you a list of field conductor terminations for each sign cabinet and controller cabinet. The Department maintains the sign assemblies.

87-12.04 Payment

Not Used

87-13 Reserved

87-14 Radar Speed Feedback Sign Systems

87-14.01 General

87-14.01A Summary

Section 87 -14 includes specifications for installing radar speed feedback sign systems . Radar speed feedback sign system includes:

1.Foundations
2.Pull b oxes
3.Conduit
4.Conductors and cables
5.Standards or wood posts 6 SECTION 87 ELECTRICAL SYSTEMS Vehicle speed feedback sign
7.Service equipment enclosure
8.Signs The components of a radar speed feedback sign system are shown on the project plans.

87-14.01B Definitions

Reserved

87-14.01C Submittals

Submit 2 copies of:

1.Test data report complying with NEMA -TS-2 for the vehicle speed feedback sign
2.Shop drawings or installation manuals for the si gn support, electrical connections, attachments, and mounting configurations

87-14.01D Quality Assurance

87-14.01D(1) General

Reserved

87-14.01D(2) Quality Control

Equipment setup must comply with the sign manufacturer's instructions. Notify the Engineer at least 5 business days before performing the system test . Test the system in the presence of the Engineer. Radar speed feedback sign system test consists of:

1.Turning on the radar speed feedback sign system
2.Driving a vehicle and recording the speeds displayed: 2.1. By the vehicle speedometer 2.2. On the vehicle speed feedback sign for the vehicles
3.Performing the test 5 times per lane detected
4.Ensuring that the 5 reco rded speeds of the vehicle speed feedback sign are within ± 1 mph of the vehicle speeds recorded from the vehicle speedometer After successful testing, present the recorded results to the Engineer.

87-14.01D(3) Training

Provide training to a maximum of 4 Department employees on the operation of the vehicle speed feedback sign. Training must be a minimum of 1 hour and include how to program, adjust, troubleshoot, and repair the sign.

87-14.02 Materials

87-14.02A General

Vehicle speed feedback sign consists of a housing, display window, and radar unit. Sign must:

1.Comply with the California MUTCD, Chapter 2B
2.Have an operating voltage of 120 V(ac) for permanent installations
3.Have a maximum weight of 45 lb
4.Have a wind load rating of 90 mph
5.Have an operating temperature range from -34 to 165 degrees F
6.Have a retroreflective white sheeting background

87-14.02B Housings

Housing must:

1.Be weatherproof (NEMA 3R or better) and vandal resistant SECTION 87 ELECTRICAL SYSTEMS
2.Be made of 0.09 -inch-gauge welded aluminum with the outer surfaces being UV resistant
3.Have the manufacture r's name, model number, serial number, date of manufacture, rated voltage and rated current marked inside
4.Have the internal components easily accessible for field repair without removal of the sign

87-14.02C Display Windows

Display window consists of a cover, LED character display, and dimming control. Character display and cover must deflect together without damage to the internal electronics and speed detection components. Cover must be:

1.Vandal resistant and shock absorbent
2.Field replaceable with the removal of external stainless -steel, tamper proof fasteners Cover must be made of a minimum 0.25 -inch-thick, shatter -resistant polycarbonate. LED character display must:
1.Consist of two 7 -segment, solid -state, numeric characters, which must: 1.1. Be a minimum : 1.1.1. 18 inches in height for freeways and expressways 1.1.2. 14 inches in height for conventional highways 1.2. Have a width -to-height ratio between 0.7 and 1.0 1.3. Have a stroke width -to-height ratio of 0.2 1.4. Be visible from a minimum distance of 1 ,500 feet and legible from a minimum distance of 750 feet 1.5. Consist of a minimum 16 LEDs, which must: 1.5.1. Be amber and have a wavelength from 590 to 600 nm and rated for minimum 60,000 hours 1.5.2. Maintain a minimum 85 percent of the initial light output after 48 months of continuous use over the temperature range
2.Be capable of displaying the detected vehicle speed within 1 second
3.Remain blank when no vehicles are detected within the radar detection zone
4.Have the option to flash the pre -set speed limit when the detected vehicle speed is 5 miles higher than the pre -set speed
5.Be viewable only by the approaching traffic Dimming control must:
1.Automatically adjust the character light intensity to provide optimum character visibilit y and legibility under all ambient lighting conditions
2.Have minimum 3 manual dimming modes of different intensities

