87 ELECTRICAL SYSTEMS
87-1 General
87-1.01 General
87-1.01A Summary
Section 87 -1 includes general specifications for constructing and installing electrical systems. The Department deducts the cost for maintenance performed by the Department on new or portions of existing systems modified under the Contract.
87-1.01B Definitions
Reser ved
87-1.01C Submittals
Submit a digital file for geographic information system mapping for:
87-1.01D Quality Assurance
87-1.01D(1) General
Reserved
87-1.01D(2) Quality Control
87-1.01D(2)(a) General
Before shipping the material to the job site, submit to METS test samples of:
87-1.01D(2)(b) Electronic Markers
Electronic marker test consists of placing the electronic marker in the pull box, temporarily marking the pull box location with a utility flag, and using a compatible electronic marker locator to perform the following location test in the presence of the Engineer:
87-1.01D(2)(c) Battery Backup System
Notify the Engineer 48 hours before testing the battery backup system . Test the battery backup system in the presence of the Engineer by turning off the service power to the electrical system to be powered by the battery backup system . The electrical system must remain in full continuous operation for 30 minutes. If the test fails, correct the probl em and retest the system. After successful completion of the test, turn on the service power for the electrical system.
87-1.01D(2)(d) Piezoelectric Axle Sensors
Piezoelectric axle sensors test consists of:
87-1.02 Materials
Not Used
87-1.03 Construction
87-1.03A Gene ral
The Engineer determines the final locations of electrical systems. Verify the locations of electrical systems and the depths of existing detectors, conduits, and pull boxes. Notify the Engineer before performing work on the existing system. You may shu t down the system for alteration or removal. SECTION 87 ELECTRICAL SYSTEMS Where an existing Department underground facility is shown within 10 feet of any excavation, locate and field mark the facility before performing work that could damage or interfere with the existing facility. If a mandrel is used, it must be sized per the manufacture r's requirements. If an existing facility is within 2 feet of an excavation, determine the exact location of the facility by excavating with hand tools before using any power -operated or power -driven excavating or boring equipment. A vacuum excavator may be used if authorized. Notify the Engineer immediately if an existing facility is damaged by your activities:
87-1.03B Conduit Installation
87-1.03B(1) General
The installation of conduit includes installing caps, bushings, and pull tape and terminating the conduit in pull boxes, foundations, poles, or a structure. Limit the number of bends in a conduit run to no more than 360 degrees between pull points. Use conduit to enclose conductors except where they are inst alled overhead or inside standards or posts. You may use a larger size conduit than specified for the entire length between termination points. Do not use a reducing coupling. Extend an existing conduit using the same material. Terminate conduits of differ ent materials in a pull box. Install conduit of a minimum size :
87-1.03B(2) Conduit Installation for Structures
87-1.03B(2)(a) General
Paint exposed Type 1 conduit on painted, stained, or colored structures . Comply with section 59 -3 except the final coat of paint must match the structure. Install galvanized steel hangers, steel brackets, and other fittings to support conduit i n or on a wall or bridge structure . Cast into concrete or pass -through openings conduit installed inside box girders. Size openings to fit the conduit and fittings, and remove lost deck material. Do not install conduit through drainage openings. Install co nduit parallel or at right angles to girders. Install expansion fitting s on structures with only longitudinal movement. Size the fittings for the longitudinal movement of the structure . The p iston inside expansion fittings must be positioned so the piston expands the full movement of the bridge without damaging the fitting. Install deflection fitting s on structures with only transverse movement. Size the fittings for the transverse movements of the structure. All block outs for deflection fittings must have clearance or be sized for the physical size and the maximum rated movement of the fittings without touching concrete or structural elements. Install multiple expansion, and deflection, or combination expansion -deflection fittings in series on structures w ith longitudinal and transverse movement. Size the fittings for the longitudinal and transverse movements of the structure . The total movement of the multiple fittings must be greater than the structure movement range. Fill expansion and deflection fitting pockets with resilient weatherproof compound. Install expansion and deflection fittings parallel to superstructure girders. SECTION 87 ELECTRICAL SYSTEMS
87-1.03B(2)(b) New Structures
Seal and make watertight the conduits which lead to soffits, wall -mounted luminaires, other lights, and fixtures located below the pull box grade. If you place a conduit through the side of a nonmetallic pull box, terminate the conduit 2 inches from the wall and 2 inches above the bottom. Slop e the conduit toward the top of the box. For ease of installation and if authorized, you may use Type 4 conduit instead of Type 1 conduit for the final 2 feet of conduit entering a pull box in a reinforced concrete structure. For conduit installed inside o f bridge structures, you must:
87-1.03B(2)(c) Existing Structures
Install surface -mounted conduit :
87-1.03B(3) Conduit Installation Underground
87-1.03B(3)(a) General
Notify the Engineer at least 4 business days before starting horizontal directional drilling method or jack and drill method . Install conduit to a depth of:
87-1.03B(3)( b) Conduit in Trenches
87-1.03B(3)(b)(i) General
Backfill trench with:
87-1.03B(3)( b)(ii) High Density Polyethylene Conduit Installation
For swee ps, maintain a conduit bend radius of a minimum 10 times the outside diameter of the conduit. Conduits must not protrude more than 2 inches inside the pull box and vaults, and must enter at an angle less than 20 degrees from either the vertical or horizontal axis. Demonstrate a minimum of 2 test fusions to the Engineer prior to performing fusion operations on HDPE conduit to be installed. Join HDPE conduit using electro fusion couplings under the manufa cturer 's instructions . Do not expose conduit to direct flame. The electro fusion must be performed by a person certified by the conduit manufacturer. Slurry concrete must be pigmented to match color no. 21105 of AMS -STD-595. Blow out all conduits with compressed air until all foreign material is removed, before installing innerducts . Install innerducts as one continuous unit between vaults. Innerducts may be interrupted inside pull boxes located between vaults and cabinets. Lubricate innerducts per manu facturer's instructions during installation. Seal the ends of conduit after cables or pull tape are installed.
87-1.03B(3)(b)(iii) Trench-In-Pavement Method
Install conduit in a trench approximatel y 2 inches wider than the outside diameter of the conduit but not exceeding 6 inches in width. Dig the trench by hand to the required depth at pull boxes. Backfill the trench with slurry cement to the top of the pavement's surface by the end of each workda y. When work includes resurfacing the roadway, complete the trenching before the final pavement layer is applied. When work does not include resurfacing the roadway, within 3 day s after trenching:
87-1.03B(3)(c) Horizontal Directional Drilling Method
Install a conduit to a minimum depth of 4 feet and maximum depth of 6 feet. If you must install a conduit less than 4 feet in depth or greater than 6 feet in depth, the installation must be authorized. The diameter of the bore hole must be no larger than 1.5 times the outs ide diameter of the conduit. Water -based mineral slurry or wetting solution may be used to lubricate the boring tool and stabilize the soil surrounding the boring path. SECTION 87 ELECTRICAL SYSTEMS Dispos e of residue per section 13 -4.03D. The horizontal directional drilling equipment must have directional control of the boring tool and have an electronic boring tool location detection system. During operation, the equipment must be able to determine the location of the tool both horizontally and vertically. Use a mandrel to prove the c onduit is free and clear of dirt, rocks, and other debris after installation.
