B
HomeLibrariesCopilotSearchProjectsBookmarks
FeedbackHelp Desk
Libraries
Building Codes
Code LibraryIBC — BuildingIRC — ResidentialIFC — FireIPC — PlumbingIMC — MechanicalIFGC — Fuel GasIECC — EnergyNEC — ElectricalModel Codes
Specifications
CSI SpecificationsDOT SpecsTransit SpecsUSACE
Standards
TransportationRailroadFire SafetyAccessibilityStructural
Tools & References
DiagramsAssembliesProductsCalculatorsChecklistsPermits
PricingLog in
General Provisions (00100-00999)

503Prestressed Concrete and Precast Members

NV · 2014 Standard SpecificationsBook pages 253274View official source ↗

247 SECTION 503 DESCRIPTION

503.01.01 General. This work consists of furnishing and installing prestressing and post -tensioning systems

and other items necessary for the particular prestressing system used, including but not limited to ducts, anchorage assemblies , and local zone reinforcement in precast concrete members or cast -in-place concrete members. This work also consists of furnishing and placing either precast reinforced concrete members or precast prestressed concrete members as indicated on the plans. Where reference is made herein to the “pretensioning method,” the prestressing steel strands or bars are assumed to be tensioned in a casting bed prior to placing concrete in the forms. Where referenc e is made herein to the “post -tensioning method,” the prestressing steel strands or bars are assumed to be tensioned in ducts after the concrete has been placed and has obtained the specified strength. Furnish all components of a post -tensioning system fr om a single supplier. Prestressing steel can be obtained from any supplier as long as all prestressing steel in a tendon is from one supplier. Furnish and place complete precast prestressed concrete and precast concrete members including all concrete, pre stressing steel and items appurtenant to the pretensioning method used, reinforcing steel , and incidental materials in connection therewith. Install prestressing steel, which may be strands or bars, in the concrete. Stress to a predetermined load. Where post-tensioning is used, grout ducts to fill all voids and install protection at end anchorages.

503.01.02 P recast Plant Certification. Produce all precast prestressed concrete members in a fabrication

plant certified by the Precast/Prestressed Concrete Institute ( PCI), unless otherwise approved in writing. The fabrication plant shall have a B3 or B4 Certification as required for the members being produced, unless otherwise approved in writing. Portable pretensioning beds will not be allowed. Submit a co py of the fabrication plant’s PCI Certification and most recent PCI plant audit report before or along with the first submittal of shop drawings.

503.01.03 Personnel Certification s. Provide project personnel meeting the requirements of this Subsection.

For p recast concrete plant f acility Quality Control (QC) , provide an on -site production manager, an on -site Facility Manager for QC, a plant engineer, and on -site QC inspectors/technicians to provide complete QC inspections and testing. Ensure the Facility Manager for QC has at least five years of related experience and a current Precast/Prestressed Institute (PCI) QC personnel Level III certification. Ensure that the QC inspector/technician has current PCI QC Technician/Inspector Level II certification. Submit copies of personnel certifications and qualifications for approval with the precast member shop drawings. Perform all post -tensioning field operations under the direct supervision of a technician certified as a Level 2 Bonded PT Field Specialist thro ugh the Post -Tensioning Institute (PTI). Provide the name of the technician and furnish proof of certification with the prestressing working drawings. Provide an individual certified as either a Certified Grouting Technician through the American Segmental Bridge Institute (ASBI) or a PTI Level 2 Bonded PT Field Specialist to supervise, inspect, and document the entire grouting operation. Provide close observation and control of all grouting operations by the certified technician. Have the certified technic ian on -site at any time when grouting is taking place. Provide the name of the grouting technician and furnish proof of certification with the Grouting Operations Plan. MATERIALS

503.02.01 General. Material shall conform to the following Sections and Sub section:

Portland Cement Concrete ................................ ................................ ................................ ................................ ..................... Section 501 Concrete Structures ................................ ................................ ................................ ................................ ............................... Section 502 Reinforcing Steel ................................ ................................ ................................ ................................ ................................ .... Section 505 Prestressing Steel ................................ ................................ ................................ ................................ ................... Subsection 713.03.0 3 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 248 503.02.02 Tendon Grout. Provide a commercial, prepackaged, tendon grout for grouting post-tensioning ducts. Deliver grout in moisture proof plastic lined or coated bags. Provide bags with manufacturer’s labels showing brand name, intended application, date of manufacture, expiration date, lot number, and mixing and pumping instructions. Use grout within six months of the manufacture date. Tendon grout shall conform to the requirements for a Class C grout, as defined by the Post -Tensioning Institute (PTI) Specification for Grouting of Post -Tensioned Structures and shall meet the vertical rise requirements for the project tendons. Tendon grout shall not contain aluminum powder, gas generating components that produce hydrogen gas, carbon dioxide, or oxygen, expansive admixtures, or admixtures containing chloride. Submit certified mill test reports for the tendon grout upon request. Tendon grouts will be approved based on prequalification testing. Perform testing by an independent certified testing facility. Test tendon grout at normal laboratory temperatures of 18 to 25 °C (65 to 78 °F) unl ess otherwise specified by the referenced test method. Re-qualify tendon grout for any changes made to either the source or type of all ingredients of the tendon grout. Testing conducted for other state transportation agencies may be accepted as prequalif ication testing provided the test requirements herein are satisfied. For findings and evaluations of other state Departments of Transportation see the AASHTO Prod uct Evaluation Listing Service. Submit evidence that the grout manufacturer has an on -going q uality control program for the tendon grout it produces. Evidence may include, but is not limited to, quality control data sheets, or recent test results for the proposed tendon grout. Test results shall be dated within one year of the intended grouting of the tendons. Tendon grout shall conform to the following: TEST TEST METHOD REQUIREMENT Strength ASTM C942 21 MPa (3,000 psi) minimum @ 7 days 35 MPa (5,000 psi) minimum @ 28 days Initial Set ASTM C953 3 hr minimum , 12 hr m aximum Permeability ASTM C1202 as m odified by Section 4.4.3 of PTI* Less than 2,500 coulombs after 6 hours using 30 volts on 28 day grout Volume Change ASTM C1090 Vertical height change between 0.0% and + 0.1% @ 24 hours Vertical height change of + 0.2% maximum @ 28 days Fluidity For thixotropic grouts, ASTM C939 as modified by Section 4.4.5.2 of PTI* For non -thixotropic grouts, ASTM C939 After either test above, let sample stand for 30 minutes without further agitation , remix for 30 seconds , then test immediately Efflux time between 5 and 30 seconds for a 1 liter discharge immediately after mixing Efflux time between 11 and 30 seconds immediately after mixing For thixotropic grout, e fflux time of 30 seconds maximum for a 1 liter discharge For non -thixotropic grout, e fflux time of 30 seconds maximum Wick Bleed Wick Induced Bleed ASTM C940 as modified by Section C4.4.6.1 of PTI* 0.0% maximum at 3 hours @ 20 °C (70 °F) Pressure Bleed Schupack Pressure Bleed (Gelman Pressure) in accordance with Appendix C of PTI* 4% max at 20 psi with vertical rise between 0 to 0.6 m (0 to 2 ft) 2% max at 30 psi with vertical rise between 0.6 to 1.8 m (2 to 6 ft) 0% max at 50 psi with vertical rise between 1.8 to 30.5 m (6 to 100 ft) Chloride Ions ASTM C1152 Less than 0.08% by mass of cementitious material Fine Aggregate ASTM C136 99% passing the 300 µm (No. 50) sieve * PTI Specifications for Grouting of Post -Tensioned Structures. * Use ASTM C117 procedure modified to use a No. 50 sieve. Determine the percent passing the No. 50 sieve after washing the sieve. Water for mixing grout shall have less than 500 ppm of chloride ions and no organic materials. Water with a pH less than 4.5 or greater than 8.5 and a resistivity less than 500 ohm•cm will be tested according to AASHTO T26. Any indication of unsoundness, marked change in time of setting, or a reduction of more than 10% in strength from results obtained with grout mixtures containing the water of satisfactory quality shall be sufficient cause for rejection of the water under tests.

503.02.03 N onshrink Grout . Provide grout that is a non -metallic, non -metal oxidizing, and non -gas-liberating

flowable fluid containing natural aggregate, Portland cement and additives and requiring only the a ddition of water. Provide a minimum of 385 kg of cement per cubic meter (650 lb of cement per cubic yard) nonshrink grout. Provide premeasured and prepackaged grout by the manufacturer, that is suitable for baseplate and foundation grouting. Show no aggreg ate segregation or settlement at fluid consistency at specified times or temperatures. Grout shall pass through a flow cone with continuous flow one hour after mixing. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 249 Provide nonshrink grout conforming to the requirements of ASTM C1107, and the following additional requirements: PROPERTY TEST METHOD REQUIREMENT Shrinkage ASTM C827 0.0% Expansion ASTM C827 0.0% minimum, 4.0% maximum Fluid Consistency USACE CRD -C611/ASTM C939 20-30 seconds at 4 -38 °C (40 -100 °F) 1-day Compressive Strength ASTM C109 24.1 MPa (3500 psi) minimum 3-day Compressive Strength ASTM C109 31.0 MPa (4500 psi) minimum 28-day Compressive Strength ASTM C109 51.7 MPa (7500 psi) minimum Chloride Content ASTM C1152 0.24 kg/m3 (0.40 lb/yd3) maximum Grout shall have a minimum initial set time of 4 hours and minimum final set time of 6 hours at 21 °C (70 °F). Prior to use , store materials in suitable moisture resistant containers in a cool and dry environment. Label containers clearly with manufacturer’s recommendations, limitations and cautions. Do not use broken or open packages. Provide grout with low levels of chlorides as specified above and free from other corrosion -causing chemicals. Design nonshrink grout for an air content of 4 to 6 percent. Mix, place , and cure grout in accordance with the manufacturer’s requirements, these specifications , and as approved. Provid e mix water conforming to the requirements of Subsection 503.02.02. Use cold water in hot weather conditions to maintain the mixed grout temperature from 7 to 32 °C (45 to 90 °F). Use a quantity of water to be b lended with the dry component within the limits recommended by the manufacturer. Use the least amount of water required to produce a flowable or fluid batter as required for the application, and as approved. Submit for approval, specific printed manufactu rer’s product data including recommended preparation , placement and curing methods for each nonshrink grout applicat ion. Nonshrink properties shall not be based on gas or gypsum expansion. CONSTRUCTION

