SECTION 918 – ELECTRICAL MATERIALS
918.01 Conduit and Fittings
Ensure that exposed conduit and fittings on sign structures are aluminum conforming to UL standards for rigid metallic conduit. Use fittings and accessories for aluminum conduit that are made of aluminum or stainless steel. Ensure that conduit and fittings used as a raceway for the installation of wires and cables conform to the following:
918.02 Cable and Wire
The manufacturer shall provide to the RE and the Contractor all splicing and terminating information necessary for proper installation of the cables and wires. Ensure that conductors are made of stranded copper and conform to the standard rule s of the American Institute of Electrical Engineers and of the National Board of Fire Underwriters. Do not use conductors that are smaller than No. 14 AWG or Brown and Sharp Gage. Ensure that conductors are soft annealed copper wire according to ASTM B 3, Class B for tin -coated conductors or are bare copper conductors according to ASTM B 8, Class B. Submit a certificate of compliance, as specified in 106.07, for all materials, components, and assemblies.
918.02.01 Loop Detector Lead
Use only one type of loop detector lead on the Project.
918.02.02 Loop Wire
Ensure that the loop wire is thermoplastic single conductor wire with a 1/4 inch PVC tube or 1/4 inch, HDPE tube extruded over the loop detector wire, is manufactured in conformance with ICEA Publication No. S -61-402/NEMA Publication No. WC5, and conforms to the following:
918.02.03 Multiple Lighting and Service Wire
Use wire conforming to current ICEA -NEMA Standards Publi cation for Cross -linked-thermosetting-polyethylene- insulated Wire and Cable for the Tran smission and Distribution of Electrical Energy, ICEA Publication No. S-66-524/NEMA Publication No. WC 7 and UL Type RHW-USE. Ensure that the insulation is a heat -resistant, moisture-resistant submarine compound conforming to ICEA Publication No. S-66-524/NEMA Publication No. WC 7, except for the thickness of insulation. For all conductors, use insulation that is required for 600 volt rated circuit voltage according to Table 3-1 for cross-linked-thermosetting-polyethylene-insulated power cables, Column A of ICEA Publication No. S-66-524/NEMA Publication No. WC 7.
918.02.04 Traffic Signal Cable
Use only one type of traffic signal cable on the Project.
918.03 Bonding and Grounding Materials
For rigid metallic conduit with a diameter of 1 inch or more, use bushings that are hot-dip galvanized or electro-galvanized malleable iron, with a bakelite, nylon, or some other type of heat-resistant plastic molded and locked into the bushing. Use an aluminum, bronze, copper, or other corrosion-resistant metal lug. Ensure that the set screws, lug mounting, and binding screws are stainless steel. The Contractor may use threadless bushings at specific locations where the conduit is not threaded. Fabricate insulating bushings for rigid metallic conduit with a diameter of less than 1 inch of molded high-impact thermoset plastic with a high dielectric and mechanical strength. Bond the conduit with bonding lock nuts. Do not use bushings made of materials that support combustion. Use ground wire that is bare or insulated with a conductor that is 7 strand, soft-drawn copper conforming to ASTM B 8, Class B. Ensure that bare conductors are tinned. For insulated conductors, cover the conductor with an insulation that meets or exceeds the requirements of UL Type THW. Use ground rods that are 5/8 inch in diameter and 12 feet long, composed of a steel core with copper covering. Thoroughly weld the 2 metals so that an interlocking crystalline union is secur ed between the 2 metals. Ensure that the minimum thickness of the copper on the cylindrical portion of the rod averages at least 0.010 inch. Submit a certificate of compliance, as specified in 106.07, for all materials, components, and assemblies.
918.04 Cable Connectors
Use cable connectors that are fused for on line wires and nonfused on neutral wires. Ensure that the connec tors are a waterproof inline type connector and are composed of a line side and a load side housing, each made of water -resistant synthetic rubber. In each housing, include a section to form a watertight seal around the cable, an interior arrangement to receive and retain the copper fuse contacts, and a watertight seal section at the point of disconnection. Use contacts that are spring loaded, designed for a maximum current of 30 amperes at 600 volts and have a 90 percent minimum conductivity. Ensure that the contacts are suitable for gripping a cartridge -type midget fuse. Ensure that the fuse is 13/32 inch in diameter and 1 1/2 inches in length and is rated at 5 amperes and that the contacts are fully annealed and compressed onto the cable. Determine the size of each housing based on the cable diameter. Permanently mark each side of the housing as either load side or line side. Submit manufacturer’s certification for all materials, components, and assemblies as specified in 106.07.
918.05 Resin Splicing Kits
918.06 Electrical Tape
918.07 Cable Racks
Use cable racks that are molded polycarbonate and have a dielectric strength of less than 2 microamps at 100,000 volts. Ensure that the polycarbonate used in the construction of the rack is fire retardant with an SE -1 rating. Use a cable rack that is 3 inches wide and 3 feet long in ground-installed junction boxes or that is 3 inches wide and 1 foot long in structures. Ensure that the cable rack contains 3 saddle arms with a capacity of 2 inches. As an alternative, the Contractor may use steel cable racks that consist of a steel channel, welded steel supports, a clip, and porcelain insulators for each support. Hot -dip galvanize all steel components. Use a cab le rack that is approximately 2 feet long with 3 supports in ground installed boxes an d 7 inches long with 1 support in junction boxes located on structures. Space support holes on the channel approximately 1 1/2 inches on center. Ensure that the cable supports are designed with an interlocking feature at the rear of the support to prevent tilting and that the installed cable supports extend approximately 4 inches from the rack. Construct the porcelain insulator required on each support with a hook bottom groove to prevent slipping. Submit a certificate of compliance, as specified in 106.07, for all materials, components, and assemblies.
