SECTION 682 - ELECTRICAL DISTRIBUTION SYSTEM
682.01 Description. In additional to the requirements set forth in Section 681, the
electrical distribution system generally cons ists of the secondary electrical service, grounding and bonding system, secondary distribution and secondary power controller. The secondary electrical service shall be 480 volts, 1 phase, 3-wire, 60 HZ, unless indicated otherwise on the plans. The overhead service entrance shall have five (5) feet of tail-wire extension from the service entrance cap for connection to the Utility Company's overhead transformer service facilities. An underground service entrance shall consist of conduit and wire placed, after coordination with the serving utility, in a manner to connect the secondary power controller with the ground mounted transformer. The system will be metered as per serving utility company's requirements. Bonding and grounding of all electrical service equipment enclosures and ground terminals shall be as shown on the plans and/or in accordance with Article 250 of the National Electrical Code. The secondary distribution shall consist of furnishing, installing, erecting and laying electrical branch circuits. All branch circuits shall be buried underground except where shown otherwise on the plans. Branch circuits shall consist of conduit, conductors, connectors, and all hardware necessary to complete the work. Pull boxes and junction boxes may be both underground and/or structure mounted. The secondary power controller shall consist of a lighting controller for control of roadway lighting, enclosure, conduit with fittings, wire, devices, ground rods, photocell, and miscellaneous hardware. The controller shall have a dead front behind outer doors with only breaker handles, hand-off automatic sel ector switch and receptacle exposed. All controllers shall be labeled with a phenolic engraved label having 1/4-inch white letters on a black background. Example: "SPC#l".
682.02 Materials.
682.02.1 Secondary Distribution. The materials used in this construction shall meet the
requirements of Subsection 723.02.
682.02.2 Secondary Power Controller . The materials used in this construction shall
meet the requirements of Subsection 723.03.
682.03 Construction Requirements.
682.03.1 Grounding and Bonding System. Where conduit enters an enclosure, a
bonding type bushing shall be used on all conduits with #6 AWG copper bonding conductors bonded to all conduits thence to equipment enclosure or ground bus. The green equipment grounding terminal of all grounding type equipment shall be bonded to its equipment ground conductor with a properly sized green bonding conductor. One (1) green equipment grounding conductor shall be pulled into all raceways, sized the same as the branch circuit conductors, or as noted on the plans. This conductor shall be bonded to box ground terminals, pole ground terminal, ground bus of panel, cabinet, enclosures, and/or ground electrodes shown on the plans.
682.03.2 Secondary Distribution. All trenching shall be performed by mechanical
means and all sides shall be straight and vertical. Width of trenches shall not exceed eight
682.03.3 Pull Boxes and Junction Boxes. Pull boxes and junction boxes shall be
installed in accordance with the plans. The location of the boxes may be adjusted to accommodate field conditions with the approval of the Engineer. When specified, pads around pull and junction boxes may be required.
682.03.4 Secondary Power Controller. The secondary power control unit shall be
installed in accordance with the plans and sh all present a neat and workmanlike finished appearance. The Contractor shall cooperate with utility in completion of unit.
682.04 Method of Measurement.
682.04.1 Secondary Distribution. Branch circuits shall be measured by the linear foot.
The measurement being computed as follows: Jacked or Bored - Horizontally along the length of the jacked section of conduit. Underground - Horizontally along the trench lengths. Structure mounted branch circuit - horizontally or vertically along the length of the sections of conduit installed. No extra length will be allowed for risers to lighting assemblies or secondary power controllers. The terminals for measurement of lengths will be considered specifically as the center of lighting assemblies, power controllers, and junction boxes. Payment for branch circuit connectors, tape, etc. shall be included in payment allowed for the total length of branch circuits. Hardware, fittings, support devices, excavation, sod, backfill, seeding and other incidentals will not be measured for separate payment, but shall be included in the contract unit price per linear foot for branch circuits. Pull boxes and junction boxes will be measured as a unit quantity per each as detailed on the plans.
682.04.2 Secondary Power Controller. Secondary power controllers complete in place
will be measured as unit quantities per each, which shall include all items necessary to complete the installation.
682.05 Basis of Payment.
682.05.1 Secondary Distribution. Branch circuits of the type specified, measured as
prescribed above, will be paid for at contract unit price per linear foot, which price shall be full compensation for furnishing, installing, connecting, excavating, trenching, backfilling