A.General. Provide a level, fully insulated, and weather tight building Equip the exterior doors with a working latch and a hasp that is capable of receiving a padlock. Provide a laboratory that has the following:
1.A minimum of six screened windows on two or more sides, with a minimum of one window in each room. Windows shall have a minimum area of 4 square feet;
2.A constant source of electricity;
3.A minimum of 6 convenience outlets spaced throughout the building;
4.Sufficient light fixtures to uniformly light the interior;
5.A constant potable water supply with a minimum pressure of 5 psi or a minimum head of 12 feet when a gravity tank is used;
6.A faucet and sink. The sink shall drain to the exterior and away from the laboratory;
7.A heating system capable of maintaining a minimum temperature of 70°F;
8.An air conditioning system capable of maintaining a temperature below 80°F;
9.An operable portable fire extinguisher capable of controlling Class A, B, and C fires in each room of the laboratory;
10.Entry steps with a 4 feet x 4 feet landing that meet the following: − A non-slip surface; − Securely fastened to the building; − Position the landing so a person carrying a load can stand on the platform and safely enter the laboratory; and − A safety railing.
11.Workbenches shall be: − Sturdy; − A minimum of 24 inches deep; and − 36 inches to 42 inches above the floor.
12.A Microwave with a minimum of 900 Watts of power, 1 cubic foot of interior space, and a removable glass tray;
13.30 inch range with an oven capable of maintaining a temperature between 221°F and 239°F;
15.A table or desk. Furnish Aggregate and Bituminous labs with DSL broadband internet and a router that broadcasts Wi -Fi and will allow for hard wiring of a computer. The building and fixtures remain the property of the Contractor after the work is completed. 326 B. Aggregate Laboratory. Place the laboratory at a location acceptable to the Engineer. The Engineer will have the full control and the exclusive use of the laboratory. Provide a laboratory with a minimum floor area of 230 square feet, minimum exterior width of 8 feet, and a minimum ceiling height of 7 feet. Partition the building into a minimum of two rooms, a smaller room having a floor area of approximately 70 square feet. Provide a workbench with a length of 7 feet in the smaller room: Provide the following equi pment in the larger room:
1.Mechanical shaker capable of receiving 6 trays that have a screen size of 14 inches by 14 inches and the following compatible sieves: − 1-1/2 inch; − 1-1/4 inch; − 1 inch; − 3/4 inch; − 1/2 inch; − 3/8 inch; − No. 4; and − An enclosed dust pan.
2.Mary Ann shaker capable of being adjusted to receive 8 and 12 inch diameter sieves;
3.Splitter with a maximum hopper capacity of 0.6 cubic feet;
4.Splitter with a minimum hopper capacity of 1.0 cubic feet; and
5.An exhaust fan capable of changing the air in the room every minute.
C.Bituminous Laboratory. Place the laboratory at the plant site near the Contractor’s laboratory and where plant operations will not interfere with the laboratory equipment. The Engineer will have the full control and the exclusive use of the laboratory. Provide the following items:
1.Mary Ann shaker capable of being adjusted to receive 8 and 12 inch diameter sieves.
2.Splitter with a maximum hopper capacity of 0.6 cubic feet.
3.Splitter with a minimum hopper capaci ty of 1.0 cubic feet.
4.A water bath that holds a minimum of 5 gallons. Equip the water bath with thermostatic controls capable of maintaining a water temperature between 76°F and 78°F. Equip the water bath with an overflow system to maintain a uniform water level and a recirculation system with on/off controls.
5.An orbital shaker with: − An orbit size of 0.75 in and a stirring speed range between 40 and 400 RPM; − A top plate large enough to accommodate two 2,000 milliliter filtering flasks; and − Two clamps to hold flasks in place.
6.A vacuum pump capable of evacuating air from a 2000 milliliter filtering flask to a residual pressure of 30 millimeters mercury (4.0 kilopascals).
7.A vacuum gauge capable of measuring a minimum pressure of 30 millimeters mercury (4.0 kilopascals). 327 8. A forced draft oven with an interior capacity of 6 cubic feet and that is capable of maintaining a temperature between 320°F and 330°F.
9.An insulated container to transport bituminous mix from the paver to the laboratory. Provide a container large enough to hold 22 pounds of mix that will be in other containers.