87-14.02D Radar Units

Radar unit must:

1.Be able to detect up to 3 lanes of appro aching traffic
2.Operate with an internal, low power, 24.159 GHz (K -band)
3.Be FCC approved Part 15 certified
4.Have a speed accuracy of ±1 mph Have a maximum 15 W power consumption

87-14.03 Construction

Install the vehicle speed feedback sign under the manufacturer's instructions. Install R2 -1 SPEED LIMIT sign. Perform the conductor test. Configure the radar speed feedback sign system to detect only traffic in the approach direction of travel. 1238 5 SECTION 87 ELECTRICAL SYSTEMS Perform the radar speed feedback sign system test. Perfo rm the operational test for the system.

87-14.04 Payment

Not Used

87-15 87-17 Reserved

87-18 Interconnection Conduit and Cable

87-18.01 General

Section 87 -18 includes specifications for constructing interconnection conduit and cable . Interconnection conduit and cable includes:

1.Pull boxes
2.Conduit
3.Signal interconnect cables
4.12 position terminal block The components of an interconnection conduit and cable are shown.

87-18.02 Materials

Terminal block must comply with TEES, chapter 1, section 3.

87-18.03 Construction

Test the signal interconnect cable. Install the terminal block on the input panel in the controller cabinet. Connect the signal interconnect cable to the terminal block as sh own in the following table: Signal Interconnect Termination Terminal Block Color 1 BLUE 2 BLACK 3 RED 4 BLACK 5 BROWN 6 BLACK 7 GREEN 8 BLACK 9 YELLOW 10 BLACK 11 WHITE 12 BLACK

87-18.04 Payment

Not Used

87-19 Fiber Optic Cable Systems

87-19.01 General

87-19.01A Summary

Section 87 -19 includes specifications for constructing fiber optic cable systems . A fiber optic cable system includes:

1.Conduit and accessories
2.Vaults SECTION 87 ELECTRICAL SYSTEMS
3.Warning tape
4.Fiber optic cables
5.Fiber optic splice enclosures
6.Fiber distribution units
7.Fiber optic markers
8.Fiber optic connectors and couplers The components of a fiber optic system are shown on the project plans.

87-19.01B Definitions

Reserved

87-19.01C Submittals

At least 15 days before cable installation, submit :

1.Manufacturer 's procedures for pulling fiber optic cable
2.Test reports from a laboratory accredited to International Standards Organization/Inte rnational Electrotechnical Commission 17025 by the American Association for Laboratory Accreditation (A2LA) or the ANSI -ASQ National Accreditation Board (ANAB) for: 2.1. Water penetration 2.2. Cable temperature cycling 2.3. Cable impact 2.4. Cable tensile loading and fiber strain 2.5. Cable compressive loading 2.6. Compound flow 2.7. Cyclic flexing
3.Proof of calibration for the test equipment including: 3.1. Name of calibration facility 3.2. Date of calibration 3.3. Type of equipment, model number and serial number 3.4. Calibration result Submit optical time -domain reflectometer data files for each test in a Microsoft Excel format. After performing the optical time -domain reflectometer test and the power meter and light source test, submit within 4 bus iness days a hard copy and electronic format:
1.Cable Verification Worksheet
2.Segment Verification Worksheet
3.Link Loss Budget Worksheet The worksheets are available at the Division of Construction website.