503.03.01 General. Perform prestressing by either (a) pretensioning methods, or (b) post -tensioning methods.

If the plans show details for only one particular method, the use of the alternate method will be allowed only upon approval. If use of the alternate method is appro ved, submit complete details and design calculations for the alternate and for any other necessary modifications to the member for approval . Details and design calculations for approved alternate methods shall be stamped by a n engineer who is r egistered as a Civil or Structural Engineer in the State of Nevada. Do not commence work until details and design calculations are approved in writing. Submit working drawings according to Subsection 105.02 , giving complete details and substantiating calculations o f the method, materials, and equipment proposed for use in the construction, prestressing, and/or erection operations. Outline in such details the method of prestressing, and include the arrangement of the prestressing steel and mild steel reinforcement in the member (including grillage reinforcing designated in the Standard Plans) , any additions or rearrangement of reinforcing steel, any revision in concrete dimensions from that shown on the plans, and working stresses. Submit complete, independent working drawings for each structure, working drawings shall not refer to drawings submitted for other structures. For the pretensioning method, show on the shop drawings a sequence for cutting or releasing the prestressing steel. Include details and calculations for lifting embedments and lifting locations; methods of handling, storage, and transport . Provide a sequence of casting indicating when forms will be stripped, strands cut, and beams removed from the bed. Indicate the decision process for each action in the casting sequence. Do not start fabrication of any precast prestressed concrete member until shop drawings have been approved, written notice of the start of fabrication has been provided, and a pre -fabrication meeting has been completed . For the post -tensioning method also include on the working drawings the specifications and details of anchoring devices and distribution plates or assemblies, calculated stresses in the anchorages and distribution plates, type of post-tensioning enclosures, sequence of stressing prestressing steel, pressure grouting materials and equipment, including all inlets, outlets, drains, permanent grout caps, direction of grouting and a method of detensioning the prestressing steel should it become necessary to do so before grou ting takes place. The working drawings shall 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 250 also include results of post -tensioning anchorage system prequalification testing according to Subsection 503.03.04 and a grouting operations plan according to Subsection 503.03.07 . Do not use or install prestr essing steel in the work until the prestressing steel has been sampled, tested and approved for use. When requested, s ubmit drawings of forms proposed for the precast concrete members according to Subsection 105.02 . Show in such drawings the complete details of the type of forms proposed for providing any indicated openings and proposed method of supporting and anchoring such forms. If electing to prestress precast concrete members and a prestressed option is not shown on the plans, design the members as precast prestressed members and the design calculations and drawings according to Subsection

105.02 Design calculations and drawings shall be stamped by an engineer who is registered as a Civil or Structural

Engineer in the State of Nevada. Do not com mence work until details and design calculations are approved in writing. Give notice in writing 14 days in advance of performing prestressing operations.

503.03.02 Protection of Materials. Store and protect all prestressing materials in a weatherproof e nclosure

until time of use. Protect all prestressing steel against physical damage, rust, and other results of corrosion at all times from manufacture to grouting or encasing in concrete. Prestressing steel that has sustained physical damage will be reject ed. The development of visible rust or other results of corrosi on will be cause for rejection. Package prestressing steel in containers or shipping forms for the protection of the steel against physical damage and corrosion during shipping and storage. Pl ace a corrosion inhibitor which prevents rust or other results of corrosion in the package or form, or incorporate in a corrosion inhibitor carrier type packaging material, or when permitted , apply directly to the steel. The corrosion inhibitor shall have no deleterious effect on the steel or concrete or bond strength of steel to concrete. Immediately replace or restore packaging or forms damaged from any cause to original condition. Clearly mark the shipping package or form with a statement that the packa ge contains high -strength prestressing steel, the care to be used in handling, and the type, kind and amount of corrosion inhibitor used, including the date when placed, safety orders and instruction for use. Do not weld reinforcing or prestressing steel. Any weldments to reinforcing or prestressing steel shall be subject to rejection. Replace any reinforcing or prestressing steel rejected by the Engineer. Make no welds or grounds for welding equipment on the forms or on the steel in the member after the prestressing steel has been installed. If prestressing steel for pretensioning is placed in the stressing bed and exposed to the elements for more than 36 hours before encasement in concrete, take acceptable m easures to protect said steel from contamination or corrosion. If prestressing steel for post -tensioning is installed in members prior to the placement of concrete, such as strand in flat ducts , continuously protect prestressing steel against rust or othe r corrosion, until grouted, by means of a corrosion inhibitor placed in the ducts or applied to the steel in the duct . Provide a vapor phase corrosion inhibitor formulated for use in protecting prestressing steel in ungrouted tendons that does not contain silicates, phosphates, nitrates or heavy metals, that provides up to 24 months of continuous protection using a monomolecular inhibiting layer and which does not affect the physical properties of the concrete or grout. Submit brand name, MSDS, product instructions and evidence of past successful use on other projects for approval. When prestressing steel for post -tensioning is installed in the ducts after completion of concrete curing, and if stressing and grouting are completed within 10 days after the pr otective packaging has been opened, rust which may form during said 10 days will not be cause for rejection of the steel. The use of a corrosion inhibitor in the duct following installation of the prestressing steel within the above 10 days, will not be re quired except when requested because of adverse weather conditions. Prestressing steel installed as above but not grouted within 10 days shall be subject to all the requirements in this Subsection pertaining to corrosion protection and rejection due to rust. When steam curing is used, do not install prestressing steel for post -tensioning until the steam curing is completed. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 251 Ship ducts for prestressing steel in bundles which are covered during shipping and storage. Protect ducts against crushing, excessive bending, dirt contamination and corrosive elements during transportation, storage and handling. Do not remove covering supplied with the ducts until the ducts are incorporated into the bridge component. Store ducts on a raised platform and completely cove red to prevent contamination. If necessary, wash ducts before use to remove contamination. Use water for flushing ducts containing either quick lime (calcium oxide) or slaked lime (calcium hydroxide) in the amount of 12 g/L (0.10 lb/gal). Use oil free compressed air to blow out ducts. Store tendon grout in waterproof enclosures maintaining temperatures within the range recommended by the manufacturer . Do not open packaging until time of mixing. Bags or bulk containers that are damaged or previously opened will be rejected.

503.03.03 Forms. Do not deposit concrete in the forms until after inspection of reinforcement, anchorages,

ducts, inlet and outlet pipes, embedments , and/or prestressing steel. Deposit concrete in forms that have a minimum temperatu re of 5 °C (41 °F) and are within 17 °C (30 °F) of the temperature of the concrete at the time of placement. Vibrate the concrete internally or externally, or both, as required to consolidate the concrete. Vibrate with care and in such a manner to not dis place reinforcement, ducts, anchorages, embedments and/or prestressing steel. Construct forms for interior cells or holes in the members of a material that will resist breakage or deformation during the placing of concrete and will not materially increase the mass of the member. “Lost forms,” left in place in interior cells, shall not exceed 575 N/m2 (12 lb/ft2) of supported deck area. Provide access through forms to locations where operations for duct pressure testing and grouting operations will be performed. Side forms for prestressed members may be removed the day after placing concrete therein, provided satisfactory arrangements are made for curing and protecting the concrete. Remove all side forms before releasing pretensioned prestressing steel and before tensioning post -tensioned prestressing steel. Remove side forms of precast pretensioned members after the concrete has reached the compressive strength shown on the plans or a minimum of 21 MPa (3,000 psi) . Remove side forms prior to cooling wh en accelerated curing methods are used. For precast members, provide holes for anchor bars, and for diaphragm dowels which pass through the member, openings for connection rods, recesses for grout, and any other holes and recesses as necessary in the memb ers according to the details shown on the plans or the approved working drawings . Where diaphragm dowels do not pass through the member, the dowels may be anchored in the member by embedment in the concrete or by means of an approved threaded insert. Lifting anchors may be installed in precast members provided any portion of the anchor extending beyond the precast member is removed after the member is placed.

503.03.04 Anchorages and Distribution. Secure all post -tensioned prestressing steel at the ends b y means

of approved permanent type anchoring devices. Post-tensioning anchorage systems will be approved based on prequalification testing. Conduct prequalification testing by an independent testing laboratory which certifies that the complete tendon anch orage system meets the requirements of Subsection 10.3.2.3 of the AASHTO LRFD Bridge Construction Specifications . Testing conducted for other state transportation agencies may be accepted as prequalification testing. Submit documentation of anchorage system prequalification with the working drawings for approval. Include the following information in the submittal:

1.Dimensions of the test specimen.
2.Drawings and dimensions of the anchorage device, including all confining reinforcing steel.
3.Amount and arrangement of supplementary skin reinforcement.
4.Type and yield strength of reinforcing steel.
5.Type and compressive strength at time of testing of concrete .
6.Type of testing procedure and all recorded measurements. Ensure all anchorage devices for post -tensioning hold the prestressing steel, when tested in an unbonded state, at a load producing a stress of not less than 9 6% of the actual ultimate tensile strength of the prestressing steel without exceeding the antic ipated set. 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 252 Design anchorages so that the average concrete bearing stress is in compliance with the AASHTO LRFD Bridge Design Specifications. Use materials and workmanship conforming to Section 506. Approved anchorage devices are designed and provided by the anchorage manufacturer and typically include a trumpet, anchor plate, anchor head with seating wedges, and confining reinforcement located directly behind the anchor head (referred to as local zone reinforcement). Provide local zone reinforcement at al l anchorages according to the approved prequalification testing drawings. Also provide supplemental grillage reinforcing as indicated in the contract documents. Provide wedge plates with centering lugs or shoulders to facilitate alignment with the bearing plate. Cast anchorages with grout outlets suitable for inspection from either the top or front of the anchorage. The grout outlet will serve a dual function of grout outlet and post -grouting inspection access. The geometry of the grout outlets must facil itate being drilled using a 9.5 mm (3/8 in.) diameter straight bit to facilitate endoscope inspection directly behind the anchor plate. Anchorages may be fabricated to facilitate both inspection locations or may be two separate anchorages of the same type each providing singular inspection entry locations. Trumpets associated with anchorages shall be made of either ferrous metal or polypropylene plastic material. The thickness of the trumpet at the transition location (choke point) shall not be less than t he thickness of the duct. Alternately, the trumpet material may be polyolefin containing antioxidants with a minimum Oxidation Induction Time (OIT) according to ASTM D3895 of not less than 20 minutes. Perform OIT test on samples taken from the finished pro duct. Test the remolded finished polyolefin material for stress crack resistance using ASTM F2136 at an applied stress of 2.4 MPa (348 psi) resulting in a minimum failure time of 3 hours. Epoxy coat any additional reinforcing at anchorages, including adde d spirals or grillages, located within 300 mm (12 in.) of the driving surface where the contract documents call for epoxy coating of the deck steel. For such bars where only a portion of the bar is within 300 mm (12 in.) of the driving surface, epoxy coat the whole bar. Galvanize any anchorage where any portion of the anchorage is within 300 mm (12 in.) of the driving surface. Galvanize according to Section 715. If loop tendon anchorages are used, enclose them in ducts for their entire length. Equip all a nchorages with a permanent grout cap that is vented and bolted to the anchorage. Where the end of a post -tensioned assembly will not be covered by concrete, recess the anchoring devices so that the ends of the prestressing steel and all parts of the anchor ing devices, including grout caps, will be at least 50 mm (2 in.) inside of the end surfaces of the members, unless a greater embedment is shown on the plans. Following post -tensioning, fill the recesses with non -shrink grout and finish flush. Use permane nt grout caps made from fiber reinforced polymer or ASTM A240 Type 316L stainless steel. The resins used in the fiber reinforced polymer shall be nylon, Acrylonitrite Butadiene Styrene (ABS) or polyester. For products made from nylon, the cell class of the nylon according to ASTM D5989 shall be S -PA0141 (weather resistant), S -PA0231 or S -PA0401 (ultimate strength not less than 69 MPa (10,000 psi) with UV stabilizer added). Seal the cap with “0” ring seals or precision fined flat gaskets placed against the b earing plate. Place 13 mm ( 1/2 in.) minimum grout vent on the top of the cap. Grout caps shall be rated for a minimum pressure rating of 1.03 MPa (150 psi). Use ASTM A240 Type 316L stainless steel bolts to attach the cap to the anchorage. When stainless st eel grout caps are supplied, provide certified test reports documenting the chemical analysis of the steel. Submit material certifications and test reports with the working drawings.

