Division VII — Drainage Facilities

62STORMWATER TREATMENT

CA · 2024 Standard SpecificationsBook pages 959963View official source ↗

62 STORMWATER TREATMENT

62-1 General

62-1.01 General

62-1.01A Summary

Section 62 -1 includes general specifications for constructing permanent stormwater treatment best management practices. Earthwork must comply with section 19. Concrete and joint seals must comply with section 51. Sealant must comply with section 41 -5. Reinforcement must comply with section 52. Underdrain must comply with section 68 -2. Miscellaneous metal must comply with section 75. Cable railing must comply with section 83 -2.07.

62-1.01B Definitions

Reserved 62-1.01C Submittals At least 5 business days before placing permeable material, submit a certificate of compliance for the gradation of the material from the source. No more than 5 business days after placing permeable material, submit:

1.At least one ASTM D6913 test on permeable mater ial sampled at: 1.1. Job site 1.2. Authorized location
2.Verification that the permeable materials testing results meet the gradation requirements

62-1.01D Quality Assurance

Submit verification that the placed material complies with the gradation for th e Class 4 and Class 5 permeable materials. Submit verification of the uniformity coefficient for Class 5 permeable material. For Department acceptance, the depth of the permeable material will be measured after the in -place washing is complete.

62-1.02 Ma Terials

62-1.02A General

Reserved

62-1.02B Class 4 Permeable Material

Class 4 permeable material must consist of sand, gravel, or crushed stone that is hard, durable, and clean. The material must be free from organic material, clay balls, or other delete rious substances. The percentage composition by weight of Class 4 permeable material in place must comply with the gradation requirements shown in the following table: SECTION 62 STORMWATER TREATMENT Class 4 Permeable Material Gradation Requirements Sieve size Percentage passing 2" 100 1-1/2" 95–100 3/4" 50–100 3/8" 15–55 No. 4 0–25 No. 8 0–5 No. 100 0 Class 4 permeable material must have a durability index of not less than 40.

62-1.02C Class 5 Permeable Material

Reserved

62-1.02D Miscellaneous Metal

Fabricate the parts shown in the table below from the corresponding materials shown: Miscellaneous Metal Parts Part Material Ladders Steel Handrails Steel Trash screen Steel Components of riser support brackets Stainless steel complying with ASTM A276, Grade 304 CIP inserts must be ferrule loop type

62-1.02E Filter Fabric

Class D filter fabric must comply with the requirements shown in the following table: Class D Filter Fabric Quality characteristic Test method Requirement Permittivity (min and max, sec -1) ASTM D4491 1.6–1.8 Apparent opening size, average roll value (min and max, US standard sieve size) ASTM D4751 60–80 Grab breaking load, 1 -inch grip, in each direction (min, lb) ASTM D4632 120 Apparent elongation, in each direction (min, %) ASTM D4632 50 UV resistance, retained grab breaking load, 500 hours (min, %) ASTM D4355 70

62-1.02F 62-1.02I Reserved

62-1.03 Construction

62-1.03A General

Placing filter fabric must comply with section 68 -1.03B.

62-1.03B Permeable Material

62-1.03B(1) General

Before placement, wash Class 4 and Class 5 permeable materials:

1.To remove silt and clay particles
2.With potable water equal to at least 4 times the volume of the material being placed After placement, wash Class 4 and Class 5 per meable materials:
1.With potable water
2.Until the discharged water has a turbidity reading of: 2.1. 30 NTU or less for a project within the Tahoe Hydrologic Unit 2.2. 200 NTU or less for a project outside the Tahoe Hydrologic Unit SECTION 62 STORMWATER TREATMENT Capture the wash wate r. Handle the wash water by any of the following means:
1.Dispose of
2.Use as dust control
3.Disperse onsite in an authorized location other than the BMP

62-1.03B(2) Class 5 Permeable Material

Place Class 5 permeable material:

1.In a way that does no t damage or displace the filter fabric
2.Using methods that produce a finished surface as shown

62-1.03C 62-1.03H Reserved

62-1.04 Payment

Not Used

62-2 Design Pollution Prevention Infiltration Area

Reserved

62-3 Infiltration Trench

62-3.01 General

62-3.01A Summary

Section 62 -3 includes specifications for constructing infiltration trenches. Concrete curb must comply with section 73.

62-3.01B Definitions

Reserved

62-3.01C Submittals

At least 5 business days before placing permeable material , submit a certificate of compliance for the gradation of the material from the source.