87-19.01D Quality Assurance

87-19.01D(1) General

Reserved

87-19.01D(2) Quality Control

Notify the Engineer 4 business days before performing field tests. Include exact location of the system or components to be tested. Do not proceed with the testing until authorized. Perform each test in the presence of the Engineer. The optical time -domain reflectometer test consists of:

1.Inspecting the cable segment for physical damage.
2.Measuring the attenuation levels for wavelengths of 1 ,310 an d 1,550 nm in both directions for each fiber using the optical time -domain reflectometer.
3.Comparing the test results with the data sheet provided with the shipment. If there are attenuation deviations greater than 5 percent, the test will be considered unsatisfactory and the cable segment SECTION 87 ELECTRICAL SYSTEMS will be rejected. The failure of any single fiber is a cause for rejection of the entire segment. Replace any rejected cable segments and repeat the test. The power meter and light source test consists of:
1.Testing each fiber in a link using a light source at one end of the link and a power meter at the other end
2.Measuring and recording the power loss for wavelengths of 1 ,310 and 1 ,550 nm in both directions Index matching gel is not allowed. Installation and splicing of the fiber optic cable system must be performed by a certified fiber optic installer. The optical time -domain reflectometer test and the power meter and light source test must be performed by a certified fiber optic technician. Certification for the fiber optic installer and technician must be from an organization recognized by the cable manufacturer and current throughout the duration of the project.

87-19.02 Materials

87-19.02A General

All metal components of the fiber optic cable system must be corrosion resistant. All connectors must be factory -installed and tested. Patch cords, pigtails, and connectors must comply with ANSI/TIA -568. Pigtails must hav e a minimum 80 N pull out strength. A splice cassette may be used in place of a pigtail and a splice tray. Each cable reel must have a weatherproof label or tag with information specified in ANSI/ICEA S -87-640 including:

1.Contractor's name
2.Contract nu mber
3.Number of fibers
4.Cable attenuation loss per fiber at 1 ,310 and 1 ,550 nm The labeled or tagged information must also be in a shipping record in a weatherproof envelope. The envelope must be removed only by the Engineer.

87-19.02B Vaults

A vault must:

1.Comply with section 86 -1.02C and AASHTO HS 20 -44, and load tested under AASHTO M 306.
2.Be a minimum: 2.1. 4 feet wide by 4 feet high by 4 feet long nominal inside dimensions for box type 2.2. 4 feet high by 4 feet outside diameter for round type
3.Have a minimum access of: 3.1. 30 inches diameter for round type 3.2. 3 feet wide by 3 feet long for box type
4.Be precast either modular or monolithic.
5.Have cable racks installed on the interior sides. A rack must: 5.1. Be fabricated from ASTM A36 steel plate 5.2. Support a minimum of 100 pounds per rack arm 5.3. Support a minimum of 4 splice enclosures and a minimum of 4 cables with a minimum slack of 50 feet each 5.4. Be hot -dip galvanized after manufacturing 5.5. Be bonded and grounded
6.Have a minimum: SECTION 87 ELECTRICAL SYSTEMS 6.1. Two 4 -inch diameter knockouts on each side for box type 6.2. Two 4 -inch diameter knockouts placed every 90 degrees for round type
7.Have a minimum 2 -inch-diameter drain hole at the center of base. Entry points for knockouts must not cause the cable to exceed its maximum bend radius. The access cover must:
1.Be a two -piece torsion -assisted sections or a minimum 30 -inch-diameter cast iron
2.Have inset lifting pull slots
3.Have markings CALTRANS and FIBER OPTIC

87-19.02C Fiber Optic Cable

The fiber optic cable must:

1.Comply with 7 CFR parts 1755.900, 1755.901, and 1755.902, and ANSI/ICEA S -87-640
2.Be a singlemode, zero -dispersion, an d have non -gel loose type buffer tubes
3.Have no splices
4.Have a Type H or Type M outer jacket
5.Be shipped on a reel
6.Have 10 feet of length on each end of the cable accessible for testing

87-19.02D Fiber Optic Splice Enclosures

A fiber optic splice enclosure must:

1.Not exceed 36 inches in length, 8 inches in width, and 8 inches in height
2.Be made of thermoplastic material, weather proof, chemical and UV resistant, and re -sealab le
3.Accommodate a minimum of 8 internal splice trays
4.Have from 1/4 to 1 inch in diameter cable entry ports
5.Have brackets, clips and cable ties
6.Have means to anchor the dielectric member of the fiber optic cable
7.Include grounding hardware

87-19.02E Fiber Distribution Units

The fiber distribution unit ) consists of a housing, a patch panel, a 12 -multicolor pigtail, and a splice tray. The fiber distribution unit must be self -contained and pre-assembled. The housing must:

1.Be a 19 -inch rack -mountable modular -metal enclosure
2.Be a one rack unit
3.Have cable clamps to secure buffer tube to the chassis
4.Have cable accesse s with rubber grommets or similar material to prevent the cable from coming in contact with the bare metal
5.Be weatherproof
6.Have a hinged top door with a latch or thumbscrew to hold it in the closed position A patch panel must have a minimum of 12 -singlefiber type connector sleeves. A pigtail must:
1.Be a simplex single mode fiber in a 900 µm tight buffer with a 12 -inch-outer -diameter PVC jacket
2.Have a fiber optic connector attached on one end and bare fiber on the other end
3.Be at least 3 feet in length
4.Have the manufacturer's part number on the jacket Pigtails must be single -fiber or ribbon type.

87-19.02F Patch Cords

Patch cords must: SECTION 87 ELECTRICAL SYSTEMS

1.Be a singlemode fiber in a 900 µm tight buffer with a 0.12 -inch-outer -diameter PVC jacket
2.Have fiber optic connectors attached on both ends
3.Be at least 6 feet in length
4.Have manufacturer's p art number on the jacket Duplex patch cords must be of round cable structure, and not have zip -cord structure.

87-19.02G Splice Trays

Splice trays must:

1.Have brackets to spool inco ming fibers a minimum of 2 turns.
2.Have means to secure and protect incoming buffer tubes, pigtails, and a minimum of 12 heat shrink fusion splices.
3.Be stackable.
4.Have a snap -on or hinged cover. The cover may be transparent.

87-19.02H Fiber Optic Markers

Fiber optic markers must be:

1.Type K -2 (CA) object markers for vaults or pull boxes.
2.Disk markers for paved areas and transition points from unpaved to paved areas. The disk marker must be metallic, lead free and 4 inches in diameter, and must have a mounting stem at the center of the disk. The mounting stem must be a minimum 3 inches long and a minimum 0.70 inch in diameter.
3.Non-reflective Class 1, Type F, flexible post delineato rs for unpaved areas.

87-19.02I Fiber Optic Connectors and Couplers

Connectors must be:

1.0.1-inch ceramic ferrule pre -radiused type
2.Capped when not used Couplers must be made of the same material as the connector's housing and have ceramic sleeves. Singlemode fiber optic connectors must have a yellow strain relief boot or a yellow base.

87-19.03 Construction

87-19.03A General

Perform the optical time -domain reflectometer test :

1.On the fiber optic cable upon its arrival to the job site and before its installation. Complete the Cable Verification Worksheet. Do not install the fiber optic cable until the Engineer's w ritten approval is received.
2.After the fiber optic cable segments have been pulled, but before breakout and termination. Complete the Segment Verification Worksheet.
3.Once the passive cabling system has been installed and is ready for activation. If t he measured individual fusion splice losses exceed -0.30 dB, re -splice and retest. At the conclusion of the optical time-domain reflectometer test, perform the power meter and light source test. If the measured link loss exceeds the calculated link loss, r eplace the unsatisfactory cable segments or splices and retest. Complete the Link Loss Budget Worksheet.

87-19.03B Vaults Installation

Install a vault as shown and with the side facing the roadway a m inimum of 2 feet from the edge of pavement or back of dike, away from traffic. Install the top of the vault flush with surrounding grade in paved areas and 2 inches above the surrounding grade in unpaved areas. Place 6 inches of minor concrete around vault s. In unpaved areas, finish top of concrete at a 2 percent slope away from cover. In paved areas, finish top of concrete to match existing slope. SECTION 87 ELECTRICAL SYSTEMS Bolt the steel cover to the vault when not working in it.