503.03.05 Ducts. Provide and accurately place duct enclosures for prestressing steel of mortar -tight rigid

galvanized ferrous metal. Ensure that all connectors, connections , and components of post -tensioning system hardware are rated for the minimum pressure requirements herein. Ducts for prestressi ng steel made up of a single wire, bar or strand, shall have a minimum inside diameter 13 mm (1/2 in.) larger than the diameter of the wire, bar, strand, or couplers to be used. For tendons made up of a plurality of wires, bars, or strands, the duct area s hall be at least 2.5 times the gross area of the pre stressing steel. Use rigid ducts with either welded or interlocked seams. Galvanizing of the welded seam will not be required. Provide ducts of sufficient strength to maintain their correct alignment dur ing placing of concrete. Use positive metallic connections between sections which do not result in angle changes of the joints. Use waterproof tape at the connections. Bend ducts without crimping or flattening. Transition couplings connecting ducts to anch oring devices need not be galvanized. Construct tendons using a minimum number of duct splices. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 253 Accurately align ducts and position at the locations shown on the plans and according to the approved shop drawings or as otherwise directed. The center of gravity of the prestressing force shall not vary from girder to girder unless noted in the plans or approved shop drawings. Securely fasten all internal ducts in position as necessary to maintain accurate duct placement during concreting and at regular intervals not exceeding 610 mm (24 in.) for round galvanized duct and 300 mm (12 in.) for flat ducts to prevent movement, displacement or damage from concrete placement and consolidation operations. Show the method and spacing of duct supports on the shop drawings. Use mandrels as needed to maintain duct alignment and shape. Place ducts providing a smooth and continuous alignment with no lips, kinks , or dents. Provide smooth transitions in duct joints without any kinks. Do not exceed angle changes by more t han ± 3 degrees in any direction. Install post -tensioning ducts to within the following tolerances: Application Vertical Position mm (in.) Lateral Position mm (in.) Horizontal tendons in slabs or in slab regions of larger members ± 6 (1/4) ± 13 (1/2) Longitudinal draped super -structure tendons in webs: Tendon over supports or in middle third of span Tendon in middle half of web depth ± 6 (1/4) ± 13 (1/2) ± 6 (1/4) ± 6 (1/4) Longitudinal, generally horizontal, superstructure tendons in top or bottom of member ± 6 (1/4) ± 6 (/4) Horizontal tendons in substructures and foundations ± 13 (1/2) ± 13 (1/2) Application Longitudinal Position mm (in.) Transverse Position mm (in.) Vertical tendons in webs ± 25 (1) ± 6 (1/4) Vertical tendons in pier shafts ± 13 (1/2) ± 6 (1/4) Construct ends of tendon anchorage entrance and exit angles to within ± 3 degrees of the angle shown on the approved shop drawings when measured in any direction. Provide smooth transitions without any kinks or deviations in the align ment. Locate anchorages within ± 6 mm (1/4 in.) of desired position laterally and ± 25 mm (1 in.) along the tendon except that minimum cover requirements shall be maintained. Position anchorage confinement reinforcing steel as shown on the approved shop drawings in the form of spirals, multiple U shaped bars or links, to be properly centered around the duct and to start within 13 mm (1/2 in.) of the back of the main anchor plate. In the event of conflicts between the reinforcing steel and post -tensioning duct, the position of the post-tensioning duct shall prevail with the reinforcing steel adjusted locally as approved. Carefully check and repair all ducts as necessary before placing concrete. Use methods to place and consolidate concrete which will not displace or damage post -tensioning ducts, anchorage assemblies, splices and connections, reinforcement , or other embedments. Fabricate duct splices to prevent duct kinks during concrete placement. Use mandrels as needed to maintain duct alignment and shape . Plug all tendons except preloaded ducts at the anchorages with plumbing type expanding compression plugs at the time the anchorages are attached to the forms and before concrete placement. Maintain plugs in place until after curing is completed and the ducts are ready for pressure testing prior to strand installation. Place grout inlets and outlets at locations as shown on the plans and working drawings. At a minimum, place grout inlets and outlets in the following positions:

1.Top of the tendon ancho rage.
2.Top of the grout cap.
3.At high points of duct when vertical distance between highest and lowest point is more than 0.5 m (20 in.).
4.At a location 1.0 m (3 ft) past high points of the duct in the direction of grouting.
5.At all low points.
6.At major changes in the cross section of the duct.
7.At additional locations as directed. At high points and 1.0 m (3 ft) past high points , provide a minimum length inlet and outlet above the deck surface of 1.5 m (5 ft) plus 0.3 m (1 ft) for each 10 m (30 ft) of duct between the adjacent low points. 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 254 Mark all inlets and outlets not located at anchorages with a tag indicating the tendon number and vent number for identification during grouting. Provide permanent grout inlets, outlets, and threaded plugs made of ASTM A240 Type 316 stainless steel, nylon, or polyolefin materials. For products made from nylon, the cell class of the nylon according to ASTM D5989 shall be S -PA0141 (weather resistant), S -PA0231 or S -PA0401 (ultimate strength not less than 69 M Pa (10,000 psi) with UV stabilizer added). Products made from polyolefin shall contain antioxidants with a minimum Oxidation Induction Time according to ASTM D3895 of not less than 20 minutes. Test the remolded finished polyolefin material for stress crack resistance using ASTM F2136 at an applied stress of 2.4 MPa (348 psi) resulting in a minimum failure time of 3 hours. Equip inlets and outlets with pressure rated mechanical shut -off valves or plugs rated for a minimum pressure of 1.03 MPa (150 psi). Use inlets and outlets with a minimum inside diameter of 20 mm (3/4 in.) for multi -strand systems and 13 mm (1/2 in.) for single bar tendons and four -strand duct with lengths of less than 30 m (100 ft). Specifically designate temporary items, not part of the p ermanent structure, on the working drawings. Temporary items may be made of any suitable material . The diameter of the opening in the duct for installation of the grout inlets and outlets shall be equal to the inside diameter of the inlets and outlets. After installing ducts and before concrete placement, seal the ends of all ducts, connections to anchorages, splices, inlets and outlets until grouting is complete. Provide an absolute seal of anchorage and duct termination locations by using plumbing type expanding compression plugs or equal. Maintain plugs in place until after curing is completed and the ducts are ready for pressure testing. Grout inlets and outlets shall be installed with plugs or valves in the closed position. Leave low point outlets op en. After completion of concrete curing , prove that the post -tensioning ducts are free and clear of any obstructions or damage and are able to accept the intended post -tensioning tendons by passing a torpedo through the ducts. Use a torpedo having the sam e cross -sectional shape as the duct that is 6 mm (1/4 in.) smaller all around than the clear nominal inside dimensions of the duct, and has rounded ends. Make no deductions to the torpedo section dimensions for tolerances allowed in the manufacture or fixi ng of the ducts. For straight ducts, use a torpedo at least 0.6 m (2 ft) long. For sharply curved ducts, determine the length so that when both ends touch the outermost wall of the duct, the torpedo is 6 mm (1/4 in.) clear of the innermost wall. If the torpedo will not travel completely through the duct, the member will be rejected. A rejected member may be accepted if a workable repair can be made to clear the duct or it is demonstrated that the equivalent cross sectional area of an undamaged duct is pr ovided and all required strand can be loaded into the duct.

