ADA Bathroom Requirements — Clearances, Grab Bars & Fixtures
Accessible toilet rooms are covered by Sections 603–606 of the 2010 ADA Standards. The controlling geometry: a 60-inch turning circle, a water closet centered 16–18 inches off the side wall, and grab bars on the side and rear walls.
Worth knowing
- Doors may not swing into the required fixture clearance except in single-user rooms with clear floor space beyond the door swing (§603.2.3).
- Flush controls go on the open side of the toilet, max 44 in. high (§604.6).
- Accessible stalls in multi-user restrooms are 60 in. wide minimum; ambulatory stalls (35–37 in.) are also required at 6+ fixtures (§604.8).
- Employee-only and residential facilities have modified rules — verify scope with your designer or AHJ.
Source: 2010 ADA Standards for Accessible Design (U.S. Department of Justice, public domain) — read the full standard at ada.gov. Your local building code (and ICC A117.1 where adopted) applies in addition — find it on your jurisdiction page.