62-3.01D Quality Assurance

Reserved

62-3.02 Materials

62-3.02A General

Filter fabric must be Class D.

62-3.02B Surface Gravel

Surface gravel must be Class 1, Type A permeable material under section 68 -2.02F.

62-3.02C Trench Filler Material

Trench filler material must be Class 6 permeable material and must consist of rock or high porosity backfill material. Rock must be non -crushed, pre -washed, clean, hard, sound, du rable, and uniform in quality. Rock must be free of detrimental quantity of soft, friable, thick elongated or laminated pieces, organic material, clay balls, oil, alkali, or other deleterious substances. The percentage composition by weight of Class 6 perm eable material in place must comply with the gradation requirements shown in the following table: SECTION 62 STORMWATER TREATMENT Class 6 Permeable Material Gradation Requirements Sieve size Percentage passing 4" 100 3" 75 2" 8 1.5" 2 Class 6 permeable material must have a minimum durability index of not less than 40.

62-3.02D Observation Well

PVC pipe for the observation well must be perforated, have a smooth wall, and comply with AASHTO M278. PVC matted end cap and vented well cap must comply with AASHTO M278. Concrete mu st be minor concrete. Pull box must comply with section 86 -1.02C, except an electronic m arker is not required. The cover marking must be OBSERVATION WELL .

62-3.02E Alternative Trench Filler Material

Reserved

62-3.03 Construction

62-3.03A General

Place filter fabric under section 68 -1.03B.

62-3.03B Observation Well

The only joint allowed in the pipe in the observation well is between the perforated and solid wall pipe sections. Place the observation well pipe vertically. No permeable material, san d, or other material must be inside the well pipe.

62-3.04 Payment

Not Used

62-4 Infiltration Basin

Reserved

62-5 Infiltration Gallery

Reserved

62-6 Reserved

62-7 Bioretention

Reserved

62-8 Detention Basin

Reserved

62-9 Austin Earth Berm

Reserved

62-10 Austin Vault Sand Filter

Reserved

62-11 Delaware Sand Filter

Reserved SECTION 62 STORMWATER TREATMENT

62-12 Gross Solids Removal Device

62-12.01 General

Section 62 -12 includes specifications for constructing gross solids removal devices.

62-12.02 Materials

62-12.02A General

Anchorages must comply with the specifications for concrete anchorage devices in section 75 -3.02C.

62-12.02B Miscellaneous Metal

Fasteners used to connect grates and screen to the frame must be vandal resistant. Stainless steel wedge -wire screens, plates, and bars must comply with ASTM A240/ A240M, Type 304, with a no. 2B finish. Finished screens must be descaled by immersion in a nitric/hydrofluoric acid bath, rinsed, and air dried to achieve passivation. Fasteners, anchorage devices, hardware for the inclined screen and screened pipe must be Type 304 stainless steel . Welding of steel members must comply with AWS D1.1, D1.4, and D1.5. Welding of stainless steel members must comply with AWS D1.6. Before welding, prepare and clean with stainless steel brushes and non -ferrous abrasives. Equipment used in the fabrication of carbon steel must not be used. After welding, the stainless steel surface must be smooth and without waves. Fabricate the parts shown in the table below from the corres ponding materials shown: Miscellaneous Metal Parts Part Material Jet plate Steel Deflector Steel Cleanout Steel or Type 304 stainless steel Chain Steel

62-12.02C Fiberglass Reinforced Plastic Components

Reserved

62-12.02D Inclined Screen

Inclined screen must be s tainless steel wedge wire . The screen slot width must be between 0.17 to 0.20 inch. Stainless steel wedge wire screen must have an open area from 60 to 70 percent of the total screen area .

62-12.02E Screened Pipe

Screened pipe, jo ints, supports, hatches, doors and ancillary hardware must be c onstructed of stainless steel. Screened pipe must comply with ASTM A778, and must be Type 316L . Screened pipe must be 0.25 -inch thick well screen with machine -made evenly spaced louvered openin gs perpendicular to the axis of the casing. Fabricate screened pipe with perforations and louvers as shown . Fabrication tolerances on the screened pipe, joints, hatches, and doors must not exceed 0.20 in ch. Screened pipe sections must be joined after fabri cation. Sections must be numbered using a metal tagging system after compatibility matching, with the tag indicating project location and section number. Section numbering must indicate the placement at each location, with the non -louvered section being labeled as the first section and continuing sequentially until the fi nal section for each location. The metal tags must remain in place after installation .

Source: California Standard Specifications, 2024 Edition. Pages 959963 of 1,372.