503.03.06 Prestressing. Furnish and install prestressing steel and t ension by means of hydraulic jacks so that

the force in the prestressing steel is not less than the value shown on the plans. For post -tensioning of cast -in-place members, distribute the prestressing steel so that the force in each girder stem is equal as required by the plans, or as provided herein. For box girders with more than 2 girder stems, the prestressing force may vary u p to 5% from the theoretical required force per girder stem provided the required total force in the superstructure is obtained and the force is distributed symmetrically about the centerline of the cross section. Distribute the prestressing steel so that the center of gravity of the prestressing tendon path in each girder stem matches the path shown on the plans. Do not install strand into ducts until the curing of the deck is complete, unless flat ducts require installation prior to concrete placement . Push or pull p restress ing strands through the ducts to make up a tendon using methods which will not snag on any lips or joints in the ducts. When strands are pushed, round their ends or fit them with a smooth protective cap. Do not use mechanical devices to rotate strand during the installation into the duct. Alternatively, strands may be assembled to form the tendon and pulled through the duct using a special steel wire sock or other device attached to the end. Do not weld strand together . Round the end of the pre -assembled tendon for smooth passage through the duct. Cut strands using an abrasive saw or equal. Flame cutting is not allowed. Suspend or support strand during loading so that it does not come in contact with the ground. Where strands are pull ed in and must be assembled outside the tendon, provide raised platforms, tarps or other means to prevent dirt and dust contamination of the strands. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 255 Do not post -tension cast -in-place and precast concrete until at least 10 days after the last concrete has been placed in the member and until the compressive strength of concrete has reached the strength required on the plans and shop drawings. Compressive strength shall be determined by cylinder tests. Conduct all stressing operations in the presence of t he Engineer. After stressing, do not cut exposed strand until the elongations are approved. Do not cut or release prestressing steel in any pretensioned member until the concrete has attained the minimum compressive strength value specified for releasing of the steel. Tension prestressing steel to an initial force of 20% of the jacking force , unless shown otherwise on the plans or approved shop drawings . After initial tensioning, apply final jacking force to prestressing steel and measure elongation. Do not allow the temporary tensile stress (jacking stress) to exceed 80% of the specified minimum ultimate tensile strength of the prestressing steel. Do not overstress tendons to achieve the expected elongation. Anchor prestressing steel at stresses (init ial stress) that will result in the ultimate retention of permanent stresses or forces of not less than those shown on the plans . Do not allow the initial stress at the anchorage s to exceed 70% of the specified minimum ultimate tensile strength of the pres tressing steel. Limit the initial stress in the prestressing steel at all locations along the tendon except at the anchorages to 74% of the specified ultimate tensile strength. Working force and working stress will be considered as the force and stress re maining in the prestressing steel after all losses, including creep and shrinkage of concrete, elastic compression of concrete, creep of steel, losses in post-tensioned prestressing steel due to sequence of stressing, friction and take up of anchorages, an d all other losses peculiar to the method or system of prestressing have taken place or have been provided for. The loss in stress in post -tensioned or pretensioned prestressing steel due to creep and shrinkage of concrete, creep of steel, sequence of str essing, and elastic compression of concrete shall be as indicated on the plans. Determine losses p articular to the chosen method or system of prestressing such as sequence of stressing or friction and take up of anchorage and include in submittal of substa ntiating calculations for review. Prepare substantiating calculations in accordance with the bridge design specifications and design parameters as indicated on the plans. Compensate for the loss of prestress in pretensioned members due to the temperature of prestressing steel being appreciably lower than the estimated temperature of the concrete by increasing the calculated elongation. Take into account the loss of prestress in the total forces in the prestressing steel, but do not exceed a jacking stress of 80% of the specified minimum ultimate tensile strength of the prestressing steel. Only use jacking equipment furnished by the supplier of post -tensioning system (tendons, hardware, anchorages, etc.). If power seating st ressing equipment is used to reduce losses due to anchor set, submit certified test results showing the amount of seating loss that can be consistently achieved. Equip each jack used to stress tendons with either a pressure gage or a load cell for determi ning the jacking stress. Provide pressure gage, if used, with an accurately reading dial at least 150 mm (6 in.) in diameter. Calibrate each jack and its gage as a unit with the cylinder extension in the approximate position that it will be at final jackin g force, and accompany with a certified calibration chart. Provide calibrated load cell, if used, with an indicator by means of which the prestressing force in the tendon may be determined. Do not use the lower 10% of the manufacturer’s rated capacity of t he load cell in determining the jacking stress. Calibrate each jack and its gage s as a unit. The calibration shall consist of three test cycles with the cylinder extension of the jack in various positions including the approximate cylinder position expect ed at the final jacking force [i.e. 50 mm (2 in.), 100 mm (4 in.), 200 mm (8 in.), etc strokes ]. At each pressure increment, average the forces from each test cycle to obtain an average force. Perform the calibration with the equipment (jack, pump, hoses, etc.) setup in the same configuration that is intended to be used at the job site. The post -tensioning supplier or an independent laboratory shall perform initial calibration of jacks and gage s. Use load cells calibrated within the past 12 months to calibr ate stressing equipment. For each jack and gage unit used on the project, furnish certified calibration charts and curves prior to stressing. For extended duration projects, furnish updated calibration charts and curves every 6 months, or as requested. Supply documentation denoting the load cells calibration date and traceability to NIST (National Institute of Standards and Technology) along with the jack/gage calibration. 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 256 Any hydraulic jack repair, such as replacing seals or changing the length of the hyd raulic lines, is cause for recalibration using a load cell. Provide a calibrated load cell, if used, with an indicator by means of which the prestressing force in the tendon may be determined. The certified calibration charts for the hydraulic jacks, pre ssure gage s, or load cells used for tensioning prestressing steel may be checked before and during tensioning operations with State -furnished load cells. Provide sufficient labor, equipment, and material to install and support the load cells at the prestre ssing tendons and to remove the load cells after the checking is complete, as ordered. The checking operations will be conducted by the Engineer. Except as noted on the plans or the approved shop drawings, tension post-tensioning tendons from both ends. Apply t he required force at one end and subsequently at the other end. Where one end stressing is shown on the plans or approved shop drawings , and the stressing end is not indicated , tension one-half of the tendons from one end of the member and the other half from the opposite end. For construction in stages where some tendons are required to be stressed before others, install and stress in accordance with the plans or approved shop drawings or as otherwis e approved. Conduct the tensioning process so that tension being applied and the elongation of the prestressing steel may be measured at all times. Mark the strand or provide a positive attachment to the strand so that slippage or uneven jack pull can be easily identified. Record gage pressures and elongations at all times while tensioning and submit for approval. Measure elongations to the nearest 1.5 mm (1/16 in.). Stop stressing operations if the measured elongation at total tendon force is not within ± 5% of the calculated theoretical elongation or if similar tendons differ by more than ± 4%. Determine cause and do not restart stressing operations until corrective measures are approved. Do not exceed the total tendon force to achieve the calculated theoretical elongation. When ordered, check prestressing steel in pretensioned members, if tensioned individually, for loss of prestress not more than 3 hours before placing concrete. The method and equipment for checking the loss of prestress will be subjec t to approval. Re-tension all tendons to the original intended jacking force which show a loss of prestress in excess of 3%. Multi -strand post -tensioning tendons having wire or strand failures, by breaking or slippage during stressing, may be accepted at the discretion of the Engineer under the following conditions:

1.The completed structure shall have a final post -tensioning force of at least 98% of the design total post-tensioning force.
2.For precast or cast -in-place segmental construction or for similar construction that has members post-tensioned together across a common joint face, at any stage of erection, the post -tensioning force across a mating joint shall be at least 98% of the post -tensioning required for that mating joint for that stage of erection.
3.Any single tendon shall have no more than a 5% reduction in cross -sectional area of post -tensioning steel due to wire failure. Investigate persistent wire breakage and change procedures or equipment to avoid or significantly reduce wire or strand failures. Remove and replace tendons in which an unacceptable level of wire or strand failures has occurred . Maintain strand stress between anchorages in precast members until placement of concrete is complete and the concrete has reached the minim um compressive strength shown on the plans. Release prestressing steel in such an order that lateral eccentricity of applied prestressing force will be a minimum. Cut prestressing steel flush with the end of the member, unless otherwise shown on the plans, and coat exposed ends of the prestressing steel with an approved zinc -rich paint.

503.03.0 7 Bonding and Grouting. Bond post -tensioned prestressing steel by completely filling the entire void

space in the duct with grout. Complete grouting each tendon wit hin 14 days of placing the strand or bar into the duct. Fully tension all post -tensioning within the structure prior to any grouting operation. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 257 When shown on the plans, debond pre -tensioned prestressing steel by encasing strands in plastic sheathing along the entire debonded length, and seal the ends with waterproof tape. Split plastic sheathing may be used provided the seam is sufficiently sealed with waterproof tape to prohibit concrete infiltration. Do not use sheathing that will permanently alter the p hysical or chemical properties of the surrounding concrete. Full-length debonding of straight strands will only be allowed if designated on the approved working drawings . Full-length debonding, when permitted, shall be symmetrical about the vertical centerline of the beam and limited to 10% of the total number of straight strands or 6 straight strands, whichever is less. Do not debond draped strands full length.

