924.1General Description
This section includes the requirements for the following miscellaneous electrical materials: • Ground rods—924.2.01 • Pull and Junction Boxes—924.2.02 • Breakaway Bases—924.2.03 • Fuses and fuse holders—924.2.04 • Surge Protective Devices and Lightning Arrestors—924.2.05 • Circuit breakers—924.2.06 • Photoelectric controls—924.2.07 • Magnetic contactors—924.2.08 • Service Entrance Caps (Weatherheads)—924.2.09 • Transformers—924.2.10 • Enclosures—924.2.11 • Service Disconnect Switch—924.2.12 924.1.01 Related References
General Provisions 101 through 150.
ASTM F883-13, Standard Performance Specification for Padlocks ASTM C857-16, Standard Practice for Minimum Structural Design Loading for Underground Precast Concrete Utility Structures ANSI C136.10, Locking-Type Photocontrol Devices and Mating Receptacles—Physical and Electrical Interchangeability and Testing ANSI/IEEE C62.41.2, Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits ANSI/SCTE 77 2017, Specifications for Underground Enclosure Integrity IEC EN 62561-2, Lightning Protection System Components IEEE C62.1-1989, Standard for Gapped Silicon-Carbide Surge Arresters for AC Power Circuits NEC Article 110.28 NEC Article 314.28, Pull and Junction Boxes and Conduit Bodies 1790
Underwriter’s Laboratories (UL) Standards: UL 50, Standard for Enclosures for Electrical Equipment UL 98, Enclosed and Dead-Front Switches UL 248-4, Standard for Safety Low-Voltage Fuses – Part 4: Class CC Fuses UL 489, Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures UL 467, Standard for Grounding and Bonding Equipment UL 508, Standard for Industrial Control Equipment UL 514B, Conduit, Tubing, and Cable Fittings UL 773, Standard for Plug-In Locking Type Photocontrols for Use with Area Lighting UL 1066, Standard for Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures UL 1332, Standard for Organic Coatings for Steel Enclosures for Outdoor Use Electrical Equipment UL 1449, Standard for Surge Protective Devices UL 2416, Standard for Audio/Video, Information and Communication Technology Equipment Cabinet, Enclosure and Rack Systems UL 5085-1, Low Voltage Transformers - Part 1: General Requirements
924.2Materials
Ensure that all electrical materials are approved by the Underwriter’s Laboratory or other acceptable testing agency. 924.2.01 Ground Rods
otherwise shown in the Contract.
UL 467. Complies with IEC EN 62561-2
exposed end.
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150. 1791
924.2.02 Pull and Junction Boxes
capacity of the box’s internal capacity in accordance to NEC 314.28(A).
cable. Splicing of service or branch circuit cable within pull boxes is not allowed.
type, conduit type or other transition. Proper splicing within above grade junction boxes is permitted.
Contract.
AASHTO H-15 loading requirements, including the lid. For installations where heavy truck traffic is expected, AASHTO H-20 load rating shall be used.
Design Loading for Underground Precast Concrete Utility Structures, ASTM International, West Conshohocken, PA, 2016, www.astm.org. Boxes shall have the minimum rating specified in the Contract.
15 loading requirements. For installations where heavy truck traffic is expected, AASHTO H-20 load rating shall be used.
STANDARD--Specifications for Underground Enclosure Integrity
loading requirements. For installations where heavy truck traffic is expected, AASHTO H-20 load rating shall be used.
shall comply with NEC Article 314.28, Pull and Junction Boxes and Conduit Bodies.
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150. 1792
924.2.03 Breakaway Bases
intended to be utilized on traffic signal, camera, ATMS or other poles that have electrical equipment.
See Section 924.2.4.
application in which it is used, and the manufacturer must furnish a letter of eligibility for the device from the FHWA.
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150 924.2.04 Fuses and Fuse Holders
the type UL Class CC or as required. Each section shall be permanently marked with line and load side designations and the unit shall have a water and vapor-tight seal rated IP67when the sections are joined. Two- pole fuse holders with setscrew terminals shall be used unless otherwise specified.
suitable for contacts as approved by the Engineer. The contacts shall be spring loaded or tulip style to exert contact pressure on mating parts. Fuse holders shall be rated for 30 A at 600 V at 167 °F (75 °C) operation.
attach to the fuse holder by a crimping operation, except that connection of No. 2 wires to breakaway fuse holder receptacles may be via a set screw connection. Each fuse holder shall be of a size proper for the wires to be attached. The assembly shall be provided with insulating boots as needed.
the same time. Phase to neutral circuit applications shall be designed so that both phase and neutral conductors are disconnected at the same time. Blanks shall be used instead of fuses for the neutral conductor and they shall be clearly marked with white bands to designate a neutral plug.