87-19.03C Fiber Optic Cable Installation

Install fi ber optic cable by a certified installer or a representative from the fiber optic cable manufacturer during installation. When using mechanical aids to install fiber optic cable:

1.Maintain a cable bend radius at least twenty times the outside diameter of the cable
2.Use cable grips having a ball bearing swivel
3.Use a pulling force on a cable not to exceed 500 pound -foot or manufacturer's recommended pulling tension, whichever is less When installing the cable using the air blown method, the cable must withstand a static air pressure of 110 psi. Lubricate the cable using a lubricant recommended by the cable manufacturer. Install fiber optic cable without splices except where shown. Provide a minimum of 65 feet of slack for each fiber optic cable at each vault. Divide the slack equally on each side of the splice enclosure. Install tracer wires in the fiber optic conduits and innerducts as shown. Provide a minimum 3 feet of slack tracer wire in each pull box and splice vault from each direction. You may splice tracer wire at intervals of not less than 500 feet and only inside splice vaults or pull boxes . If a fiber optic cable and tracer wire are installed in an innerduct, pulling a separate f iber optic cable into a spare duct to replace damaged fiber will not be allowed. Apply a non -hygroscopic filling compound to fiber optic cable openings. Seal the ends of conduit and innerducts after cables are installed. Install strain relief for fiber optic cable entering a fiber optic enclosure. Identify fibers and cables by direct labeling, metal tags, or bands fastened in such a way that they will not move. Use mechanical methods for labeling. Provide identification on each fiber optic cable or each group of fiber optic cables in each vault and at the end of terminated fibers. Fiber optic cable must be identified as shown in the following table: SECTION 87 ELECTRICAL SYSTEMS Cable Identificationa Sequence order Description Code Numbers of characters 1 Fiber type S: Singlemode 1 2 Fiber count ###: Example 048 3 3 Begin point T: TMC H: Hub V: Video Node D: Data Node C: Cable Node TV: Camera CM: CMS E: Traffic Signal RM: Ramp Meter TM: Traffic Monitoring/ Count Station/Vehicle Count Station (VDS, TMS) HA: Highway Advisory Radio EM: Extinguishable Message Sign RW: Roadway Weather Information System WM: Weigh In Motion WS: Weigh -Station Bypass System SV: Vault SC: Splice Cabinet 1 or 2 4 Begin point county abbreviation AA or AAA: Examples: Orange (ORA), San Mateo (SM) 2 or 3 5 Begin point route number ###: Examples: 005, 082, 114 3 6 Begin point post mile #####: 02470 (example 024.70): Actual PM value to the 1/100 value 5 7 End Point In the same way as for Begin Point 1 or 2 8 End point county abbreviation In the same way as for Begin Point County Abbreviation 2 or 3 9 End point route number In the same way as Begin Point Route Number 3 10 End point post mile In the same way as Begin Point Post Mile 5 aCable identification example: The cable code S 048 SV SM 084 02470 SV SC 082 02510 describes a singlemode, 48 strand, cable starting at a fiber optic vault in San Mateo County on Route 84 at post mile 24.70, and ending at another fiber optic vault in Santa Clara County on Route 82 at post mile 25.10. Place labels on the cables at the following points:
1.Fiber optic vault and pull box entrances and exits
2.Splice enclosures entrance and exit
3.Fiber distribution unit entrance Lace fiber optic cable inside controller cabinets and secure to the cage. Support the fiber optic cable within 6 inches from a termination and every 2 feet. Secure fiber optic cables to the cable racks. Store excess cable in a figure 8 fashion. SECTION 87 ELECTRICAL SYSTEMS

87-19.03D Fiber Optic Cable Splic es

Use fusion splicing for fiber optic cables . Splice single -buffer tube cable to multi -buffer tube cable using the mid -span access method under manufacturer's instructions. Any mid -span access splice or fiber distribution unit termination must involve only those fibers being spliced as shown. Place fiber splices in the splice enclosures installed in the vaults.

87-19.03E Splice Enclosures Installation

Maintain an equal amount of slac k on each side of the splice enclosure . Secure the fiber optic splices in splice tray. Secure the splice trays to the inner enclosure. Label cables and buffer tubes. Do not seal fiber splice enclosure until authorized and the power meter and light source test is performed. Seal the enclosure under manufacturer's instructions. Flash test the outer enclosure under manufacturer's instructions in the presence of the Engineer. Visually inspe ct the enclosure. If bubbles are present, identify the locations where the bubbles are present, take corrective actions and repeat the flash test until no bubbles are present. Attach the splice enclosure to the side wall of a vault or hub with a minimum 2 feet distance between the ground and the bottom of the enclosure. Secure fiber optic cables to the chassis using cable clamps for fiber optic units. Connect a minimum of one bonding conductor to a grounding electrode after mounting the fiber optic enclosur e to the wall. If there are multiple bonding conductors, organize the conductors in a neat way.