87-1.03B(3)(d) Jack and Drill Method
Keep the jacking or drilling pit 2 feet away from the edge of pavement except when instal ling conduit under rail -road tracks. Construct the jacking or drilling pit a minimum of 13 feet from the centerline of the track to the closest side of the pit. Do not weaken the pavement or soften the subgrade with excessive use of water. Cover the jacking pit with planking if left overnight. If an obstruction is encountered, obtain authorization to cut small holes in the pavement to locate or remove the obstruction. You may install Type 2 or Type 3 con duit under the pavement if a hole larger than the conduit's diameter is predrilled. The predrilled hole must be less than one and half the conduit's diameter. Remove the conduit used for drilling or jacking and install new conduit for the completed work.
87-1.03C Installation of Pull Boxes
87-1.03C(1) General
Install pull boxes no more than 200 feet apart. Place the cover on the box when not working in it.
87-1.03C(2) Roadway Pull Boxes
87-1.03C(2)(a) General
You may instal l larger pull boxes than specified or shown and additional pull boxes to facilitate the work except in structures. Where a roadway pull box is adjacent to a post or standard, place the pull box within 5 feet from the post or standard on the downstream side of traffic when practical . Install a pull box on a minimum 6 -inch deep bed of crushed rock and grout it before installing conductors. The grout must be from 0.5 to 1 inch thick and sloped toward the drain hole. Place a layer of roofing paper between the g rout and the crushed rock sump. Make a 1 -inch drain hole through the grout at the center of the pull box. Set the pull box such that the top is 1 -1/4 inches above the surrounding grade in unpaved areas and leveled with the finished grade in sidewalks and o ther paved areas. Grout around conduits that are installed through the sides of the pull box. Bond and ground the metallic conduit before installing conductors and cables in the conduit. Bond metallic conduits in a nonmetallic pull box using bonding bushin gs and bonding jumpers. Do not install pull boxes in concrete pads, curb ramps, or driveways. Reconstruct the sump of a pull box if disturbed by your activities. If the sump was grouted, remove and replace the grout.
87-1.03C(2)(b) Nontraffic Pull Boxes
For a buried nontraffic pull box , install the electronic marker and set the box such that the top is from 6 to 8 inches below the surrounding grade. Place a 20 -mil-thick plastic sheet made of HDPE or PVC virgin compounds to prevent water from entering the box. When a pull box is in a structure, modify the base as required. SECTION 87 ELECTRICAL SYSTEMS Place mortar between a nontraffic pull box and a pull box extension. Where a nontraffic pull box is in the vicinity of a curb in an unpaved area, place the box adjacent to the back of the curb if practical. If you replace the cover on a nontraffic pull box, anchor it to the box. Perform the electronic marker test.
87-1.03C(2)(c) Traffic Pull Boxes
Place minor concrete around and under a traffic pull box as shown . Bolt the steel cover to the box when not working in it . Bond the steel cover to the conduit with a minimum 3 -foot-long jumper and bolt it down after installing the conductors and cables.
87-1.03C(2)(d) Tamper-Resistant Pull Boxes
Install the tamper -resistant pull boxes under the manufacturer 's instructions.
87-1.03C(3) Structure Pull Boxes
Install structure pull boxes parallel to the structure. After removing the knockouts, flatten the surrounding area. Bond conduit to a structure pull box using locknuts on the inside and outside of the box. Cover pull boxes with a 1/4 -inch plywo od during pouring of PCC. For a no. 9 pull box, the upper edge of the plywood must fit against the lower edge of the rain tight hood. Install no. 7 pull box with bottom flanges flush with the bottom of the box girder. Place top and bottom covers and seal t he pull box during PCC pouring. For no. 9 and 9A pull boxes:
87-1.03D Battery Backup System Cabinets
Install the battery backup system cabinet to the right side of the controller cabinet. If installation on the right side is not possible, obtain authorization for installation on the left side. Construct access opening between controller cabinet and battery backup cabinet using:
87-1.03E Excavating and Backfilling for Electrical Systems
87-1.03E(1) General
Notify the Engineer at least 72 hours before starting excavation activities. Dispose of surplus excavated material. Restrict closures for excavation on a street or highway to 1 lane at a time unless otherwise specified. 1 SECTION 87 ELECTRICAL SYSTEMS
87-1.03E(2) Trenching
Do not trench until conduit or direct burial cables are on-site and ready for installation . Place excavated material in a location that will not interfere with traffic or surface drainage. Compact native material backfill to a minimum relative compaction of:
87-1.03E(3) Concrete Pads, Foundations, and Pedestals
Construct concrete pads, foundations , and pedestals under section 56 -3. Construct a pad in front of a Type III service equipment enclosure. The pad must be 24 inches in length, 4 inches in thickness, and must match the width of the foundation. In unpaved areas, place the top of the foundation 6 inches above the surrounding grade, excep t place the top:
87-1.03F Conductors and Cable s Installations
87-1.03F(1) General
The installation of conductors and cables includes splicing conductors and attaching the terminals and connectors to the conductors. Clean the conduit , install conduit bushings, and pull all conductors and cables as a unit. If new conductors or cables are to be added in an existing conduit: Remove the content
87-1.03F(2) Cables
87-1.03F(2)(a) General
Reserved
87-1.03F(2)(b) Communication Cables
87-1.03F(2)(b)(i) General
Terminate the ends of the communica tion cables as shown.
87-1.03F(2)(b)(ii) Category 5E and 6 Cables
Do not splice category 5E and 6 cables .
87-1.03F(2)(b)(iii) Telephone Cables
Do not splice telephone cables between the telephone demarcation point and the contr oller cabinet.
87-1.03F(2)(c) Copper Cables
87-1.03F(2)(c)(i) General
Reserved
87-1.03F(2)(c)(ii) Detector Lead -in Cables
Install a Type B or C detector lead -in cable in conduit. Seal the ends of the lead -in cable before installing it in the conduit to prevent moisture from entering the cable. Splice loop conductors for each direction of travel for the same phase, terminati ng in the same pull box, to a separate lead -in cable running from the pull box adjacent to the loop detector to a sensor unit mounted in the controller cabinet. Install the lead -in cable without splices except at the pull box when connecting to loop wire. Verify in the presence of the Engineer that the loops are operational before making the final splices between loop conductors and the lead -in cable. Identify and tag each lead -in cable with the detector designation at the cabinet and pull box adjacent to the loops.