a.Grouting Operations Plan. Submit a Grouting Operations Plan for approval at least 30 days in advance of grouting operations. Written approval of the Grouting Operations Plan will be required before grouting of the permanent structure takes place. Address and provide procedures for the following:
1.Names and proof of training for the technicians who will be present in the field during grouting.
2.Type, quantity, and brand of materials used including all certifications required.
3.Type of equipment proposed, including capacity in relation to demand and working condition.
4.General grouting procedure.
5.Types and locations of inlets, outlets, vents and drains based on the intended grouting procedure.
6.Calculate of the maximum vertical rise of the grout within the tendon using the actual bridge ge ometry where the vertical rise is defined as the distance between the lowest and highest points within the tendon or the anchorages.
7.Duct cleaning and proofing equipment and methods, including torpedo dimensions.
8.Duct pressure test and repair procedu res.
9.Method to be used to control the rate of flow within ducts.
10.Theoretical grout volume calculations for each typical duct.
11.Mixing and pumping procedures.
12.Direction of grouting.
13.Sequence of use of the inlets and outlet pipes.
14.Propo sed forms for recording grouting information.
15.Procedures for handling blockages. When more than one structure on a contract are being prestressed, the Contractor may submit only one Grouting Operations Plan if the operations are the same for all struc tures and the types and locations of all grout inlets, outlets, vents and drains, calculated maximum vertical rise of the grout, duct cleaning and proofing equipment and methods, direction of grouting and sequence of use of the inlets and outlet pipes are included on the prestressing working drawings for each structure. Before grouting operations begin, conduct a joint meeting of the Contractor, grouting technician and Department personnel. At the meeting the Grouting Operation s Plan, required testing, cor rective procedures, and any other relevant issues will be discussed. Resubmit the Grouting Operations Plan detailing proposed repair methods when grout voids are found.
b.Tendon Grout Trial Batch. Within 48 hours of beginning grouting on a structure, mix a trial batch of grout using the equipment, materials, and proportions proposed for use. Mix a minimum of 150 L (40 gal) of grout. Dispose of excess grout not used for the trail batch testing according to Subsection 107.14. Perform the following tests on the trial batch:
1.Fluidity. Determine the efflux time at 0 quiescent time according to ASTM C939 modified as follows: Fill the flow cone to the top of the cone. When thoroughly mixed, the efflux time of grout will be the time to fill a one liter co ntainer that is placed directly under the flow cone. Ensure the efflux time of the grout immediately after mixing is between 5 and 30 seconds. Let the grout stand in the collection container for 30 minutes without agitation then retest after remixing for 3 0 seconds using a handheld colloidal mixer. Ensure the efflux time of the grout immediately after remixing is 30 seconds or less.
2.Mud Balance. For a tendon grout that meets the required fluidity, determine a wet density value for mud balance comparativ e testing during grouting operations according to American Petroleum Institute Recommended Practice 13B -1. Use this mud balance value during production for acceptance, as specified herein. 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 258 3. Compressive Strength. For a tendon grout that meets the required fluidity, provide two sets of 3 cubes. Testing shall be performed in accordance with ASTM C109.
4.Simulated Field High Temperature Fluidity Test. Where air temperatures are expected to remain above 27 °C (80 °F) during tendon grouting and as directed, p erform a high temperature grout fluidity test as described below using production grouting equipment utilizing both mixing and storage tanks. Tendon grouts shall conform to the requirements of these specifications including initial fluidity test. For the t est to be successful, the tendon grout shall have an efflux time of not greater than 30 seconds at the end of the one hour test period. Determine efflux time by the modified ASTM C939 described herein. Perform the test in a temperature conditioned room. Condition the room, grout, water, duct, pump, mixer and all other equipment to be used to a temperature of 33 °C (90 °F) for a minimum of 12 hours prior to the test. Use 122 m (400 ft) of duct for the test. Use a duct with a nominal inside diameter of 25 mm (1 in.). Mix the tendon grout to the specified water content. Pump the grout through the duct until the grout discharges from the outlet end of the duct and is returned to the pump. Start the one -hour test period after the duct is completely filled with g rout. Constantly pump and recirculate the grout into the commercial grout mixer storage tank. Pump and recirculate the grout for a minimum of one hour. Record , at 15 -minute intervals throughout the test period, the pumping pressure at the inlet, grout temp erature, and fluidity at the discharge outlet.
c.Grouting Procedures and Equipment. Conduct pressure test s for all ducts prior to loa ding strand and after stressing is completed. Do not load strand or commence grouting until pressure tests are successful. Submit complete records of testing prior to loading strand or commencing grouting. A ttach all grouting appurtenances such as valves and grout caps, inlets and outlets, and test the duct with oil free compressed air. Pressurize the duct to 207 kPa (30 psi) and lock -off the outside air source. Record pressure loss for one minute. If the pressure loss exceeds 1 03 kPa (15 psi), repair the duct using approved methods and retest. Do not apply air pressure to multiple ducts simultaneously without prior approval. Provide accessory equipment that will accurately measure the amount of water being added to the mixer. Provide watertight grout hoses, valves, and pipe fittings. Mix prepackaged grout and water in accordance with the manufacturer’s written in structions. Provide grouting equipment with separate motors or engines for the grout mixer, the holding tank, and the grout pump, and a system for controlling each independent of the other. Provide a secondary holding and agitating tank of approximately t he same volume as the primary holding and agitating tank. Use high speed, high shear, colloidal grout mixers capable of continuous mixing that will produce a uniform thoroughly mixed grout, that is free of lumps and undispersed grout mix. Mix for such dura tion, as required by the grout manufacturer, to produce a uniformly blended grout. Do not exceed the water content recommended by the grout manufacturer. Do not add additional water to improve the flowability of the grout. Continuously agitate grout until it is pumped. Determine the fluidity of the grout in accordance with the test requirements of Subsection 503.02.02, at least once at the beginning of each days grouting, or at other times, and at a frequency as directed to verify flow characteristics rem ain within the tolerances specified. The grout sample for fluidity testing may be taken from a production batch of grout. Perform sampling after mixing either prior to entering the pump or at the outlet at the end of the tendon, as directed. The efflux tim e measured at the mixer, at any time during grouting, shall not be more than 5 seconds different from the efflux time at the mixer of the trial batch, and shall also be between 5 and 30 seconds. The efflux time of grout ejected from the vents shall not be more than 5 seconds different than the efflux time at the mixer. Perform mud balance wet density testing on each batch of grout mixed. Compare and document the mud balance wet density with the value obtained during the trial batch, if the value differs by more than 3%, rerun ASTM C939, as modified in these specifications, for continued compliance. Stop grouting if the proposed tendon grout does not produce acceptable fluidity or wet density. Do not restart grouting until the tendon grout product or manufa cturer is changed and another trial batch is successful with a qualified tendon grout. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 259 Use grouting equipment of a positive displacement type capable of maintaining a discharge pressure of at least 1.0 MPa (150 psi), but not more than 1.7 MPa (250 psi) a t the tendon inlets. Provide a pump with adequate seals to prevent introduction of oil, air, or other foreign substance into the grout, and to prevent loss of grout or water. Use grouting equipment with gravity feed to the pump inlet from a hopper attached to and directly over it. Keep the hopper at least partially full of grout at all times during the pumping operation to prevent air from being drawn into the post-tensioning duct. Furnish grouting equipment with a pressure gage having a full -scale reading of not more than 2.0 MPa (300 psi). The pressure gage shall be placed at the duct inlet such that the pressure in the duct can be read at all times even when not actively pumping grout. If hoses in excess of 30 m (100 ft) are used, use two gages, one at t he pump and one at the inlet. Thoroughly clean grouting equipment including mixers, holding tanks, and hoses at the end of each grouting stage or every 4 hours whichever occurs first. Under normal conditions, the grouting equipment shall be able to conti nuously grout the longest tendon in less than 20 minutes. Pump grout within 30 minutes of the first addition of the mix components. Completely empty the grout mixer of grout into the pump or holding tank before mixing another batch of grout in the mixer. Provide standby flushing equipment capable of developing a pressure of 1.7 MPa (250 psi) and of sufficient capacity to flush out any partially grouted ducts due to blockage or breakdown of equipment. Demonstrate that the standby system is accessible and op erable should its use be required. Clean and free ducts of deleterious materials that would impair bonding of the grout or interfere with grouting procedures. Blow out each duct with oil free air within one hour prior to grouting. Pass grout through a screen with 3 mm (1/8 in.) maximum clear openings before introduction into the pump. When hot weather conditions would contribute to quick stiffening of the grout, cool the grout or mix water by approved methods to prevent blockages during pumping operati ons. Extend grout tubes a sufficient distance out of the concrete member to allow for proper closing of the valves. Open all grout outlets before starting the grouting operation. Grout tendons in accordance with the Grouting Operations Plan. Unless appr oved otherwise, pump grout at a rate of 5 to 15 m (16 to 50 ft) of duct per minute. Conduct normal grouting operations at a pressure range of 69 to 345 kPa (10 to 50 psi) measured at the grout inlet. Do not exceed the maximum pumping pressure of 1.0 MPa (1 50 psi) at the grout inlet. Use grout pumping methods that will ensure complete filling of the ducts and complete encasement of the steel. Grout shall flow from the firs t and subsequent outlets until residual water or entrapped air has been removed prior to closing the outlet. Pump grout through the duct and continuously discharge it at the anchorage and grout cap outlets until free water and air are discharged and the consistency of the grout is equivalent to that of the grout being pumped into the inlet. Close the anchorage outlet and discharge a minimum of 7.5 L (2 gal) of grout from the grout cap into a clean receptacle. Close the grout cap outlet. After all outlets have been bled and sealed, elevate the grout pressure to approximately 345 kPa ( 50 psi), seal the inlet valve and wait two minutes to determine if any leaks exist. Note any pressure loss on the gage in -line with the duct. If leaks are present, fix the leaks using approved methods. Repeat the above process until no leaks are present. If no l eaks are present, using caution to always maintain positive pressure, bleed the pressure to approximately 6 9 kPa (10 psi) and wait a minimum of ten minutes for entrapped air to flow to the high points. After the minimum ten minute period has expired, incre ase the pressure as needed and sequentially discharge grout at each high point outlet to eliminate entrapped air or water. Complete the process by locking a pressure of 207 kPa (30 psi) into the tendon by closing the grout inlet valve. If the actual grout ing pressure exceeds the maximum allowed, close the inlet and pump the grout at the next outlet that has just been, or is ready to be closed as long as a one -way flow is maintained. Do not pump grout into a succeeding outlet from which grout has not yet fl owed. If this procedure is used, fit the outlet/inlet to be used for pumping with a positive shut -off and pressure gage. 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 260 When complete grouting of the tendon cannot be achieved by the steps stated herein, stop the grouting operation. Flushing immediately w ith water may be used to remove grout from the tendon. Do not exceed the allowable grouting pressures when flushing. If flushing is not successful or if electing not to flush, submit proposed repair procedures for approval. When freezing weather condition s are possible during and following the placement of grout, keep ducts free of water to avoid damage due to freezing. At the time of grouting, have the surface temperature of the concrete in the member at 7 °C (45 °F) or higher and maintain at or above thi s temperature for 24 hours before and 48 hours after grouting. Do not allow the temperature of the grout to be less than 10 °C (50 °F) nor more than 32 °C (90 °F) during mixing, when measured at the mixer, or during pumping, when measured at the grout inle t. During grouting and for a period of 4 hours after completion of grouting, eliminate vibrations from all contractor controlled sources such as moving vehicles, jackhammers, large compressors or generators, pile driving operations, soil compaction, etc., that are operating within 30 m (100 ft) of the ends of the span in which grouting is taking place. After precast members have been grouted, do not move or otherwise disturb the members for a period of 24 hours. During cold weather conditions, when temperatures are below 10 °C (50 °F), do not move or disturb members for a period of 48 hours. Do not remove or open inlets or outlets until grout has cured for a minimum of 24 hours. In the presence of the Engineer, investigate the ducts for voids between 24 hours and 7 days after grouting completion and within one hour of removal of an inlet or outlet. Remove the vent plugs from the top of each permanent grout cap to determi ne if the cap was completely filled with grout. Remove grout caps where removal of the vent plug indicates incomplete grouting. Reinstall vent plugs after inspection by the Engineer. Inspect inlet and outlet ports at the anchorages and at high points in th e tendons for voids by drilling a minimum of 10%, randomly, as selected by the Engineer, and inspecting with a borescope. Use drilling equipment that will automatically shut off when steel is encountered during drilling so as not to damage strand. Dependin g on the geometry of the grout inlets/outlets, drilling may need to penetrate the inner surface of the trumpet or duct. Should any drilled hole inspection reveal a void with exposed strand, every anchorage shall be drilled. Completely fill voids found with secondary grouting in accordance with an approved grouting repair plan. Drilled holes not indicating voids shall be filled with epoxy using an injection tube extended to the bottom of the drilled hole and withdrawn as the epoxy is injected. Provide a gro uting report signed by the Contractor’s ASBI or PTI trained technician within 72 hours of each grouting operation. Report the theoretical quantity of grout anticipated as compared to the actual quantity of grout used to fill the duct. Give notification imm ediately of shortages or overages. Information to be noted in the records shall include but not necessarily be limited to the following: identification of the tendon; date grouted; time grouting started and ended; number of days from tendon installation to grouting; type of grout; injection end and applied grouting pressure, ratio of actual to theoretical grout quantity; records of air and structure temperature during grouting; summary of tests performed and results; personnel carrying out the grouting work ; summary of problems encountered and corrective action taken; summary of void investigations and repairs made. Provide vacuum grouting equipment at the job site, when required for grouting repairs and when directed, consisting of the following:
1.Volum eter for the measurement of void volume.
2.Vacuum pump with a minimum capacity of 0.283 m3 per minute (10 cfm) and equipped with flow -meter capable of measuring the amount of grout being injected.
3.Manual colloidal mixers and/or dissolvers (manual high speed shear mixers), for voids less than 20 L (5 gal) in volume.
4.Standard colloidal mixers, for voids 20 L (5 gal) and greater in volume. Perform all vacuum grouting operations under the direct sup ervision of a crew foreman who has been trained and has experience in the use of vacuum grouting equipment and procedures.
d.Grout for Pour -backs, Keyways, and Hole Repairs. Use nonshrink grout conforming to Subsection

503.02.03 for filling and repairin g anchorage pour -backs, grout inlets and outlets, keyways and access holes.

Mechanically clean and abrasive blast clean the surface of concrete against which nonshrink grout is to be placed until clean aggregate is exposed. Abrasive blast clean the contac t surfaces of existing concrete and any exposed reinforcing steel, as necessary, to remove all rust, paint, grease, asphalt or other foreign materials. Take necessary steps to not damage reinforcing steel coatings. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 261 Remove ends of grout vents a minimum of 75 mm (3 in.) below the top of the top slab and a minimum of 50 mm (2 in.) from the bottom surface of all bottom slabs or vertical surfaces after grouting has been completed. Top slab grout vents extended to the edge of deck to exit within the barrier area may be removed flush with the surface of the deck. Use cored holes or formed blockouts with 25 mm (1 in.) minimum deep vertical edges at all sides. Do not use blockouts larger than 125 mm (5 in.) in largest horizontal dimension. Do not sawcut past corners on square blockouts to obtain the required vertical surfaces. Following surface preparation, coat surfaces with Type II epoxy conforming to Subsection 728.03.02. Apply bonding agent to saturated surface dry concrete and in accordance with the manufacturer’s recommendations . Immediately prior to placing the nonshrink grout, re -clean all surfaces by air blasting, or by other approved means, as necessary to remove any debris which have accumulated during construction or after abrasive blast clean ing. Place nonshrink grout when surface temperature of the areas to be covered is between 7 and 32 °C (45 and 90 °F). Methods proposed to heat said surfaces are subject to approval by the Engineer. Place nonshrin k grout when the contact surface is saturated surface -dry. Cure n onshrink grout after initial set by continual wetting with water for a period of 48 hours. After 48 hours of wet curing , spray the nonshrink grout with two coats of curing compound as specif ied in Section 501. Provide a flow cone and cube molds with restraining plates for onsite evaluation of nonshrink grout . Make three 50 mm by 50 mm (2 in. by 2 in.) cubes for each 0.5 m3 (0.67 yd3) of nonshrink grout used. Provide restraining caps for the cube molds in accordance with USACE CRD-C621. Store cubes at 21 °C (70 °F). Nonshrink grout cubes shall test equal to or greater than the specified minimum 28 -day strength. Submit test reports for cubes for approval. Do not use nonshrink grout that is caked, lumpy, or shows any signs of deterioration. Nonshrink grout will be rejected if the grout does not achieve the design fluidity or consistency when mixed according to the manufacturer’s recommendations. Nonshrink grout used in pourbacks exceeding 0.028 m3 (1 ft3) in volume may be extended by adding graded, dust-free, hard, 12.5 mm ( 1/2 in.) diameter rounded aggregate supplied by the grout manufacturer. Vibrate nonshrink grout extended with aggregate. Do n ot use calcareous aggregate made from limestone. Use mix proportions in conformance with manufacturer's written recommendations. Grout extended with aggregate shall meet the specified strength requirements. Prior to deck grooving, coat the repaired access holes, block -outs and an area extending 150 mm (6 in .) outside the perimeter of the repair with an approved crack sealant specified in Section 646 . Apply and remove excess material as per manufacturer’s instructions.