pole knockdown. The fuse shall remain enclosed in the de-energized portion of the fuse holder upon disconnection. The fuse shall not be utilized as the disconnection means. Break-away style must readily disconnect from power in case of a pole knockdown and shall be compliant with AASHTO breakaway quick disconnect requirements. The breakaway feature shall consist of a receptacle permanently attached to the power line and a fuse holder with matching terminals. If a knockdown occurs, the parts shall separate, leaving the energized conductor recessed and unexposed. 1793
long x 13/32 in. dia. (38 mm x 10 mm), cylindrical fuses of the time-delay type. The fuses shall be rated for 600 V AC, Type FNQ time-delay fuses and meet the requirements of UL Standard 248-4. The fuses shall have a UL listed interrupting rating of not less than 10,000 rms symmetrical amperes at rated voltage. They shall be sized at 300 percent of the starting or operating current whichever is greater, but in no case greater than 50 percent of the branch circuit conductor ampacity.
General Provisions 101 through 150.
General Provisions 101 through 150. 924.2.05 Surge Protective Devices and Lightning Arrestors Lightning Arrestors shall be located in the Controller Cabinet when the application calls for equipment to be powered from the secondary side of a step-down transformer. Each Luminaire shall have an internal primary lightning arrestor or surge protective device. See below for details.
accordance with ANSI/IEEE C62.41.2 guidelines.
maximum case temperature rating.
8/20 μSec waveform and repetitive surges of 200 amperes for a minimum of 10,000 occurrences.
provided in the LED driver used in the luminaire, and a maximum continuous over voltage (MCOV) rating of at least 550V.
indicate proper function and protection for each line.
the inability of the device to provide its rated surge protection to the luminaire. 1794
gap structure and silicon carbide valve blocks.
ungrounded secondary services. The arrestors shall meet all applicable ANSI, NEMA, IEEE, and OSHA
standards, Such as IEEE C62.1-1989 Standard for Gapped Silicon-Carbide Surge Arresters for
AC Power Circuits.
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150.
924.2.06 Circuit Breakers
manually-operated molded-case type with frame size, number of poles, current trip ratings and enclosures
as shown in the Contract.
rated circuit voltage.
pole breakers shall have trip elements on each pole connected to a common trip bar. The circuit breakers
shall be trip-free from the handle on overloads and short circuits. Automatic tripping shall be clearly
indicated by the handle position. The breakers shall be treated to resist fungus Circuit breakers shall
conform to adjacent breakers, be NRTL listed per UL 1066, conform to NEMA Standard AB 1, and meet
Federal Specifications W-C-375b.
circuit breakers.
indicated in the lighting system wiring diagram whichever is greater plus two spare circuit breakers.
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150. 1795
924.2.07 Photoelectric Controls
delay response to preclude nuisance tripping due to stray light.
for 1,000 watts minimum load.
remain energized in the event the photo control components become inoperative.
Manufacturer and maximum tolerances of ± 20% for the specified values shall be acceptable.
impact resistant plastic weatherproof housing. A locking type receptacle mounted in an impact resistant
housing with ¾ in. pipe thread suitable for conduit mounting shall be provided for installation as indicated on
the Standard Drawings or the Contract. Receptacles shall be impact resistant and withstand the impact of the
luminaire being dropped from a 3-foot height and the receptacle striking a concrete surface. It shall operate
on a supply voltage of 105-130 volts, 60 Hz AC, with an inrush rating of 120 amperes at 120 volts and be
NRTL listed to UL 773.
Withstand an ambient temperature range of–65° to 158° F (–54° to 70° C)
3-1/4 in. (85 mm)
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150. 1796
924.2.08 Magnetic Contactors
a lockable NEMA type 4x enclosure (per NEMA 250) as shown in the Contract or in the Standard Drawings.
The contactors shall meet the requirements of Underwriters’ Laboratories Standard UL 508.
shall be obtained without the use of hooks, latches or semi-permanent magnets.
shall be self-aligning and renewable from the front of the panel. Terminals shall be pressure wire connectors.
the control circuit. The control solenoid and circuit shall be fused and wired for operation from a separate
120V, AC supply source unless otherwise specified. One set of spare contacts and 2 sets of spare fuses shall
be provided with each contactor.
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150.
924.2.09 Service Entrance Caps (Weatherheads)
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150 1797
924.2.10 Transformers
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150.
924.2.11 Enclosures
with all hardware of the same or higher grade
to accommodate future requirements.
scale and imperfections
gasket installed
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 15
924.2.12 Service Disconnect Switch
rating specified in the Contract.
specified. Switch may be installed separately or with a magnetic contactor. 1798
switch shall have an external lockable handle and shall provide for locking in either the “On” or “Off” positions.
Padlocks shall be included and shall be certified to ASTM F883-13 Grade 6 and comply with relevant safety
and security standards.
General Provisions 101 through 150.
General Provisions 101 through 150.
General Provisions 101 through 150.. 1799