87-1.03F(2)(c)(iii) Conductors Signal Cables
Do not splice signal cables. Provide identification at the ends of terminated conductors in a cable as shown. Provide identification for each cable in each pull box showing the signal standard to which it is connected. Connect conductors in a 12 -conductor cable as shown in the following table: SECTION 87 ELECTRICAL SYSTEMS 12CSC Color Code and Functional Connection Color code Termination Phase Red Red signal 2, 4, 6, or 8 Yellow Yellow signal 2, 4, 6, or 8 Brown Green signal 2, 4, 6, or 8 Red/black stripe Red signal 1, 3, 5, or 7 Yellow/black stripe Yellow signal 1, 3, 5, or 7 Brown/black stripe Green signal 1, 3, 5, or 7 Black/red stripe Spare or as required for red or DONT WALK -- Black/white stripe Spare or as required for yellow -- Black Spare or as required for green or WALK -- Red/white stripe Pedestrian signal DONT WALK -- Brown/white stripe Pedestrian signal WALK -- White Terminal block Neutral Use the neutral conductor only with the phases associated with that cable. Do not intermix neutral conductors from different cables except at the signal controller.
87-1.03F(2)(c)(iv) Signal Interconnect Cable s
Do not splice the cable unless authorized. If splices are authorized, insulate the conductor splices with heat -shrink tubing and overlap the insulation at least 0.6 inch. Cover the splice area of the cable with heat -shrink tubi ng and overlap the cable jacket at least 1 -1/2 inches. Provide a minimum of 3 feet of slack at each splice.
87-1.03F(2)(c)(v) Railroad Preemption Cable s
Do not splice railroad preemption cable from controller cabinet to r ailroad cabinet. Terminate individual conductors with ferrule connectors in the controller cabinet. Provide identification on both ends of the cable and connect the cable end in the controller cabinet as shown in the following table: Color Code and Functional Connection Conductor no. Color code Controller cabinet field terminal connections Conductor identification 1 Black Not Used Spare 2 White Not Used Spare 3 Red FT8-A145 Health Status DC+ 4 Green Not Used Spare 5 Orange FT7-A134 Simultaneous DC- 6 Blue FT7-A131 Advance DC- 7 White/black strip e Not Used Spare 8 Red/black strip e FT8-A144 Gate Down /Island 9 Green/black strip e Field Terminal FT 8-A142 Advance Pedestrian Preemption 10 Orange/black strip e FT7-A135 Simultaneous Primary 11 Blue/black strip e FT7-A132 Advance Primary 12 Black/white strip e Not Used Spare 13 Red/white strip e FT8-A143 Gate Down /Island DC- 14 Green/white strip e FT8-A141 Advance Pedestrian Preemption DC- 15 Blue/white strip e FT7-A133 Advance Secondary 16 Black/red strip e Not Used Spare 17 White/red strip e FT8-A146 Health Status DC- 18 Orange/red strip e FT7-A136 Simultaneous Secondary Keep all exposed conductors the same length and individually insulate spare conductors against each other. SECTION 87 ELECTRICAL SYSTEMS Provide a minimum 6 feet of slack in the pull box adjacent to the railroad cabinet. Connect the cable end in the railroad cabinet as directed by the railroad agency r epresentative.
87-1.03F(3) Conductors
87-1.03F(3)(a) General
Do not run conductors to a terminal block on a standard unless they are to be connected to a signal head mounted on that standard. Provide 3 spare conductors in all conduits containing ramp metering and traffic signal conductors. Install a separate conductor for each terminal of a push button assembly and accessible pedestrian signal.
87-1.03F(3)(b) Reserved
87-1.03F(3)(c) Copper Conductors
87-1.03F(3)(c)(i) General
Install a minimum no. 8 grounding copper conductor in conduit and connect it to all -metal components. Where conductors from different service points occupy the same conduit or standard, enclose the conductors from one of the services in flexible or rigid metal conduit.
87-1.03F(3)(c)(ii) Inductive Loop Conductors
Install a Type 1 or 2 inductive loop conductor except use Type 2 for Type E and F loop detectors. Install the conductor without splices except at the pull bo x.
87-1.03F(4) Manual Installation Method
Use an inert lubricant for placing conductors and cables in conduit . Pull the conductors and cables into the conduit by hand using pull tape.
87-1.03F(5) Direct Burial Aluminum Cable Installation Method
Install direct burial aluminum cable at a minimum 30 inches below grade in unpaved areas or at a minimum 18 inches below finished grade in paved areas. Do not splice the direct burial aluminum cable between pull boxes and enclosures. Fill trench with slu rry cement backfill to between 4 to 6 inches below finished grade under section 19 - 3.02E. Fill the remaining trench to finished grade with native material. In paved area, fill the remaining trench to finished grade with the same material of the paved area.
87-1.03G Equipment Identification Ch aracters
The Engineer provides you with a list of the equipment identification characters . Stencil the characters or apply the reflective self -adhesive labels to a clean surface. Treat the edges of s elf-adhesive characters with an edge sealant. Place the characters on the side facing traffic on:
87-1.03H Conductor and Cables Splices
87-1.03H(1) General
You may splice :
87-1.03H(2) Splice Insulation Methods
Insulate splices in a multiconductor cable to form a watertight joint and to prevent moisture absorption by the cable. Use heat -shrink tubing or Method B to insulat e a splice. Use heat -shrink tubing as follows:
87-1.03I Connectors and Terminals
Apply connectors and terminals to cables and conductors using a crimping compression tool under the manufacturer's instructions. The tool must prevent opening of the handles until the crimp is completed. Install crimp -style terminal lugs on stranded con ductors smaller than no. 14. Solder no. 8 and smaller copper conductors to connectors and terminal lugs.
87-1.03J Standards, Poles, Pedestals, and Posts
Install standards, poles, pedestals, and posts under section 56 -3. Ground standards with a handhole by attaching a bonding jumper from the bolt or lug inside the standard to a metal conduit or to the grounding wire in the adjacent pull box. The bonding jumper must be visible when the handhole cov er is removed. Ground standards without a handhole or standards with a slip base by attaching a bonding jumper to all anchor bolts using ground clamp s and connecting it to a metal conduit or to the grounding wire in the adjacent pull box. The bonding jumpe r must be visible after mortar has been placed on the foundation.
