SECTION 920 — Lighting Standards and Towers
920.1General Description
This section includes the requirements for the structural components of poles, towers, bases, anchor bolts, luminaires, and other attachments used for roadway, high mast, or other lighting. In particular, the section covers the following: • Steel lighting standards and towers • Aluminum lighting standards • Prestressed concrete standards • Support and lowering assemblies • Grounding 920.1.01 Related References
A.Standard Specifications
SECTION 105 — Control of Work
SECTION 501 — Steel Structures
SECTION 645 — Repair of Galvanized Coatings
SECTION 682 — Electrical Wire, Cable, and Conduit
SECTION 865 — Manufacture of Prestressed Concrete Bridge Members
B.Referenced Documents
ASTM AASHTO A 27/A 27M A 53/A 53M A 123/A 123M A 153/A 153M A 193/A 193M A 588/A 588M A 709/A 709M B 108 M 222/M 222M M 314 MIL-W-83420 AISI 304 AISI 1020 AASHTO Specifications for Structural Supports for Highway Signs, Luminaires, and Traffic Signals, with Interims (SLTS) ANSI C136.30, American National Standard for Roadway and Area Lighting Equipment-Pole Vibration 1770
SECTION 920 — Lighting Standards and Towers
920.1.01 Submittals Submit to the Engineer shop drawings and design calculations for each type of lighting standard, or tower to be used, for review and approval. Submission should be made electronically in a portable document format (pdf) and include an index. Format all drawings to fit 11 in. x 17 in. (279 mm x 432 mm) paper. Present calculations to fit 8.5 in. x 11 in. (216 mm x 297 mm) paper. The submission shall be prepared and stamped by the Design Engineer who shall be registered as a Professional Engineer in the State of Georgia. The Engineer will distribute submitted documents to the Bridge Engineer (SLTS@dot.ga.gov) for review.
920.2Materials
Design lighting assemblies consisting of standard, tower, bracket arms, lowering assembly, and luminaire support and assemblies according to AASHTO SLTS 920.2.01 Steel Lighting Standards and Towers
A.Requirements
1.Design
Poles shall be designed to the following wind speeds using a 1700 Mean Recurrence Interval (MRI) with Fatigue Category 1 for the listed counties: 150 mph: Bryan, Camden, Chatham, Effingham, Glynn, Liberty, McIntosh 140 mph: Brantley, Bulloch, Charlton, Evans, Long, Screven, Tattnall, Wayne 130 mph: Appling, Bacon, Brooks, Burke, Candler, Clay, Clinch, Decatur, Early, Echols, Emanuel, Grady, Jeff Davis, Jenkins, Lowndes, Miller, Pierce, Seminole, Thomas, Toombs, Ware 120 mph: For all counties not listed above
2.Include the following in the makeup of lighting standards and towers:
• A pole and bracket arms as required on the Contract. • A steel base welded to the other end complete with bolts for use as an anchor base pole, or attached to an approved breakaway device, such as slip base, aluminum transformer base, breakaway couplings, etc., when so specified.
3.Steel Structures
Use structural carbon or structural low alloy steel that meets the requirements of AASHTO SLTS. However, do not use ASTM A 588/A 588M steel.
4.Steel Pipe
When steel pipe is used, use steel pipe complying with ASTM A 53/A 53M Grade B or approved equal. No hydrostatic test is required.
B.Fabrication
1.Roadway Standards
Unless otherwise specified, do the following:
a.Make the shaft or appropriate shape continuously tapered with a base welded to the lower end.
b.The welds of the base flange to the shaft shall be configured such that the weld joints are loaded in shear,
never in tension.
c.Construct the standard of steel at least 11 gauge (3.1 mm) thick to the dimensions required for the
specified mounting height. Form the standard from one piece with one electrically full penetration welded longitudinal joint and no intermediate horizontal joints.
d.After forming and welding, cold-roll the shaft longitudinally under sufficient pressure to flatten the weld
and increase the physical characteristics of the metal in the shaft.
e.Ensure that the shaft has a reinforced handhole with a cover, except where a transformer base is
specified. 1771
SECTION 920 — Lighting Standards and Towers
1) Provide a 0.5 in. (13 mm) approved grounding connector in the shaft or base. 2) Equip the top of the shaft with a removable pole cap held securely in place. 3) Galvanize the shaft, base plate, bracket arm(s), handhole cover, and all elements of the pole with the hot-dipped method in ASTM A 123/A 123M.
f.Equip the top of the shaft with a removable pole cap held securely in place with set screws. Cap shall
match material and meet the same requirements as the pole.
2.Lighting Towers
a.Make the shaft to meet the requirements of the roadway standard (Subsection 920.2.1.B.1).
b.Construct the standard to continuously taper 0.14 to 0.40 in./ft. (12 to 33 mm/m).
c.Ensure that the standard has the necessary dimensions and metal quality to meet the requirements for
the specified mounting height.
d.The shaft may be formed in sections with each section having no more than two longitudinal welded
seams. Sections shall be a minimum of 30 feet in length.
e.Use intermediate horizontal welds only at section joints.
f.Make telescoped joints overlap at least 1-1/2 pole diameters, measured at the minimum diameter of the
inner telescoping section.
g.Have field welding performed only by an approved certified welder who represents the manufacturer.
Ensure the welding follows the requirements of Section 501.
h.Repair any damage to galvanized coating according to Section 645.
i.Match-mark all sections of the shaft so that the tapered sections are assembled properly.
3.Post Top or Other Standards for Special Installation
a.Make the post top and other standards meet the requirements for roadway standards (Subsection
920.2.01.B.1).
b.Make the top diameter of the shaft 2 in. (50 mm) or include a 2 in. (50 mm) tenon, unless otherwise
specified, to insert the shaft or tenon into the luminaire.
