Incidental Construction (600-699)

632SIGNAL CABLE

FL · 2024 Standard SpecificationsBook pages 851852View official source ↗

632-1 Description.

Furnish and install underground and aerial signal cable as shown in the Plans and in accordance with Standard Plans, Index 634-001.

632-2 Materials.

Use only new materials meeting the requirements of this Section.

632-2.1 Signal Cable: Use either polyethylene insulated, polyvinyl chloride jacketed

signal cable conforming to the requirements of the International Municipal Signal Association, Inc. (IMSA ) Specification No. 19-1 or polyethylene insulated, polyethylene jacketed signal cable conforming to the requirements of IMSA Specification No. 20-1. Use signal cable conductors of stranded copper, No. 14 AWG or larger.

632-2.2 Cable Support Wire: Provide utilities grade zinc -coated support wire meeting

the requirements of ASTM A475, whether separate or integral to signal cable, having a minimum nominal diameter of 1/4 inches.

632-2.3 Cable Attachment Hardware: Ensure that all bolts and nuts less tha n 5/8 inch

in diameter are passivated stainless steel, Type 316 or Type 304 and meet the requirements of ASTM F593 and ASTM F594 for corrosion resistance. Ensure that all bolts and nuts 5/8 inch and over in diameter are galvanized and meet the requirements of A STM A307. Use attachment hardware with sufficient tensile strength for the application. Use stainless steel lashing wire, galvanized or stainless steel lashing rod, cable rings or self -locking cable ties of UV stabilized black plastic having a minimum tens ile strength of 100 pounds.

632-3 Installation Requirements.

Except for mast arm assemblies, install signal cable in continuous lengths between the traffic signal controller cabinet and the first disconnect hanger (or traffic signal head) on the span and between the traffic signal controller cabinet and each pedestrian signal head and pedestrian detector. Do not use the neutral return conductor for pedestrian detectors as a neutral return for any other device. Conductors for the pedestrian signal head and the push button must be separated at the base of the pedestal and routed to the detection panel using separate raceways.

632-3.1 Number of Conductors: Determine the number of conductors required for each

signal cable unless specified in the Contract Docu ments. Provide three spare conductors for each signal cable used at all signal installations. Install the three spare conductors from the controller cabinet through each disconnect hanger (or traffic signal head) to the furthermost disconnect hanger (or traffic signal head). Identify all spare conductors in a controller cabinet and ground them to the controller cabinet ground bus bar. Provide spare conductors within the controller cabinet of sufficient length to reach the furthermost field wiring termin als in the cabinet.

632-3.2 Protection of Cable: Ensure cable drawn through conduit, ducts, drilled holes

protected by a rubber grommet, or support structures is installed in such a manner as to prevent damage to conductors or insulation. FY 2023-24 Return to Table of Contents

632-3.3 Cabling for Mast Arm Assembly: Continuous lengths of cab le between the

traffic signal controller cabinet, signal heads (or disconnect hangers), pedestrian signal heads and pedestrian detectors will be allowed only when specified in Contract Documents.

632-3.4 Cable Terminations: Terminate signal cable in the t erminal by inserting the

bared conductors into a compression type terminal block. When barrier terminal blocks are specified in the Contract Documents, crimp insulated fork or ring terminals to the bared conductors using a calibrated ratchet -crimping too l and connect the forks or ring terminals to the barrier terminal block. Neatly form and tie wrap all cable terminations. If disconnect hangers are specified in the Contract Documents, terminate spare wires at the terminal strip located inside the disc onnect hangers. Individually cap or tape any additional spares in the disconnect hanger. Connect signal cables for a mast arm assembly in the terminal compartment when provided.

632-4 Method of Measurement.

The Contract unit price for signal cable, furn ished and installed, will include furnishing all material, hardware, support wire, cable ties, cable clamps, lashing wire, terminal connectors, cable grounding and labor necessary for a complete and accepted installation. For intersections where new strai n poles, monotubes, or mast arms are installed, payment for signal cable will be based on the number of intersections at which signal cable is furnished and installed. For all other applications, including repair and replacement of signal cable, payment f or signal cable will be based on the linear feet of cable used.

632-5 Basis of Payment.

Prices and payments will be full compensation for all work specified in this Section. Payment will be made under: Item No. 632 - 7- Signal Cable FY 2023-24 Return to Table of Contents SECTION 633 COMMUNICATION CABLE

633-1 Description.

Furnish and install underground and aerial communication cable as shown in the Plans and Standard Plans .

633-2 Materials.

633-2.1 Fiber Optic Cable and Connections.

633-2.1 1 Single Mode Fiber Optic Cable: Provide all-dielectric, dry-filled,

loose-tube, dispersion -unshifted, single-mode fiber (SMF) with low water peak , gel free, and suitable for underground (i.e., in conduit) and aerial outside plant installation . All fiber op tic cable shall be splice -compatible with the Department’s existing dispersion -unshifted SMF and require no electronic equipment for dispersion compensation between new and existing fiber . Ensure that a ll components that comprise a single length of cable are continuous and of the same material. Furnish only commercial off -the-shelf materi als, equipment, and components.

633-2.1 1.1 Optical Fiber: Ensure that the optical fibers used in the cable

meet or exceed the Telecommunications Industry Association (TIA) and Electronic Industries Alliance (EIA) TIA/EIA -492-CAAB specification , the U.S. Department of Agriculture Rural Utilities Service (RUS) 7 CFR 1755.900, and International Telecommunication Union ITU- T G.652.D requirements. Use only optic al fibers meeting the additional requirements as follows: Geometry Cladding Diameter: 125µm, ±0.7 µm Core-to-Cladding Concentricity: 0.5 µm Cladding Noncircularity : 0.7% Mode Field Diameter: 1,550 nm; 10.4 µm, 0.5 µm Coating Diameter: 245 µm, 5 µm Colored Fiber Nominal Diameter: 25 0 µm 15 µm Optical Cabled Fiber Attenuation: 1,310 nm, 0.35 dB/km; 1,550 nm, 0.25 dB/km Point Discontinuity: 1,310 nm, 0.05 dB/km; 1,550 nm, 0.05 dB/km Cable Cutoff Wavelength ( ccf): 1,260 nm. Dispersion: 1,550 nm .0 ps/(nm •km) Macrobend Attenuation: Turns – 100; Outer diameter (OD) of the mandrel – 50 mm, 2 mm; 0.03 dB at 1,550 nm Polarization Mode Dispersion (PMDQ): <0.04 km ps Ensure that all fiber in the buffer tube is usable fiber that complies with attenuation requirements. Ensure that fibers do not adhere to each other. Ensure that the fiber is free of surface imperfections and inclusions. Ensure that a ll fiber optic core gl ass is from the same manufacturer . FY 2023-24 Return to Table of Contents

Source: Florida Standard Specifications for Road and Bridge Construction, 2024 Edition. Pages 851852 of 1,299.