87-1.03K Piezoelectric Axle Sensors
Obtain authorization for exact locations for installation of the piezoelectric axle sensors . SECTION 87 ELECTRICAL SYSTEMS Cut slots fo r axle sensors and screened transmission cables under section 87 -1.03V(2). Install piezoelectric axle sensors in slots. Fill the slot with epoxy grout under section 95 -1.02H. Ensure t he grout does not exceed 165 degrees F while curing. Do not reopen the la ne to traffic until the epoxy sets. Perform the conductor test. Connect the field wiring to the terminal blocks in the controller cabinet. Perform the piezoelectric axle sensor test. Perform the operational test. Failure of the system to record and store d ata as required for an accumulated time exceeding 3 hours during the 5 -day period is cause for the operational test to be rejected and repeated.
87-1.03L Utility Service
87-1.03L(1) General
Install the service equipment early enough to allow the utility to complete its work before completion of the electrical work. At least 15 days before permanent electrical and telecommunication service is required, request the service connections for permanent installations. The Department arranges with the utilities for completion of the connections and pays all costs and fees required by the utilities.
87-1.03L(2) Electric Service
87-1.03L(2)(a) General
If service equipment is to be installed on a utility -owned pole, furnish and install the conduit, conductors, pull boxes, and other necessary material to complete the service installation. The service utility decides the position of the riser and equipment on the pole.
87-1.03L(2)(b) Electric Service for Irrigation
Establishing electric service for irrigation includes installing conduit, conductors, and pull boxes and making connections from the service point to the ir rigation controllers.
87-1.03L(2)(c) Electric Service for Booster Pumps
Establishing electric service for a booster pump includes installing conduit, conductors, and pull boxes and making connections f rom the service point to the booster pump enclosure.
87-1.03L(3) Telecommunications Service
Establishing telecommunication service includes installing conduit, conductors, and pull boxes and making connect ions from the service point to the telephone demarcation cabinet.
87-1.03M Photoelectric Controls
Mount the photoelectric unit on the top of the pole for Type I, II, and III photoelectric controls . Use mounting brackets where pole -top mounting is not possible. Orient the p hotoelectric unit to face north. Mount the enclosure at a height of 6 feet above finished grade on the same standard as the photoelectric unit. Install a minimum 100 VA, 480/120 V(ac) transform er in the contactor enclosure to provide 120 V(ac) for the photoelectric control unit when switching 480 V(ac), 60 Hz circuits.
87-1.03N Fused Splice Connectors
Install a fuse splice connector with a fuse in eac h ungrounded conductor for luminaires, except for overhead sign luminaires. The connector must be located in the pull box adjacent to the luminaires. If the pull box for the roadway luminaire is tamper resistant, install a fuse splice connector with 10 A f use in the pull box and an additional fuse splice connector with a 5 A fuse in the handhole. Install a fuse splice connector with a fuse on primary side of transformer. SECTION 87 ELECTRICAL SYSTEMS Crimp the connector terminals onto the ungrounded conductors using a tool under the man ufacturer's instructions. Insulate the terminals and make them watertight.
87-1.03O Grounding Electrodes
Install a grounding electrode for each cabinet, service equipment enclosure, and transformer. Attach a ground ing conductor to the electrode using either a ground clamp or exothermic weld. Connect the other end of the conductor to the cabinet, service equipment enclosure, and transformer.
87-1.03P Service Equipment Enclosures
Installing a service equipment enclos ure includes constructing the foundation and pad and installing conduit, adjacent pull boxes, and grounding electrode. Locate the foundation such that the minimum clearance around the front and back of the e nclosure complies with NEC, article 110.26, "Spaces About Electrical Equipment, (600 V, nominal or less)." Apply a sealing compound between the foundation and the enclosure before installing the enclosure . Bond and ground metal conduit as specified in NEC and by the service utility except the grounding electrode conductor must be no. 6 or larger. If circuit breakers and components do not have a description on engraved phenolic nameplates, install them using stainless steel rivets or screws under section 86 -1.02P(2).
87-1.03Q Cabinets
87-1.03Q(1) General
Installing a cabinet includes constructing the foundation and pad and installing conduit, adjacent pull boxes, and grounding electrode. Apply a mastic or caulki ng compound before installing the cabinet on the foundation to seal the openings. Connect the field wiring to the terminal blocks in the cabinet. Neatly arrange and lace or enclose the conductors in plastic tubing or raceway. Terminate the conductors with properly sized captive or spring spade terminals. Apply a crimp -style connector and solder them. Install and solder a spade -type terminal on no. 12 and smaller field conductors and a spade -type or ring - type terminal on conductors larger than no. 12.
87-1.03Q(2) Department -Furnished Controller Cabinets
Arrange for the delivery of Department -furnished controller cabinets .
87-1.03Q(3) Reserved
87-1.03Q(4) Telephone Demarcation Cabinets
Installing a telephone demarcation cabinet includes installing conduit, cable, and pull boxes to the controller cabinet. Install the cabinet with the back toward the nearest lane of traffic.
87-1.03R Signal Heads
87-1.03R(1) General
Installing a signal head includes mounting the heads on standards and mast arms, installing backplates and visors, and wiring conductors to the terminal blocks. Keep the heads covered or direct th em away from traffic until the system is ready for operation.
87-1.03R(2) Signal Faces
Use the same brand and material for the signal faces at each location. Program the programmable visibility signal faces und er the manufacturer's instructions. The indication must be visible only in those areas or lanes to be controlled. SECTION 87 ELECTRICAL SYSTEMS
87-1.03R(3) Backplates
Install backplates using at least six 10 -24 or 10 -32 self -tapping and locki ng stainless steel machine screws and flat washers. If a plastic backplate requires field assembly, attach each joint using at least four no.10 machine screws. Each machine screw must have an integral or captive flat washer, a hexagonal head slotted for a standard screwdriver, and either a locking nut with an integral or captive flat washer or a nut, flat washer, and lock washer. Machine screws, nuts, and washers must be stainless steel or steel with a zinc or black oxide finish. If a metal backplate has 2 or more sections, fasten the sections with rivets or aluminum bolts peened after assembly to avoid loosening. Install the backplate such that the background light is not visible between the backplate and the signal face or between sections.
87-1.03R(4) Si gnal Mounting Assemblies
Install a signal mounting assembly such that its members are arranged symmetrically and plumb or level. Orient each mounting assembly to allow maximum horizontal clearance t o the adjacent roadway. For a bracket -mounted assembly, bolt the terminal compartment or pole plate to the pole or standard. In addition to the terminal compartment mounting, attach the upper pipe fitting of Type SV -1-T with 5 sections or a SV -2-TD to the standard or pole using the mounting detail for signal heads without a terminal compartment. Use a 4 -1/2-inch slip fitter and set screws to mount an assembly on a post top. After installing the assembly, clean and paint the exposed threads of the galvan ized conduit brackets and bracket areas damaged by the wrench or vise jaws. Use a wire brush to clean and apply 2 coats of unthinned, organic zinc -rich primer. Do not use an aerosol can to apply the primer. Install the conductors in the terminal compartmen t and secure the cover.