87-19.03F Fiber Optic Distribution Unit Installation

Spool incoming buffer tubes 2 feet in the splice tray and expose 1 foot of individual fibers . Maintain a minimum 2 -inch-bend radius during and after installation in the splice tray. Splice incoming fibers in the splice tray. Restrain each fiber in the splice tray. Do not apply stress on the fiber when located in its final position. Secure buffer tubes near the entrance of the splice tray. Secure splice trays under manufacturer's instructions. Label splice tray after splicing is completed. Install patch cords in fiber distribution units and patch panels. Permanently label each cord and each connector in the panel with the system as shown.

87-19.03G Fiber Optic Markers Installation

Install fiber optic markers at 12 -inch o ffset on the side furthest away from the edge of travel way:

1.For fiber optic cable at 500 feet apart in areas where the distance between vaults or pull boxes is greater than 500 feet
2.Adjacent to vaults and pull boxes
3.For fiber optic cable turns at : 3.1. Beginning of the turn 3.2. Middle of the arc 3.3. End of the turn When a fiber optic cable crosses a roadway or ramp, install a disk marker over the conduit trench on:
1.Every shoulder within 6 inches from the edge of pavement SECTION 87 ELECTRICAL SYSTEMS
2.Delineated median
3.Each side of a barrier Install markers under section 81 except each retroreflective face must be parallel to the road centerline and facing away from traffic.

87-19.04 Payment

Not Used

87-20 Temporary Electrical Systems

87-20.01 General

Section 87 -20 includes specifications for providing, maintaining, and removing temporary electrical systems . Temporary systems may be mounted on wood post s or trailer s. Obtain the Department's authorization for the type of temporary electrical system and its installation method. A temporary system must operate on a continuous, 24 -hour basis. A temporary electrical system must have a primary power source and a back -up power source from:

1.Commercial utility company
2.Generator system
3.Photovoltaic system

87-20.02 Materials

87-20.02A General

Temporary wood poles must comply with section 48 -6. The components of a temporary system are shown on the project plans. If you use Type UF -B cable, the minimum conductor size mu st be no. 12. A back -up power source must:

1.Have an automatic transfer switch
2.Start automatically and transfer the system load upon reaching the operating voltage in the event of a power source failure A trailer must be equipped with devices to level and plumb the temporary system .

87-20.02B Generators

A generator must:

1.Be 120 V(ac) or 120/240 V(ac), 60 Hz, 2.5 kW minimum, continuous -duty type
2.Be powered by a gasoline, LPG, or diesel engine operating at approximately 1,800 rpm with an automatic oil feed
3.Be equipped to provide automatic start -stop operation with a 12 V starting system
4.Have generator output circuits that have overcurrent protection with a maximum setting of 15 A
5.Have a spark arrester complying with Pub Cont Code § 4442

87-20.02C Automatic Transfer Switches

An automatic transfer switch must provide:

1.Line voltage monitoring in the event of a power outage that signals the back -up power source to start
2.Start delay, adjustable from 0 to 6 seconds, to prevent st arting if the power outage is only momentary and a stop delay, adjustable from 0 to 8 minutes, to allow the back -up power source to unload
3.Transfer delay from 0 to 120 seconds to allow the back -up power source to stabilize before connecting to the load and retransfer delay from 0 to 32 minutes to allow the line voltage to stabilize SECTION 87 ELECTRICAL SYSTEMS
4.Mechanical interlock to prevent an application of power to the load from both sources and to prevent backfeeding from the back -up power source to the primary power source

87-20.02D 87-20.02G Reserved

87-20.02H Temporary Flashing Beacon Systems

A temporary flashing beacon system consists of a flashing beacon system, wood pole, and a power source. The system must comply w ith the specifications for flashing beacon system s in section 87 -7.