503.03.08 Curing Precast Member s. Cure precast members according to Subsection 501.03.0 8 or by

accelerated curing. Inadequate curing facilities or lack of attention to proper curing of precast members will be cause for rejection of the precast member. When the curing compound method is used, abrasive blast clean portions of precast members upon which concrete will be cast later.

a.Accelerated Curing . Perform low pressure steam or radiant heat curing under a waterproof enclosure that allows for free circulation of heat about the produc t and that is constructed to contain the live steam and heat with minimum moisture loss. Maintain a relative humidity within the enclosure of not less than 90% during the entire curing period. Do not use accelerated curing methods that allow one portion o f a member to cure differently than other portions of the member unless approved. Limit the temperature differential within the enclosure to no more than 11 °C (20 °F). Steam shall be low -pressure and saturated. Do not apply live steam directly on the concrete, forms or test cylinders or so as to cause localized high temperatures. Provide and use temperature probes to monitor the internal concrete temperature and the air temperature at the concrete surfaces with in curing enclosures. Attach each temperature probe to a multi -channel continuous recording temperature device. Provide and use a minimum of 2 air temperature probes in each curing chamber, spaced approximately at or near the third points of the bed length. For curing chambers over 60 m (200 ft) in length, provide one additional air temperature probe for each 60 m (200 ft) increment. Provide a minimum of 2 concrete temperature probes embedded within the member located in areas that are expected to ach ieve the highest internal temperatures. Space temperature probes approximately at the third points the length of the member. Provide one 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 262 air temperature probe located outside of the curing enclosure in a shaded location. The system accuracy of the temperat ure probes and recording device shall be accurate to within 3 °C (5 °F) and recording devices shall continuously record the date, time, and temperatures of the enclosure and concrete during the entire heating and cooling cycles. Provide temperature records for each member for approval prior to transporting the members. Missing or incomplete time -temperature records will be cause for rejection of the precast member. After the last concrete is placed , maintain an internal concrete temperature between 10 °and 30 °C (50 and 86 °F) until the concrete has reached initial set as determined by ASTM C403. During the delay period before starting accelerated curing, keep exposed surfaces continuously wet using atomizing nozzles that form a fine mist or by the use of wet blankets. After initial set, apply heat at a rate such that the maximum internal concrete temperature does not increase more than 20 °C (36 °F) per hour. Do not exceed a maximum internal concrete temperature of 82 °C (180 °F) at any point within the member during curing. Me mbers subjected to temperatures beyond this maximum limit will be rejected and will not be considered for further evaluation for use. Maintain the maximum curing temperature uniform throughout the enclosure, with variation of not more than 11 °C (20 °F) from the maximum peak temperature until the concrete reaches the required release strength. Allow the concrete element to cool gradually at a maximum cooling rate of 20 °C (36 °F) per hour and continue cooling until the concrete is not more than 20 °C (36 °F) above the ambient temperature outside the curing enclosure. Transfer prestressing force into precast memb ers immediately after accelerated curing is terminated. Cure test cylinders under conditions that simulate those of the member. If the forms are heated by steam, locate test cylinders in the coolest zone throughout curing.

503.03.09 Handling, Transportin g, Storage, and Erection of Precast Members. During handling, transport,

storage, and erection, keep each precast girder vertical and upright to prevent twisting, racking, or other distortion that would result in cracking or damage to the precast member. U se equipment and erection methods that will not damage precast girders. Repair or replace damaged girders as determined by the Engineer. Repair all damaged girders by approved methods and materials. Lift precast girders only at their ends by approved lifti ng devices. Provide lateral bracing to prevent tipping or buckling. Do not remove precast members from forms sooner than six hours after casting and not until the concrete strength is sufficient to avoid structural damage. For AASHTO Type V, Type VI, and Bulb-T Beams, do not remove the forms supporting the top flange concrete sooner than 12 hours after casting unless the release strength has been reached. Transport precast girders at least 7 days after final concrete placement and upon reaching the requir ed 28 -day compressive strength. Do not place any loads on precast units until the 28 -day compressive design strength is reached. Store precast members in the precast yard and at the jobsite on level, stable foundations that will keep them in a vertical p osition and prevent twisting or rotation. Support girders on only two points of support within a distance not greater than 3% of the beam length from their ends. When approved, cantilever beams may be supported at locations other than near the ends. Provid e a clean and well drained storage area. Prevent excessive or differential settlement of members by storing them on stable ground and on dunnage of sufficient size, shape , and strength to prevent crushing. Immediately pick up members that have rotated or twisted and adjust supports to provide level and uniform support for the members. Support concrete box beams and U -beams beneath end diaphragms during handling, storage, hauling , and erection. When members are stacked, separate them with blocking arranged in vertical planes that will not crush under load. Stack members so that lifting devices are not damaged. Rearrange improperly stored members and inspect them for damage. Members that are improperly stored and become cracked, warped, or otherwise damaged in storage may be rejected. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 263 Where feasible, base the selection of storage sites, storage conditions and orientation upon consideration of minimizing the thermal and time -dependent creep and shrinkage effects on the camber and/or sweep of the membe rs. Measure and record the sweep and camber of beams monthly. Keep the measurement records on file for review at any time , and upon request, provide a copy of these measurements. If the sweep exceeds the tolerance specified, take immediate measures to bri ng the sweep of the product back to within tolerance. Give notification immediately when the sweep or camber exceeds the specified tolerances. Provide tie -downs, anchors, temporary shoring, diaphragms, and other devices to keep members stable and in-place before they are permanently incorporated into the work. When railroad or roadway traffic must be maintained beneath beams already placed, protect traffic against falling objects during the erection of diaphragms and other structural members, during the p lacing of cast -in-place concrete, and during the erection and dismantling of forms. Protect traffic with nets or flooring with openings not larger than 25 mm ( 1 in.) or as approved. Provide 15 days written notice before starting erection. Submit erection drawings according to Subsection 105.02. Do not consider the approval of erection drawings as relieving the responsibility for the safety and adequacy of methods or equipment or from carrying out the work in full accordance with the plans or specification s. Erection drawings shall include complete details of the erection plan and procedure to include but not limited to:

1.Procedure and sequence of operation.
2.Temporary falsework supports, bracing, and attachments to other structures.
3.Girder masses, lifting locations, lifting devices, and spreaders.
4.Cranes make and model, mass, geometry, lift capacity, and outrigger size and reactions.
5.Locations of cranes and delivery trucks.
6.Locations of crane outriggers relative to other structures includin g retaining walls and wingwalls.
7.In-place temporary tie -downs, anchors, diaphragms, bracing , and other devices. Submit along with erection drawings , all notes, calculations, assumptions, and dimensions used in the development of the erection plan and procedure. Include material properties and specifications, structural analysis, and any other data used. Submit all changes to the erection drawings in w riting for review and approval. Correct beam discrepancies including, but not limited to, horizontal misalignment or variations in vertical camber, to achieve a sa tisfactory completed structure . Correction may require replacement of the member. 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 264 503.03.1 0 Tolerances for Precast Members. Fabricate precast prestressed concrete members to plan dimensions within the tolerances listed below (tolerances are not to be considered accumulative). Dimension I-Beams and Bulb -Tee Beams U-Beams Box and Slab Beams Length ................................ ................................ ........ ± 19 mm (3/4 in.) ..................... ± 25 mm (1 in.) ................... ± 13 mm (1/2 in.) Width ................................ ............................ + 19 mm (3/4 in.), - 6 mm (1/4 in.) ...... ± 13 mm (1/2 in.) ................. ± 10 mm (3/8 in.) Nominal depth ................................ ............... + 13 mm (1/2 in.), - 6 mm (1/4 in.) ...... ± 13 mm ( 1/2 in.) .................. ± 6 mm (1/4 in.) Thickness: Top slab or flange ................................ ..... + 13 mm (1/2 in.), - 6 mm (1/4 in.) ...... ± 13 mm (1/2 in.) .................. ± 6 mm (1/4 in.) Bottom slab or flange ................................ + 13 mm (1/2 in.), - 6 mm (1/4 in.) ...... ± 13 mm (1/2 in.) ....... + 25 mm (1 in.), - 0 mm (0 in.) Web or wall ................................ ............... + 19 mm (3/4 in.), - 6 mm ( 1/4 in.) ...... ± 13 mm (1/2 in.) .................. ± 6 mm (1/4 in.) Horizontal alignment ................................ ............................. — ................................ .......... — .............................. ± 6 mm (1/4 in.) per 3 m (10 ft) of length ................................ ........... ± 3 mm (1/8 in.) .................. ± 3 mm (1/8 in.) with .......................... — ± 19 mm (3/4 in.) max. Deviation of ends (horiz ontal skew ) ............................. ± 6 mm ( 1/4 in.) ................................ — ................................ ........ — per 0.3 m (1 ft) of width ................................ ..................... — ............................ ± 3 mm (1/8 in.) with ............ ± 3 mm ( 1/8 in.) with ± 13 mm (1/2 in.) max. ± 13 mm (1/2 in.) max. Deviation of ends (vert ical batter) per 0.3 m (1 ft) of width ................................ ....... ± 3 mm (1/8 in.) with .............. ± 3 mm (1/8 in.) with ............ ± 3 mm (1/8 in.) with ± 13 mm (1/2 in.) max. ± 13 mm (1/2 in.) max. ± 13 mm (1/2 in.) max. Notched end areas, diaphragms : Depth ................................ ................................ ...... ± 6 mm (1/4 in.) ................................ — .............................. ± 6 mm (1/4 in.) Length ................................ ......................... + 50 mm (2 in.), - 25 mm (1 in.) .................... — .................. + 50 mm (2 in.), - 25 mm (1 in.) Bearing surfaces: Perpendicular to vertical axis ................................ .. ± 3 mm (1/8 in.) ................................ — ................................ ........ — Deviation from plane ................................ ............ ± 1.5 mm (1/16 in.) .................. ± 3 mm (1/8 in.) ................... ± 3 mm (1/8 in.) Longitudinal spacing : Between centers of plates ................................ .. ± 13 mm (1/2 in.) ................... ± 13 mm (1/2 in.) .................. ± 3 mm (1/2 in.) Centers of plates to member ends ...................... ± 13 mm (1/2 in.) ................... ± 13 mm (1/2 in.) ................. ± 13 mm (1/2 in.) Insert or anchor hole location: From end of member ................................ . + 19 mm (3/4 in.), - 6 mm (1/4 in.) ....... ± 6 mm (1/4 in.) ................... ± 6 mm (1/4 in.) Longitudinal spacing ................................ .............. ± 19 mm (3/4 in.) ................... ± 13 mm (1/2 in.) ................. ± 13 mm (1/2 in.) Transverse location ................................ ................ ± 13 mm (1/2 in.) ................... ± 13 mm (1/2 in.) .................. ± 6 mm (1/4 in.) Vertical location ................................ ...................... ± 13 mm (1/2 in.) ................... ± 13 mm (1/2 in.) ................. ± 13 mm (1/2 in.) Diaphragm or lateral tie location ................................ . ± 13 mm (1/2 in.) ............................... — ............................. ± 13 mm (1/2 in.) Position of internal void form (longitudinal for box beams and U -beams) ................................ ............ — ................................ ± 25 mm (1 in.) .................. ± 25 mm (1 in.) 1,2 Projection of reinforcing outside of member .............. + 13 mm (1/2 in.), .................. + 13 mm (1/2 in.), ................ + 13 mm (1/2 in.), - 19 mm (3/4 in.) - 19 mm (3/4 in.) - 19 mm (3/4 in.) Position of strand center of gravity : Vertical or Horizontal ................................ .............. ± 6 mm (1/4 in.) 3 ................... ± 6 mm (1/4 in.) ................... ± 6 mm (1/4 in.) Debonded length of strands ................................ ........ ± 75 mm (3 in.) ...................... ± 75 mm (3 in.) .................... ± 75 mm (3 in.) Position of strand hold -down points ............................ ± 150 mm (6 in.) .................... ± 150 mm (6 in.) .................. ± 150 mm (6 in.) Position of handling devices : Parallel to length ................................ .................... ± 150 mm (6 in.) .................... ± 150 mm (6 in.) .................. ± 150 mm (6 in.) Transverse to length ................................ ............... ± 25 mm (1 in.) ...................... ± 25 mm (1 in.) .................... ± 25 mm (1 in.) Local flatness of formed surfaces (excluding bearing surface) per 3 m (10 ft) ............................... ± 6 mm (1/4 in.) ..................... ± 6 mm (1/4 in.) ................... ± 6 mm (1/4 in.) Position of post -tensioning ducts at ends of girders where spliced , vertical and horizontal ......... ± 13 mm (1/2 in.) ................... ± 13 mm (1/2 in.) ............................ — Camber differential: Between adjacent members ................................ .. 25 mm (1 in.) max. .............. 13 mm (1/2 in.) max. ........... 13 mm (1/2 in.) max. Between high and low members in same span .................. — ................................ .......... — ........................... 25 mm (1 in.) max. 1 Voided box beams only. 2 Length of box beam internal void form + 25 mm (1 in.), - 150 mm (6 in.). 3 For draped strands, the tolerance for vertical position of the center of gravity of strands at the end of the beam may be inc reased to ± 13 mm (1/2 in.) provided the tested concrete compressive strength, before release of strand, is at least 5% greater than the release strength shown on the plans. Horizontal misalignment (sweep) in beams, which may increase at a later time and exceed the tolerance specified , may be acceptable if the members can be hauled, erected, and aligned to within the allowable tolerance without being damaged. Store these members in a manner that will minimize the sweep. Embedments shall be firmly held in proper position to avoid movement durin g concrete placement. Place embedments in accordance with the manufacturer’s recommendations. If stay -in-place metal deck forms are allowed, as shown on the plans, place weld clip inserts for permanent metal deck forming no more than 1.6 mm (1/16 in.) fro m the beam edge. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 265 503.03.11 Defects in Precast Members. Evaluate and correct defects in precast members. If defects affect the precast member’s structural integrity, as determined by the Engineer, the precast concrete member will be rejected. If the Engineer determines that a defect is a cosmetic or minor defect, appropriate repairs may be executed immediately according to Subsection 503.03.12 . Perform and complete cosmetic and minor defect repairs to the satisfaction of the Engineer. If the E ngineer determines that a defect is a major defect , submit a n engineering evaluation and repair proposal according to Subsection 503.03.12 (h). Make all repairs that require a repair proposal under the observation of and to the satisfaction of the Engineer .
a.Surface Defects . Surface defects are defined below. Regardless of the types of defects , when the total surface area of all defects within a single product exceeds 2.0% of the product’s length times its depth, the product will require evaluation and repair according to Subsection 503.03.1 2 (h).
1.Bug hole. A bug hole is a void caused by air that is entrapped against the form and that has an area up to 1935 mm2 (3.0 in2) and a depth up to 38 mm (1.5 in.). Treat any bug hole with a dimension exceeding either of these dimensions as a honeycomb. A bug hole with a depth less than 6 mm (0.25 in.) and less than 19 mm (0.75 in.) in diameter will not require repair . Consider all other bug holes cosmetic and repair them according to Subsection

503.03.12 (a).

2.Spall. A spall is a depression resulting when a fragment is detached from a larger mass by impact, action of weather, by pressure , or by expansion within the larger mass. A cosmetic spall is a circular or oval depression not greater than 25 mm (1.0 in.) in depth or greater than 1935 mm2 (3.0 in2) in area, and shall be repaired according to Subsection 503.03.12 ( a). With the exception of the spalls at the top flange of the beam -ends, a minor spall is defined as a spall not larger than 0.19 m2 (2.0 ft2) and no deeper than the concrete cover on the bar reinforcing steel. A spall located at the edge of the top flange, within 1/4 length from the beam -end, is considered a minor s pall if the total longitudinal length of the defect does not exceed 3 m (10 ft) and if any of the lateral dimensions of the spall perpendicular to the longitudinal axis of the beam is not greater than 15% of the width of the top flange. Repair minor spalls according to Subsection 503.03.12 ( c). A major spall is a spall that any of its dimensions exceeds the dimensions that are described for minor spalls. Evaluate and r epair major spall s according to Subsection 503.03.1 2 (h).
3.Chip. A chip is the local breaking of the corners or edges of the concrete with the resulting void containing angular surfaces. Cosmetic chips are chips where the sum of the two lateral dimensions perpendicular to the length does not exceed 50 mm (2.0 in.). Regardless of length, it is not necessary to repair cosmetic chips except for visually exposed reinforcing steel, prestressing strand, insert, or weldments surfaces, which may require repair according to Subsection 503.03.12 ( d). Minor chips are chips where the sum of the two la teral dimensions perpendicular to the length exceeds 50 mm (2.0 in.), but does not exceed 100 mm (4.0 in.), and with a length of no more than 0.3 m (1 ft). Repair minor chips according to Subsection 503.03.12 ( d). Major chips are chips larger than minor chips. Evaluate and repair major chips according to Subsection

503.03.12 (h).

4.Surface Porosity. Surface porosity is considered a minor defect and is the localized porosity of a formed surface due to medium scalin g. Medium scaling is defined as the loss of surface mortar up to 9 mm (3/8 in.) in depth and exposure of concrete aggregate. Repair surface porosity according to Subsection 503.03.12 ( b).
5.Honeycombing. Honeycombing is voids in the concrete, loss of fin es or other material from between the aggregate particles, the inclusion of air pockets between aggregate particles, or larger volumes of lost material. Remove honeycombing in its entirety to sound concrete before establishing the classification of the def ect. Minor honeycombing is a void no deeper than the concrete cover on the bar reinforcing steel and no larger than 0.185 m2 (2.0 ft2) in area that results after the removal of unsound material. Repair minor honeycombing according to Subsection 503.03.12 (e). 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 266 Major honeycombing is a void deeper than concrete cover regardless of the surface area, or shallower but with a surface area greater than 0.185 m2 (2.0 ft2) that results after the removal of unsound material. Major honeycombing requires evaluation and repair according to Subsection 503.03.1 2 (h).
b.Formed Surface Misshaping. Formed surface misshaping is the visual and measurable defect or excess of material from the specified tolerance on any surface of a product. Any defect exceeding the plan dimensions for size, length, squareness, designated skew, deviation from vertical, and the like by up to twice the specified plus (+) tolerance may be corrected by grinding to within the allowable tolerance according to Subsection 503.0 3.12 ( f). Defect s exceeding the specified minus ( -) tolerance or twice the specified plus (+) tolerance requires evaluation and repair according to Subsection 503.03.1 2 (h).
c.Bearing Areas. Consider the bearing area to extend from the end of the produc t to 75 mm (3 in.) beyond the edge of the bearing contact area for the full product width. Treat minor depressions in the bearing area, 3 mm (1/8 in.) maximum, with an approved low -viscosity epoxy, applied by the use of a squeegee. Grind bearing areas to final position with a carborundum disk if it is necessary to remove material.
d.Cracks. A crack is the separation of a product or portion thereof which may appear before or after detensioning and may or may not cause separation throughout the product thi ckness or depth. Identify cracks by the classifications and locations described below and subject them to repair as specified . Regardless of the classifications and locations of cracks within any single product, if the total surface length of all cracks on any and all surfaces exceeds one -third of the product’s length, the product requires evaluation and repair according to Subsection 503.03.1 2 (h). Establish crack sizes subsequent to release of all pretensioning forces. Regardless of cause, cracks in pre cast members shall be identified and repaired according to their surface appearance in accordance with the classifications listed herein. Cracks will be identified by the Engineer as occurring in either critical or non -critical locations of the product. Cosmetic cracks are classified as any cracks which are less than 0.15 mm (0.006 in.) wide and are in non-critical locations on the product. Minor cracks are classified as any cracks which are between 0.15 mm (0.006 in.) and 0.30 mm (0.012 in.) wide, inclusive, and are in non -critical locations on products. Repair cosmetic and minor cracks according to Subsection 503.03.12 (g). Major cracks are any cracks of any width which are located in critical locations on produc ts or cracks in non-critical locations of the product, which are greater than 0.30 mm (0.012 in.) wide. Major cracks require evaluation and repair according to Subsection 503.03.1 2 (h).