87-1.03S Pedestrian Signal Heads
Installing a pedestrian signal head includes mounting the heads on standards and wiring conductors to the terminal blocks. Install the pedestrian signal m ounting assembly under section 87 -1.03R(4). Use the same brand and material for the pedestrian signal faces at each location. Install a pedestrian signal face such that its members are arranged symmetrically and plumb or level.
87-1.03T Accessible Pedestr ian Signals
Install accessible pedestrian signals of the same manufacturer at each location . Do not install APS components inside the controller cabinet. Identify conductors on both ends of the signal inte rface cable. Label each conductor according to their function under the manufacturer's instructions. Connect the signal interface cable to the terminal blocks in the APS and pedestrian signal head . Attach the accessible pedestrian signal to the standard with hex screws by drilling and tapping. Drill a 1 - inch diameter hole on the standard for the signal interface cable. Install the 9 by 12 inches R10 -3j (CA) sign using the adapter plate provided by the APS manufacturer. Point the arrow on the accessible pedestrian signal in the crossing direction. Cut Type 2 post 2 inches above the R10 series sign. Furnish the equipment and hardware to set up and calibrate the accessible pedestrian signal. SECTION 87 ELECTRICAL SYSTEMS Arrange to have a manufacturer's representative at the job site to program the accessible pedestrian signal with an audible message or tone.
87-1.03U Push Button Assemblies
Install the push button assembly and the R10 series sign on the crosswalk side of the stand ard. Attach the sign to the assembly for Type B assemblies. Attach the sign to the standard using 2 straps and saddle brackets for Type C assemblies. You may use straps and saddle brackets to secure the push button to the standard. Cut Type 2 post 2 inches above the R10 series sign.
87-1.03V Detectors
87-1.03V(1) General
Installing a detector includes installing inductive loop conductors, sealant, conduit, and pull boxes. Center the detectors in the traffic lanes. Do not splice the detector conductor.
87-1.03V(2) Inductive Loop Detectors
Mark the location of the inductive loop detectors such that the distance between the side of the loop and a lead-in saw cut from an adjacent detector is at least 2 feet. The distance between lead -in saw cuts must be at least 6 inches. Saw cut the slots under section 13-4.03E(7). The bottoms of the slots must be smooth with no sharp edges. For Type E detector loops, saw the slots such that the sides are vertical. Wash the slots clean using water and blow dry them with compressed air to remove all moisture and debris. Identify the start of the conductor. Waterproof the ends of a Type 2 loop conductor before installing it in the conduit to prevent moisture from entering the cable. Install the loop conductor in the slots and lead -in saw cuts using a 3/16 -to 1/4 -inch-thick wood paddle. Hold the conductors in place at the bottom of the slot with wood paddles during placement of the sealant. Wind adjacent loops on the same sensor unit channel in opposite directions. Twist the conductors for each loop into a pair consisting o f a minimum of 2 turns per foot before placing them in the lead -in saw cut and the conduit leading to the pull box. Do not install more than 2 twisted pairs of conductors per lead -in saw cut. Test each loop for continuity, circuit resistance, and insulatio n resistance before filling the slots with sealant. Remove excess sealant from the adjacent road surface before it sets. Do not use solvents to remove the excess. Identify the loop conductor pair in the pull box, marking the start with the letter S and the end with the letter F. Band conductors in pairs by lane in the pull box adjacent to the loops and in the cabinet. Identify each pair with the detector designation and loop number. Install the conductors in a compacted layer of HMA immediately below the up permost layer if more than one layer will be placed. Install the loop conductors before placing the uppermost layer of HMA. Fill the slot with a sealant flush to the surface. Install the conductors in the existing pavement if one layer of HMA is to be plac ed. Install the loop conductors before placing the layer of HMA. Fill the slot with a sealant flush to the surface. SECTION 87 ELECTRICAL SYSTEMS
87-1.03V(3) Preformed Inductive Loop Detectors
Install a preformed inductive loop detector consisting of 4 turns in the loop and a lead -in conductor pair twisted at least 2 turns per foot all encased in conduit and sealed to prevent water penetration. The detector must be 6 -foot square unless shown otherwise. Construct the loop detector u sing a minimum 3/8 -inch Schedule 40 or Schedule 80 PVC or polypropylene conduit and no. 16 or larger conductor with Type THWN insulation. In new roadways, place the detector in the base course with the top of the conduit flush with the top of the base. Cov er with HMA or concrete pavement. Protect the detector from damage before and during pavement placement. In new reinforced concrete bridge decks, secure the detector to the top of the uppermost layer of reinforcing steel using nylon wire ties. Hold the det ector parallel to the bridge deck using PVC or polypropylene spacers where necessary. Place conduit for lead -in conductors between the uppermost 2 layers of reinforcing steel. Do not install detectors in existing bridge decks unless authorized. Install a d etector in existing pavement before placement of concrete or HMA as follows:
87-1.03W Sealants
87-1.03W(1) General
Reserved
87-1.03W(2) Elastomeric Sealant
Apply an elastomeric sealant with a pressure feed applicator.
87-1.03W(3) Asphaltic Emulsion Sealant
Asphaltic emulsion sealant must:
87-1.03W(4) Hot -Melt Rubberized Asphalt Sealant
Melt the sealant in a jacketed, double -boiler -type, melting unit. The temperature of the heat transfer medium must not exceed 475 degrees F. Apply the sealant with a pressure feed applicator or a pour pot when the surface temperature of the pavement is greater than 40 deg rees F.
87-1.03X Reserved
87-1.03Y Transformers
Installing a transformer includes placing the transformer inside a pull box, a cabinet, or an enclosure. Use a submersible type transformer inside pull boxes. Wire the trans former for the appropriate voltage. Ground the secondary circuit of the transformer as specified in the NEC. SECTION 87 ELECTRICAL SYSTEMS
87-1.03Z Reserved
87-1.04 Payment
Not Used
87-2 Lighting Systems
87-2.01 General
87-2.01A Summary
Section 87 -2 includes specifications for constructing lighting systems . Lighting system includes:
87-2.01B Definitions
Reserved
87-2.01C Submittals
Submit a certificate of compliance and test data for the high mast lighting luminaires.