87-20.02I Temporary Lighting Systems

A temporary lighting system consists of a lighting system, a power source, and wood poles. The system mu st comply with the specifications for lighting system s in section 87 -2.

87-20.02J Temporary Signal Systems

A temporary signal system consists of a signal and lighting system , wood poles and posts, and a power source . The system must comply with the specifications for signal and lighting system s in section 87 -4, except signal heads may be mounted on a wood pole, mast arm, tether wire, o r a trailer .

87-20.02K Temporary Radar Speed Feedback Sign Systems

A temporary radar speed feedback sign s ystem must comply with the specifications for a radar speed feedback sign system in section 87 -14, except , the LED character display must remain blan k when no vehicles are detected or when the detected vehicle speed is 10 miles less than the preset speed .

87-20.03 Construction

87-20.03A General

Provide power and telecommunication services for temporary systems. Do not use existing services unless authorized. Commercial power must be 120 V(ac) or 120/240 V(ac) single phase. Make arrangements with the utility company for providing service. Protect the power sou rce in a locked enclosure. Provide keys for all locks to the Engineer. You may install conductors and cables:

1.In a conduit
2.Suspended from wood poles at least 25 feet above the roadway
3.Suitable for direct burial Install conduit outside the paved a rea at a minimum of 12 inches below grade for Type 1 and 2 conduit and at a minimum of 18 inches below grade for Type 3 conduit. Install direct burial conductors and cables outside the paved area at a minimum depth of 24 inches below grade. Install conduct ors and cables in Type 1, 2, or 3 conduit when mounted on wood poles to a height of 10 feet above the grade. Place conductors across structures in a Type 1, 2, or 3 conduit. Attach the conduit to the outside face of the structure . Mount the photoelectric u nit at the top of the standard or wood post. You may a bandon :
1.Conductors and cables in sawed slots
2.Underground conduit after removing conductors SECTION 87 ELECTRICAL SYSTEMS

87-20.03B 87-20.03G Reserved

87-20.03H Temporary Flashing Beacon Systems

Protect each flashing beacon with a fused splice connector on the line side. Wherever conductors are run overhead, install the fused splice connector in the line side outside of the control assembly.

87-20.03I Temporar y Lighting Systems

Protect each luminaire with a fused splice connector on the line side. Wherever conductors are run overhead, install the fuse d splice connectors in the line side before entering the mast arm.

87-20.03J Temporary Signal Systems

You may splice conductors that run to a terminal c ompartment or a signal head on a pole to the through conductors of the same phase in a pull box adjacent to the pole. Do not splice conductors or cables except in a pull box or in a NEMA 3R enclosure. The Department provides the timing for the temporary si gnal. Maintain the temporary signal except for the Department -furnished controller assembly.

87-20.03K Reserved

87-20.04 Payment

Not Used

87-21 Existing Electrical Systems

87-21.01 General

Section 87 -21 includes general specifications for performing work on existing electrical systems .

87-21.02 Materials

Not Used

87-21.03 Construction

87-21.03A General

You may abandon unused underground conduit after pu lling out all conductors and removing conduit terminations from the pull boxes. Remove foundation under section 56 -3.01C(2)(a). If standards are to be salvaged, remove:

1.All components
2.Mast arms from the standards
3.Luminaires, signal heads, and sign al mounting assemblies from the standards and mast arms If the existing material is unsatisfactory for reuse and the Engineer orders you to replace it with new material, replacing the existing material with new material is change order work. If the remove d electrical equipment is to be reinstalled, supply all materials and equipment, including signal mounting assemblies, anchor bolts, nuts, washers, and concrete, needed to complete the new installation. Match the color of the existing housing , when replaci ng an existing accessible pedestrian signal or push button assembly. Remove electrical equipment, designated as a hazardous waste.

87-21.03B Maintaining Existing Electrical Systems

87-21.03B(1) General

Maintain the existing electrical system in working o rder during the progress of the work. Conduct your operations to avoid damage to the elements of the systems.

Source: California Standard Specifications, 2024 Edition. Pages 12131253 of 1,372.