3245.1SCOPE

Provide thermoplastic (TP) pipe and fittings for use as pipe sewers or subsurface drains.

3245.2REQUIREMENTS

Provide thermoplastic pipe and fittings meeting the requirements of the Contract. If pipe is not specified in the Contract, provide one of the following pipes listed below meeting the applicable application. For example, use perforated pipe for drainage application and unperforated pipe for outletting. If perforated pipe is specified, provide pipe with perforations in accordance with the applicable Specification. Unless otherwise specified, the Contractor may choose the joint type. Create perforations at manufacture’s plant; no field perforations are allowed.

(1)AASHTO M 278 Standard Specification for Class PS 46, Poly(Vinyl Chloride) (PVC) Pipe

(perforated and unperforated)

(2)ASTM D3034, Standard Specification for Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe

and Fittings, SDR 35, (unperforated only)

(3)ASTM F758, Standard Specification for Type PSM Poly(Vinyl Chloride) Type PS 46

(perforated and unperforated)

(4)ASTM F949, Standard Specification for Poly(Vinyl Chloride) (PVC) Corrugated Sewer Pipe

With a Smooth Interior and Fittings, (perforated and unperforated)

(5)ASTM D1785, Standard Specification for Poly(Vinyl Chloride (PVC) Plastic Pipe, Schedule

40 pipe perforated & unperforated as applicable with one of the following:

(a)Perforated: Slotted with maximum slot width of 1/16 inch and minimum slot

area of 1.5 inches squared/linear foot for pipe 4 inches in diameter and greater and 1.0 inches squared/linear foot for pipe less than 4 inches in diameter

(b)Perforated: Circular holes with 2 to 4 rows of holes. Hole diameter = 3/16 inch -

3/8 inch, and minimum area of holes 1.5 inches squared/linear foot for pipe 4 inches in diameter and greater and 1.0 inches squared/linear foot for pipe less than 4 inches in diameter

(c)Unperforated
(6)AASHTO M 252 Standard Specification for Corrugated Polyethylene Drainage Pipe, (CP)

dual-wall, Type “S” (unperforated) or “SP” (perforated) pipe, PS 50

3245.3SAMPLING AND TESTING

Submit to the Engineer a manufacturer’s Certificate of Compliance with each pipe shipment.