87-2.01D Quality Assurance
Reserved
87-2.02 Materials
87-2.02A General
Reserved
87-2.02B High Mast Lighting Assemblies
A high mast lighting assembly includes the foundation, pole, lowering device system, luminaires, and control pedestal. Each luminaire in a high mast lighting assembly must include a housing, an optical system, and a ballast. The housing must be made of aluminum. A painted or powder -coated housing for a high mast lighting luminaire must be able to withstand a 1,000 - hour salt spray test as specified in ASTM B117. The optical system, consisting of the reflector, refractor or lens, lamp socket, and lamp, must be in a sealed chamber. The chamber must be sealed by a gasket between the reflector and refractor or lens and a gasket between the reflector and lamp socket. The chamber must have a separate filter or filtering gasket for flow of air. An asymmetrical luminaire m ust have a refractor or reflector that is rotatable 360 degrees around a vertical axis to orient the distribution of light. The luminaire must have a slip fitter for mounting on a 2 -inch horizontal pipe tenon and must be adjustable ±3 degrees from the axis of the tenon. SECTION 87 ELECTRICAL SYSTEMS The reflector must have a specular surface made of silvered glass or aluminum protected by either an anodized finish or a silicate film. The reflector must be shaped such that a minimum of light is reflected through the arc tube of the lamp. The refractor and lens must be made of heat -resistant glass. The lamp socket must be a porcelain -enclosed, mogul -multiple type. The shell must contain integral lamp grips to ensure electrical contact under conditions of normal vibrations. The socket must be rated for 1,500 W, 600 V(ac) and 4,000 V(ac) pulse for a 400 W lamp and 5,000 V(ac) pulse for a 1,000 W lamp. The luminaire must have a dual fuse holder for 2 fuses rated at 5 A, 480 V(ac). The fuses must be 13/32 inch by 1 -1/2 inches, standard midget f errule type with a nontime -delay feature. The lamps must be vertical burning, protected from undue vibration, and prevented from backing out of the socket by a stainless steel clamp attached to the luminaire. A 1,000 W metal halide lamp must have an initia l output of 100,000 lumens and an average rated life of 12,000 hours based on 10 hours per start. A 400 W high -pressure sodium lamp must have an initial output of 50,000 lumens. A 1,000 W high - pressure sodium lamp must have an initial output of 140,000 lum ens. The ballast for the luminaire must be a regulator type and have a core and coils, capacitors, and starting aid. Ballast must be:
87-2.02C Soffit and Wall -Mounted Luminaires
87-2.02C(1) General
Soffit and wall -mounted luminaires must be weatherproof and corrosion resistant. Each luminaire must include a 70 W high -pressure sodium lamp with a minimum average rated life of 24,000 hours. The lamp socket must be positioned such that the light center of the lamp is located within 1/2 inch of the designed light center of the luminaire. Luminaire wiring must be SFF -2. Flush -mounted soffit luminaire must have:
87-2.02C(2) High -Pressure Sodium Lamp Ballasts
87-2.02C(2)(a) General
A high -pressure sodium lamp ballast must operate the lamp for its rated wattage. Starting aids for a ballast must be interchangeable between ballasts of the same wattage and manufacturer without adjustment. The ballast must be provided with a heat -generating component to serve as a heat sink. The capacitor must be placed at the maximum practicable distance from the heat -generating components or thermally shielded to limit the case temperature to 75 degrees C. The transformer and inductor must be resin impregnated for protection against moisture. Capacitors, except for those in starting aids, must be metal cased a nd hermetically sealed. The ballast must have a power factor of 90 percent or greater. For the nominal input voltage and lamp voltage, the ballast design center must not vary more than 7.5 percent from the rated lamp wattage.
87-2.02C(2)(b) Regulator -Type Ballasts
A regulator -type ballast must be designed such that a capacitance variance of ±6 percent does not cause more than ±8 percent variation in the lamp wattage regulation. The ballast must have a current crest factor not exceeding 1.8 for an input voltage variation of ±10 percent. The lamp wattage regulation spread for a lag -type ballast must not vary by more than 18 percent for ±10 percent inpu t voltage variations. The primary and secondary windings must be electrically isolated. The lamp wattage regulation spread for a constant -wattage, autoregulator, lead -type ballast must not vary by more than 30 percent for ±10 percent input voltage variatio ns.
87-2.02C(2)(c) Nonregulator -Type Ballasts
A nonregulator -type ballast must have a current crest factor not exceeding 1.8 for an input volta ge variation of ±5 percent. SECTION 87 ELECTRICAL SYSTEMS The lamp wattage regulation spread for an autotransformer or high reactance type ballast must not vary by more than 25 percent for ±5 percent input voltage variations.
87-2.03 Construction
87-2.03A General
Set the foundations for standards such that the mast arm is perpendicular to the centerline of the roadway. Tighten the cap screws of the luminaire's clamping bracket to 10 ft -lb for roadway luminaires. Label the month and year of the installation inside the luminaire housing 's door. Perform the conductor and operational tests for the system.
87-2.03B High Mast Lighting Assemblies
Mount and connect the luminaires to the accessory support ring. Aim the asymmetrical luminaire to orient the distribution of light.
87-2.03C Soffit and Wall -Mounted Luminaires
For a flush -mounted soffit luminaire :
87-2.04 Payment
Not Used
87-3 Sign Illumination Systems
87-3.01 General
Section 87 -3 includes specifications for constructing sign illumination systems . Sign illumination system includes:
87-3.02 Materials
Not Used
87-3.03 Construction
Perform the conductor test. Install overhead sign luminaires under the manufacturer's instructions. Do not modify the sign structure or mounting channels. Perform the operational tests for the system.
87-3.04 Payment
Not Used
87-4 Signal and Lighting Systems
87-4.01 General
Section 87 -4 includes specifications for constructing signal and lighting systems . Signal and lighting system includes:
87-4.02 Materials
87-4.02A General
Reserved
87-4.02B Railroad Preemption
A wire jumper for railroad preemption must be:
87-4.03 Construction
87-4.03A General
Set the foundation for a standard such that the mast arm is perpendicular to the centerline of the roadway. SECTION 87 ELECTRICAL SYSTEMS Tighten the cap screws of the roadway luminaire's clamping bracket to 10 ft -lb. Label the month and year of the installation inside the luminaire housing's door. Perform the conductor and operational tests for the system.
87-4.03B Railroad Preemption
Connect the C16 harness plug to the C16 socket on the Output File no. 2LX in the controller cabinet. Connect the terminated conductors of the C16 harness to terminal block TB9 on input panel no.1 in the controller cabinet as shown in the following table: Input Panel No. 1 Connections Pin Label TB9 1 J-12D 4 2 J-12J 5 3 J-13D 7 4 J-13J 8 5 J-14D 10 6 J-14J 11 Terminate wire jumpers with spade connectors on both ends. Connect three wire jumpers approximately 4 feet in length as show in the following table: Jumper Connections Jumper Bus TB9 1 DC- 6 2 DC- 9 3 DC- 12 Connect three wire jumpers approximately 2 inches in length as show in the following table: Jumper Connections Jumper Terminal Block Pin Pin 1 TB-12 5 7 2 TB-13 5 7 3 TB-14 5 7
87-4.04 Payment
Not Used
87-5 Ramp Metering Systems
87-5.01 General
Section 87 -5 includes specifications for constructing ramp metering systems . Ramp metering system includes:
87-5.02 Materials
Not Used
87-5.03 Construction
Connect the field wiring to the terminal blocks in the controller cabin et. The Engineer provides you a list of field conductor terminations for each controller cabinet. Perform the conductor and operational tests for the system.