4.Anchor Base
Do the following, unless otherwise specified:
a.Secure a steel base to the lower end of the shaft with two continuous electric welds. Ensure that the base
develops the full strength of the adjacent shaft section to resist bending.
b.Provide removable cast or pressed steel covers with each base. Appropriately attach each cover to
the base.
5.Steel Bracket Arms
Do the following, unless otherwise specified:
a.Use the design dimensions from the Contract.
b.Bracket arms shall be of the same material and meet the same requirements as the pole shaft.
c.Ensure that the installed bracket connects securely with the shaft and has a smooth wiring raceway.
d.Use stainless steel bolts and nuts that meet the requirements of ASTM A 193/A 193M, Type B8C or AISI
304 to attach the bracket arm assembly.
6.Transformer Bases
Do the following, unless otherwise specified:
a.Use the dimensions on the Contract to build the bases.
1) Make top and bottom plates that meet the requirements of ASTM A 709/A 709M, Grade 36 (250), and are fabricated to receive the shaft, anchor bolts, and the foundation bolts. 2) Make the side panels meet the requirements of AISI 1020. 3) Create a base thick enough for the height of the standard.
b.Fit the base with a handhole and cover that can be securely fastened.
b.Use the size indicated on the Contract or as required by the manufacturer’s shop drawings.
c.Use anchor bolts, nuts, and washers that meet the requirements of AASHTO M 314, Grade 55(370).
Supplementary requirementS 1 of AASHTO M 314 also applies. NOTE: Do not use Grade 105 (724).
d.Install anchor bolts with a leveling nut and a flat washer between the leveling nut and the base plate.
1) Use a template to install the bolts. 2) Place a flat washer on top of the base plate. 3) Use a lock washer on top of the flat washer and secure the nut. 4) Fully grout the space between the shoe base and the top of the footing with non-shrink grout.
e.Galvanize threaded ends of anchor bolts, hexagonal nuts, flat washers, and lock washers according to
ASTM A 153/A 153M and Contract details.
8.Finish
Unless otherwise specified, galvanize all steel lighting standards and towers, including pole, base, transformer base, and bracket arm assembly according to ASTM A 123/A 123M.
C.Acceptance
1.The Engineer reserves the right to inspect and run tests as necessary to ensure compliance with these
specifications and to reject items that fail testing.
2.The Engineer will accept the steel lighting standards and towers based on:
• The results of physical and chemical tests made by the Department. • The manufacturer’s certification showing physical and chemical properties of the metal prior to forming.
D.Materials Warranty
General Provisions 101 through 150. 920.2.02 Aluminum Lighting Standards
A.Requirements
1.Design
Poles shall be designed to the following wind speeds using a 1700 Mean Recurrence Interval (MRI) with Fatigue Category 1 for the listed counties: 150 mph: Bryan, Camden, Chatham, Effingham, Glynn, Liberty, McIntosh 140 mph: Brantley, Bulloch, Charlton, Evans, Long, Screven, Tattnall, Wayne 130 mph: Appling, Bacon, Brooks, Burke, Candler, Clay, Clinch, Decatur, Early, Echols, Emanuel, Grady, Jeff Davis, Jenkins, Lowndes, Miller, Pierce, Seminole, Thomas, Toombs, Ware 120 mph: For all counties not listed above
2.Include the following in making aluminum lighting standards:
a.A pole and bracket arm(s) as required on the Contract.
b.An aluminum base welded or bonded to the lower end, complete with bolts for use as an anchor base
pole or attached to an approved breakaway device such as an aluminum transformer base, breakaway couplings, etc., when so specified. 1773
SECTION 920 — Lighting Standards and Towers
B.Fabrication
Use aluminum materials that meet the requirements of AASHTO SLTS
3.Roadway Standards
a.Make the shaft with a continuous taper formed from an extruded blank (preferably 6063-T6). Weld a base
plate to the lower end.
b.Give the shaft a reinforced handhole with a cover, except when a transformer base is specified.
c.Provide a 0.5 in. (13 mm) approved grounding connection in the shaft or base.
d.Equip the top of the shaft with a removable pole cap held securely in place with set screws. Cap shall
match material and meet the same requirements as the pole.
4.For Post Top or Other Standards for Special Installation,
Do the following, unless otherwise specified:
a.Build the standard to meet the requirements for roadway standards (Subsection 920.2.01.B.1).
b.Make the top diameter of the shaft 3 in. (75 mm) or include a 3 in. (75 mm) tenon to insert the shaft or
tenon into the luminaire.
5.Anchor Base
Do the following, unless otherwise specified:
a.Secure the one-piece aluminum base to the lower end of the shaft by using two continuous welds.
b.Ensure that the base develops the full strength of the adjacent shaft section to resist bending.
c.When the Contract call for a frangible or breakaway base, attach the base to an approved breakaway
device with an approved number and type of bolts, or use a base that is an approved breakaway type.
d.Provide removable cast or pressed aluminum covers with each base. Appropriately attach each cover to
the base.
6.Aluminum Bracket Arms
a.Use the Contract design and dimensions.
b.Ensure that the installed bracket arm connects securely with the shaft and has a smooth wiring raceway.
c.Use stainless steel bolts and nuts that meet the requirements of ASTM A 193/A 193M, Type B8C or
AISI 304, to attach the bracket arm assembly.
7.Transformer Bases
a.Form the base of cast aluminum that meets the requirements of ASTM B 108, Alloy A03560, T6 to
dimensions on the Contract.
b.Make the top so it can receive the anchor base bolts and the bottom so it can receive the anchor bolts.
8.Anchor Bolts
Use bolts as described in Subsection 920.2.01.B.7.
9.Finish all aluminum lighting standards, including pole, base, transformer base, and bracket arm assembly in a