503.03.12 Repair of Precast Members. Repair cosmetic and minor defects in precast members and provide

an engineering evaluation for the repair of major defects as indicated in Subsection 503.13.11 and herein. Submit proposed alternate repair methods for approval. For each project, maintain a record of precast member defects and repair methods. Include in the record information about product description, unit production number, casting date, defect description including dimensions, repair method and materials, defect discovery date, and signature of producer’s Q uality Control Manager indicating concurrence with the information. Do not ship products, which require repairs, from the casting yard to the project site until such repairs are complete and approved . Before beginning the repair of member defects , remove laitan ce, loose material, form oil, curing compound and deleterious matter from repair area. Nonshrink grout shall conform to Subsection 503.02.03. Mix, apply, and cure the grout in accordance with the manufacturer’s recommendations. Apply epoxy bonding agent s according to the manufacturer’s recommendations and as directed. Cure repaired surfaces for 72 hour s or as otherwise indicated in the written recommendations from the manufacturer of the repair products . Ensure the repaired surfaces have a surface textu re, finish , and color that matches the appearance of the unaffected surrounding area of the product.

a.Cosmetic Surface Filling. Fill repair areas with nonshrink grout. Coating of the prepared surface with epoxy bonding agent before grout placement is n ot required. PRESTRESSED CONCRETE AND PRECAST MEMBERS 503 267 (b) Surface Restoration. Maintain the surface continuously wet for a minimum of three hours before application of repair material. Fill repair areas with a mortar mix consisting by volume of one part cement, 2.5 parts sand that will pass a 1.18 mm ( No. 16 ) sieve, and sufficient water to produce a viscous slurry mix or repair areas to be restored with nonshrink grout and cure . Cure areas repaired with a mortar mix in accordance with Subsection 501.03.0 8. Coating of prepared surface s with epox y bonding agent before grout placement is not required.
c.Cutting and Filling. Carefully cut all feathered edges of the area to be repaired back perpendicular to (or slightly undercut from) the surface to the depth of sound concrete or to a minimum dept h of 13 mm (1/2 in.), whichever is deeper. Coat the prepared surface with an approved epoxy bonding agent . Fill the cutout area with nonshrink grout , firmly consolidate, and cure .
d.Restoration of Surfaces and Edges. When reinforcing steel, prestressing strand, inserts or weldments are exposed, remove concrete from around the items to provide a 25 mm (1 in .) clearance all around or to sound concrete, whichever is more. Form surfaces and edges to the original dimensions and shape of the product. Coat the prepared surface with an approved epoxy bonding agent. Restore surfaces and edges with nonshrink grout, firmly consolidate, and cure.
e.Removal and Restoration of Unsound Concrete. Carefully cut the area of unsound concrete to be repaired back perpendic ular to (or slightly undercut from) the surface and to the depth of sound concrete or to a minimum depth of 25 mm (1 in.), whichever is deeper. When reinforcing steel, prestressing strand, inserts or weldments are exposed, remove the concrete from around t he items to provide a 25 mm (1 in .) clearance all around or to sound concrete, whichever is more. Coat the prepared surface with an approved epoxy bonding agent and fill with a nonshrink grout, firmly consolidate, and cure. Restore surfaces and edges to the original dimensions and shape of the product.
f.Surface Grinding. Grind off misshaped formed surfaces with an abrasive stone. Apply two coats of an approved crack sealant specified in Section 646 to surfaces which are not subsequently encased in concrete, immediately after grinding has been accepted. Do not apply crack sealant to surfaces to be subsequently encased in concrete.
g.Crack Repair . Treat cosmetic cracks after member detensioning with spray -on waterproofing conforming to Section 646 and as approved. Treat horizontal cosmetically cracked surfaces that will be exposed in the completed structure with crack sealant conforming to S ection 646. Repair minor cracks after member detension ing by epoxy injection with epoxy conforming to Subsection

728.03 01.

Prior to commencing epoxy injection repair, submit specifications on the epoxy materials and injection equipment , Material Safety Data Sheets , and a written procedure for the injection process. Clean the areas surrounding the crack of deteriorated concrete. Remove contaminants that may be detrimental to adhesion. The crack may be ruffed or veed in to accommodate insertion of injection ports. Perform drilling of the crack for injection ports with a vacuum attached swivel drill chuck. The crack may be slotted to facilitate installation of injection tees. Seal the surface of the crack and the area surrounding the entry ports with an approved epoxy. Use approved entry port devices spaced at intervals to insure full penetration of the epoxy. Use a surface seal epoxy of adequate strength to hold injection ports firmly in place and to resist injection pressures to prevent leakage during injection. Accomplish injection of the epoxy by a mach ine capable of metering and mixing the component proportions with a tolerance of 2.0%. Operate the injection machine at a nozzle pressure of approximately 172 kPa (25 psi). Begin injection of epoxy at the lower entry port and continue until appearance of epoxy at the adjacent port. Perform epoxy injection in the next adjacent port where epoxy has appeared. Continue this operation until the cracks are completely filled. Upon completion of the injection of epoxy and after initial cure, remove the entry ports and patch the area. 503 PRESTRESSED CONCRETE AND PRECAST MEMBERS 268 (h) Engineering Evaluation and Repair Proposal . For repair of major defects, submit an engineering evaluation and repair proposal for approval. Allow 14 days for proposal review and final disposition. Do not commence repairs to major defects before receiving written approval of the proposal. Include the following information in the proposal:

1.A cover letter indicating that the proposal has been prepared under the direction of an engineer who is registered as a Civil or Structu ral Engineer in the State of Nevada.
2.A description of the products addressed as part of the proposal.
3.Information d ocumenting complete details of the product defects.
4.Description of the proposed repair procedures including repair materials, product preparation, and curing of repair materials.
5.A structural assessment of the repaired product’s ability to perform its in tended function.
6.An assessment of durability of the repaired product relative to similar, defect -free products.
7.Any other supportive information, pictures , and sketches. When requested, provide a signed and sealed statement from the registered engineer who prepared the proposal that they have physically inspected the repairs and attest the repairs have been performed i n full conformance with the approved proposal.

503.03.1 3 Surface Finish of Precast Members. Apply an ordinary surface finish to all precast concrete

member surfaces as described in Subsection 502.03.18, unless otherwise noted on the plans. Finish the to p interface between precast concrete members and cast -in-place concrete decks by screeding the concrete to provide a dense surface without a smooth sheen or laitance . Just prior to the concrete reaching its initial set, texture the interface surface. Use a steel brooming tool to etch the surface transversely to the member leaving grooves 6 mm (1/4 in.) to 13 mm (1/2 in.) wide, between 6 mm (1/4 in.) and 13 mm (1/2 in.) deep, and spaced 6 mm (1/4 in.) to 13 mm (1/2 in.) apart. METHOD OF MEASUREMENT

503.04 01 Measurement. Precast concrete members (reinforced or prestressed) will be measured by the each.

The length of the members shown in the estimate of quantities and/or in the proposal are nominal. For exact length see the drawings of the members shown on t he plans. If concrete in precast concrete members fails to meet the specified 28 day compressive strength, liquidated damages will be assessed or the concrete will be rejected, all according to Sections 501 and 502. Liquidated damages will be based on the value of the concrete in a given member being equal to 50% of the contract unit price bid per unit for the members. Prestressing cast -in-place concrete will be measured by the lump sum. The concrete for post -tensioned cast -in-place concrete structures will be measured under Section 502. The reinforcing steel for post -tensioned cast -in-place concrete structures will be measured under Section 505. Additional concrete or reinforcing steel required by the particular system used will not be measured or paid for directly. BASIS OF PAYMENT

503.05.01 Payment. The accepted quantities, measured as provided above, will be paid for at the contract

price per unit of measurement for the pay items listed below that are shown in the proposal. Payment will be full comp ensation for the work prescribed in this Section. Payment will be made under: Pay Item Pay Unit (length) Precast Concrete Members ................................ ................................ ................................ ................................ .................. Each Prestressing Cast -In-Place Concrete ................................ ................................ ................................ ................................ ....... Lump Sum 269 SECTION 504 LIGHTWEIGHT CONCRETE FOR STRUCTURES DESCRIPTION

504.01.01 General. This work consists of furnishing and placing lightweight Portland cement concrete in

bridges, culverts, and other types of concrete structures. MATERIALS

504.02.01 General. Material shall conform to the following Sections and Subsection:

Portland Cement Concrete ................................ ................................ ................................ ................................ ..................... Section 501 Admixtures ................................ ................................ ................................ ................................ .............................. Subsection 501.02.04 Concrete Structures ................................ ................................ ................................ ................................ ............................... Section 502 Aggregates for Portland Cement Products ................................ ................................ ................................ ............................. Section 706

504.02.02 Concrete Making Properties. Lightweight concrete shall be subject to the following requirements

and test methods: Test Test Method Requirements Making Test Specimens (laboratory) ................................ ............... ASTM C192 ................................ .......... — Making Test Specimens (field) ................................ ........................... Nev. T428 ................................ .......... — Compressive Strength ................................ ................................ ..... ASTM C39 * ................................ ....... Table I Unit Weight & Cement Factor (wet) ................................ .................... Nev. T435 ................................ ....... Table I Tests for Popouts ................................ ................................ ............ ASTM C330 ............................ No Surface Popouts Air Content ................................ ................................ ......................... Nev. T431 ................................ ....... Table I Slump ................................ ................................ ................................ . Nev. T438 ................................ ....... Table I Air Dried Weight ................................ ................................ .............. ASTM C567 ................................ ....... Table I Coring Concrete ................................ ................................ ................ ASTM C42 ........................... Subsection 504.04.01 * The compressive strength requirements of Portland cement concrete will be based on the strength test, which is defined as the average of the breaking strength of 3 standard cylinders at 28 days. The compress ive strength test will be required for each 38 m3 (50 yd3), or portion thereof, placed each day. For large continuous pours, one test near the beginning of the pour and one test near the end of the pour may be substituted for the 38 m3 (50 yd3) requirement. Other cylinders may be made and broken for informational purposes. CONSTRUCTION

504.03.01 General. The construction of conventionally reinforced lightweight concrete structures shall conform

to Sections 501 and 502, with the exceptions contained in this Section. Give not less than 32 days notification in advance of use of the proposed sources of materials and make arrangements for the Engineer to obtain samples as required for testing purposes. Samples will not exceed 225 kg (500 lb) fo r each separate grading. Furnish a written statement giving the amount of cement in kg/m3 (lb/yd3), the proportions of cement and each size of aggregate in a saturated surface dry condition, the slump, and the percentage of air in the concrete proposed for use in the work. If proposing to use an admixture other than an air -entraining agent, state its complete brand name and the quantity proposed to be used per m3 (yd3) of concrete. The Engineer, after making such tests as deemed advisable, will either acc ept the proposed materials and proportions or suggest modifications needed for acceptance. After acceptance of batch proportions and materials, do not alter them during the course of the work except as found necessary to maintain yield, amount of cement, and unit mass within specification requirements. Do not revise batch proportions resulting in concrete that contains an amount of total water per cubic meter (cubic yard) greater than 105% of that contained in concrete of the accepted proportions.

504.03 02 Storage of Aggregates. Stockpile lightweight aggregate on the job or at a central batching plant for

a minimum time of 24 hours before its use. Stockpile fine and coarse aggregates separately.

Source: Nevada Standard Specifications for Road and Bridge Construction, 2014 Edition. Pages 253274 of 610.