87-5.04 Payment
Not Used
87-6 Traffic Monitoring Station Systems
87-6.01 General
Section 87 -6 includes specifications for constructing traffic monitoring station systems . Traffic monitoring station system includes:
87-6.02 Materials
Not Used
87-6.03 Construction
Connect the field wiring to the terminal blocks in the controller cabinet. The Engineer provides you a list of field conductor terminations for the controller cabinet. Perform the conductor and operational tests for the system.
87-6.04 Payment
Not Used
87-7 Flashing Beacon Systems
87-7.01 Gene Ral
Section 87 -7 includes specifications for constructing flashing beacon systems . Flashing beacon system includes:
87-7.02 Materials
Not Used
87-7.03 Construction
Perform the conductor and operational tests for the system.
87-7.04 Payment
Not Used
87-8 Pedestrian Hybrid Beacon Systems
87-8.01 General
87-8.01A Summary
Section 87 -8 includes specifications for constructing pedestrian hybrid beacon system s. A pedestrian hybrid beacon system includes:
87-8.01B Definitions
Reserved
87-8.01C Submittals
Reserved
87-8.01D Quality Assura nce
87-8.01D(1) General
Reserved
87-8.01D(2) Quality Control
Verify the sequence for the pedestrian hybrid beacon system per California MUTCD , Chapter 4F, Figure 4F-3 "Sequence for a Pedestrian Hybrid Beacon" during the operational test. Test the battery backup system.
87-8.02 Materials
87-8.02A General
The pedestrian hybrid beacon system must comply with California MUTCD , Chapter 4F. SECTION 87 ELECTRICAL SYSTEMS
87-8.02B Pedestrian Hybrid Beacon Face
A pedestrian hybrid beacon face consists of two red indications on the top and one yellow indication on the bottom .
87-8.03 Construction
Install pedestrian hybrid beacon system under section 87 -4.03A. Install battery backup system.
87-8.04 Payment
Not Us ed
87-9 87-11 Reserved
87-12 Changeable Message Sign Systems
87-12.01 General
Section 87 -12 includes specifications for constructing changeable message sign systems . Changeable message sign system includes:
87-12.02 Materials
Not Used
87-12.03 Construction
Install changeable message sign on sign structure under section 56 -2. Connect the field wiring to the terminal blocks in the sign assembl y and controller cabinet. The Engineer provides you a list of field conductor terminations for each sign cabinet and controller cabinet. The Department maintains the sign assemblies.
87-12.04 Payment
Not Used
87-13 Reserved
87-14 Radar Speed Feedback Sign Systems
87-14.01 General
87-14.01A Summary
Section 87 -14 includes specifications for installing radar speed feedback sign systems . Radar speed feedback sign system includes:
87-14.01B Definitions
Reserved
87-14.01C Submittals
Submit 2 copies of:
87-14.01D Quality Assurance
87-14.01D(1) General
Reserved
87-14.01D(2) Quality Control
Equipment setup must comply with the sign manufacturer's instructions. Notify the Engineer at least 5 business days before performing the system test . Test the system in the presence of the Engineer. Radar speed feedback sign system test consists of:
87-14.01D(3) Training
Provide training to a maximum of 4 Department employees on the operation of the vehicle speed feedback sign. Training must be a minimum of 1 hour and include how to program, adjust, troubleshoot, and repair the sign.
87-14.02 Materials
87-14.02A General
Vehicle speed feedback sign consists of a housing, display window, and radar unit. Sign must:
87-14.02B Housings
Housing must:
87-14.02C Display Windows
Display window consists of a cover, LED character display, and dimming control. Character display and cover must deflect together without damage to the internal electronics and speed detection components. Cover must be:
87-14.02D Radar Units
Radar unit must:
87-14.03 Construction
Install the vehicle speed feedback sign under the manufacturer's instructions. Install R2 -1 SPEED LIMIT sign. Perform the conductor test. Configure the radar speed feedback sign system to detect only traffic in the approach direction of travel. 1238 5 SECTION 87 ELECTRICAL SYSTEMS Perform the radar speed feedback sign system test. Perfo rm the operational test for the system.
87-14.04 Payment
Not Used
87-15 87-17 Reserved
87-18 Interconnection Conduit and Cable
87-18.01 General
Section 87 -18 includes specifications for constructing interconnection conduit and cable . Interconnection conduit and cable includes:
87-18.02 Materials
Terminal block must comply with TEES, chapter 1, section 3.
87-18.03 Construction
Test the signal interconnect cable. Install the terminal block on the input panel in the controller cabinet. Connect the signal interconnect cable to the terminal block as sh own in the following table: Signal Interconnect Termination Terminal Block Color 1 BLUE 2 BLACK 3 RED 4 BLACK 5 BROWN 6 BLACK 7 GREEN 8 BLACK 9 YELLOW 10 BLACK 11 WHITE 12 BLACK
87-18.04 Payment
Not Used
87-19 Fiber Optic Cable Systems
87-19.01 General
87-19.01A Summary
Section 87 -19 includes specifications for constructing fiber optic cable systems . A fiber optic cable system includes:
87-19.01B Definitions
Reserved
87-19.01C Submittals
At least 15 days before cable installation, submit :
87-19.01D Quality Assurance
87-19.01D(1) General
Reserved
87-19.01D(2) Quality Control
Notify the Engineer 4 business days before performing field tests. Include exact location of the system or components to be tested. Do not proceed with the testing until authorized. Perform each test in the presence of the Engineer. The optical time -domain reflectometer test consists of:
87-19.02 Materials
87-19.02A General
All metal components of the fiber optic cable system must be corrosion resistant. All connectors must be factory -installed and tested. Patch cords, pigtails, and connectors must comply with ANSI/TIA -568. Pigtails must hav e a minimum 80 N pull out strength. A splice cassette may be used in place of a pigtail and a splice tray. Each cable reel must have a weatherproof label or tag with information specified in ANSI/ICEA S -87-640 including:
87-19.02B Vaults
A vault must:
87-19.02C Fiber Optic Cable
The fiber optic cable must:
87-19.02D Fiber Optic Splice Enclosures
A fiber optic splice enclosure must:
87-19.02E Fiber Distribution Units
The fiber distribution unit ) consists of a housing, a patch panel, a 12 -multicolor pigtail, and a splice tray. The fiber distribution unit must be self -contained and pre-assembled. The housing must:
87-19.02F Patch Cords
Patch cords must: SECTION 87 ELECTRICAL SYSTEMS
87-19.02G Splice Trays
Splice trays must:
87-19.02H Fiber Optic Markers
Fiber optic markers must be:
87-19.02I Fiber Optic Connectors and Couplers
Connectors must be:
87-19.03 Construction
87-19.03A General
Perform the optical time -domain reflectometer test :
87-19.03B Vaults Installation
Install a vault as shown and with the side facing the roadway a m inimum of 2 feet from the edge of pavement or back of dike, away from traffic. Install the top of the vault flush with surrounding grade in paved areas and 2 inches above the surrounding grade in unpaved areas. Place 6 inches of minor concrete around vault s. In unpaved areas, finish top of concrete at a 2 percent slope away from cover. In paved areas, finish top of concrete to match existing slope. SECTION 87 ELECTRICAL SYSTEMS Bolt the steel cover to the vault when not working in it.