918.08 Cast Boxes and Fittings
Use cast boxes with suitable covers of lik e material held in place with stainless steel fasteners and sealed with a weatherproof neoprene gasket. Provide mounting lugs with cast boxes. Ensure that all mounting hardware is stainless steel. For cast iron boxes, conform to the requirements specified in 909.03. Hot-dip galvanize cast iron boxes and covers. Use aluminum boxes and covers that are either sand cast conforming to ASTM B 26, Alloy 356.0 -F or 356.0-T6, or die cast conforming to ASTM B 108, Alloy 356.0-T6. Use junction boxes for underdeck lighting that are cast iron of approved design, suited and adapted to the specific location and the number of conduit, nipples, and other required details. Use flush -type boxes for installation in a structure and surface-mounted-type boxes in all surface applications. Ensure that the cover has a neoprene gasket and is secured with stainless steel screws. If required, equip the box with busses to provide at least 5 full threads or a UL-approved watertight rigid conduit hub at each entry point of the conduit. Use cast aluminum for pull boxes and pull fittings exposed on sign structures. Use boxes that are of approved design, suited and adapted to the specific location and the number and arrangement of conduit, and other details for the installation. Ensure that boxes have external lugs for mounting and internal mounting buttons for mounting equipment. Submit a certificate of compliance, as specified in 106.07, for all materials, components, and assemblies.
918.09 Cabinets
For cabinets, use aluminum alloy conforming to ASTM B 209, Alloy 6061-T6. Label the door of all meter and control equipment cabinets, other than traffic signal cabinets, with a permanent reflective metallic sign indicating the voltage and the word DANGER. Apply the sign on a 0.040 inch minimum thickness aluminum alloy sheet. Use lettering that is approximately 1 1/2 inches high and is red on a white background. Install the sign with 4 stainless steel vandal proof screws. Seal a print of the system field w iring in plastic and attach it to the inside of the door of each meter cabinet, control equipment, and controller cabinet. Submit a certificate of compliance, as specified in 106.07, for all materials, components, and assemblies.
918.10 Panel Boards and Circuit Breakers
918.11 Photoelectric Controls
Use photoelectric controls that are rated for the control or lighting circuit voltage indicated. Provide mounting hardware to allow the u nit to be installed in whatever type of location is shown. Ensure that the mounting conforms to the EEI-NEMA Standards for physical and electrical interchangeability of light sensitive control devices. Submit a certificate of compliance, as specified in 106.07, for all materials, components, and assemblies.
918.12 Pedestals, Poles, Transformer Bases, and Mast Bracket Arms
Fabricate pedestals, poles, transformer bases, and mast brac ket arms for traffic signal, highway lighting, and camera standards with materials according to the appropriate ASTM standard and the AASHTO Sta ndard Specifications for Structural Supports for Highway Signs, Luminaires and Traffic Signals. Weld and fabricate steel members according to AWS D1.1, Structural Welding code. For aluminum members, weld and fabricate according to ANSI/AWS D1.2 Structural Welding Code - Aluminum. Ensure that welding is performed by welders who are qualified according to ANSI/AWS D1.1 or ANSI/AWS D1.2, as appropriate. Submit copies of the welder qualifications upon request. Perform at least the minimum specified number of quality control inspections according to the applicable ANSI/AASHTO/AWS specification and any other tests and inspections necessary to control the quality of the work. Ensure that aluminum poles, lighting, bracket arms, and traffic signal mast arms have a rotary, sand-polish finish giving a nonreflecting outer surface. Ensure that the external surfaces of transformer bases and shoe bases have a satin-type finish. Hot-dip galvanize steel poles and steel traffic signal arms according to ASTM A 123. If wire or cable passes through a hole or runs along a surface at any point, through or on the complete assembly, ensure that the holes and surfaces are deburred and void of any sharp edges or protuberances that may damage the wire or cable. Install rubber grommets in the entrance hole to the shaft and mast arms where mid-mounted traffic signals are installed. When installing aluminum traffic signal standards, use stainless steel hardware, bolts, nuts, and washers conforming to
908.04 For steel traffic signal standards, use galvanized hardware, bolts, nuts, and washers conforming to 908.01.
The manufacturer shall test standards and mast bracke t arms to ensure compliance with specified material and strength requirements. Perform testing that also ensures that the items have been manufactured in conformance with the AASHTO Standard Specifications for Structural Supports for Highway Signs, Luminaires and Traffic Signals. Ensure aluminum poles and mast bracket arms are factory wrapped to protect them during shipment. Submit a certificate of compliance, as specified in 106.07, for all materials, components, and assemblies. Submit 5 copies of the certification stipulating that the items conform to the strength and material requirements.
918.13 Tower Poles
Fabricate according to AASHTO Standard Specifications for Structural Supports for Highway Signs, Luminaires, and Traffic Signals.
918.14 Lamps
Submit a certificate of compliance, as specified in 106.07, for all materials, components, and assemblies.