87-19.03C Fiber Optic Cable Installation
Install fi ber optic cable by a certified installer or a representative from the fiber optic cable manufacturer during installation. When using mechanical aids to install fiber optic cable:
87-19.03D Fiber Optic Cable Splic es
Use fusion splicing for fiber optic cables . Splice single -buffer tube cable to multi -buffer tube cable using the mid -span access method under manufacturer's instructions. Any mid -span access splice or fiber distribution unit termination must involve only those fibers being spliced as shown. Place fiber splices in the splice enclosures installed in the vaults.
87-19.03E Splice Enclosures Installation
Maintain an equal amount of slac k on each side of the splice enclosure . Secure the fiber optic splices in splice tray. Secure the splice trays to the inner enclosure. Label cables and buffer tubes. Do not seal fiber splice enclosure until authorized and the power meter and light source test is performed. Seal the enclosure under manufacturer's instructions. Flash test the outer enclosure under manufacturer's instructions in the presence of the Engineer. Visually inspe ct the enclosure. If bubbles are present, identify the locations where the bubbles are present, take corrective actions and repeat the flash test until no bubbles are present. Attach the splice enclosure to the side wall of a vault or hub with a minimum 2 feet distance between the ground and the bottom of the enclosure. Secure fiber optic cables to the chassis using cable clamps for fiber optic units. Connect a minimum of one bonding conductor to a grounding electrode after mounting the fiber optic enclosur e to the wall. If there are multiple bonding conductors, organize the conductors in a neat way.
87-19.03F Fiber Optic Distribution Unit Installation
Spool incoming buffer tubes 2 feet in the splice tray and expose 1 foot of individual fibers . Maintain a minimum 2 -inch-bend radius during and after installation in the splice tray. Splice incoming fibers in the splice tray. Restrain each fiber in the splice tray. Do not apply stress on the fiber when located in its final position. Secure buffer tubes near the entrance of the splice tray. Secure splice trays under manufacturer's instructions. Label splice tray after splicing is completed. Install patch cords in fiber distribution units and patch panels. Permanently label each cord and each connector in the panel with the system as shown.
87-19.03G Fiber Optic Markers Installation
Install fiber optic markers at 12 -inch o ffset on the side furthest away from the edge of travel way:
87-19.04 Payment
Not Used
87-20 Temporary Electrical Systems
87-20.01 General
Section 87 -20 includes specifications for providing, maintaining, and removing temporary electrical systems . Temporary systems may be mounted on wood post s or trailer s. Obtain the Department's authorization for the type of temporary electrical system and its installation method. A temporary system must operate on a continuous, 24 -hour basis. A temporary electrical system must have a primary power source and a back -up power source from:
87-20.02 Materials
87-20.02A General
Temporary wood poles must comply with section 48 -6. The components of a temporary system are shown on the project plans. If you use Type UF -B cable, the minimum conductor size mu st be no. 12. A back -up power source must:
87-20.02B Generators
A generator must:
87-20.02C Automatic Transfer Switches
An automatic transfer switch must provide:
87-20.02D 87-20.02G Reserved
87-20.02H Temporary Flashing Beacon Systems
A temporary flashing beacon system consists of a flashing beacon system, wood pole, and a power source. The system must comply w ith the specifications for flashing beacon system s in section 87 -7.
87-20.02I Temporary Lighting Systems
A temporary lighting system consists of a lighting system, a power source, and wood poles. The system mu st comply with the specifications for lighting system s in section 87 -2.
87-20.02J Temporary Signal Systems
A temporary signal system consists of a signal and lighting system , wood poles and posts, and a power source . The system must comply with the specifications for signal and lighting system s in section 87 -4, except signal heads may be mounted on a wood pole, mast arm, tether wire, o r a trailer .
87-20.02K Temporary Radar Speed Feedback Sign Systems
A temporary radar speed feedback sign s ystem must comply with the specifications for a radar speed feedback sign system in section 87 -14, except , the LED character display must remain blan k when no vehicles are detected or when the detected vehicle speed is 10 miles less than the preset speed .
87-20.03 Construction
87-20.03A General
Provide power and telecommunication services for temporary systems. Do not use existing services unless authorized. Commercial power must be 120 V(ac) or 120/240 V(ac) single phase. Make arrangements with the utility company for providing service. Protect the power sou rce in a locked enclosure. Provide keys for all locks to the Engineer. You may install conductors and cables:
87-20.03B 87-20.03G Reserved
87-20.03H Temporary Flashing Beacon Systems
Protect each flashing beacon with a fused splice connector on the line side. Wherever conductors are run overhead, install the fused splice connector in the line side outside of the control assembly.
87-20.03I Temporar y Lighting Systems
Protect each luminaire with a fused splice connector on the line side. Wherever conductors are run overhead, install the fuse d splice connectors in the line side before entering the mast arm.
87-20.03J Temporary Signal Systems
You may splice conductors that run to a terminal c ompartment or a signal head on a pole to the through conductors of the same phase in a pull box adjacent to the pole. Do not splice conductors or cables except in a pull box or in a NEMA 3R enclosure. The Department provides the timing for the temporary si gnal. Maintain the temporary signal except for the Department -furnished controller assembly.
87-20.03K Reserved
87-20.04 Payment
Not Used
87-21 Existing Electrical Systems
87-21.01 General
Section 87 -21 includes general specifications for performing work on existing electrical systems .
87-21.02 Materials
Not Used
87-21.03 Construction
87-21.03A General
You may abandon unused underground conduit after pu lling out all conductors and removing conduit terminations from the pull boxes. Remove foundation under section 56 -3.01C(2)(a). If standards are to be salvaged, remove:
87-21.03B Maintaining Existing Electrical Systems
87-21.03B(1) General
Maintain the existing electrical system in working o rder during the progress of the work. Conduct your operations to avoid damage to the elements of the systems.