Effective with the December 2018 Letting 481 2019 Standard Spec ifications Section 656 Electrical Service
656.1Description
656.2Materials
656.2.1 General
affidavit certifying that the service conforms to the WSEC and then verbally notify the engineer that the utility received the wiring affidavit.
clad grounding electrodes. Furni sh the number and length of gro unding electrodes as required to install the service conforming to the WSEC and the local utilit y.
of the manual bypass meter socket.
incidental to the electrical service bid item. 656.2.2 Meter Socket Service
AIC circuit breakers unless the local utility requires otherwis e, grounding electrodes and connections, conduit and fittings, and necessary conductors and equipment re quired by the WSEC and the utility for a service connection. Use circuit breakers with an amperage cap acity of 50 A, unless specified otherwise in the contract. 656.2.3 Meter Breaker Pedestal Service
unless the local utility requires otherwise, grounding electrodes and connections, conduit and fittings, and necessary conductors and equi pment required by the WSEC and the utility for a service connection. Use circuit breakers with an amperage capacity 50 A , unless specified otherwise in the contract. When the meter breaker pedestal is energized, install an engineer-approved meter seal at access points on the meter trough. 656.2.4 Unmetered Service
656.2.5 Main Lugs Only Meter Pedestal Service
fittings, and necessary conductors and equipment required by the WSEC and the utility for a service connection. Provide a lug amper age capacity, and the number of phases, and service voltage rating as the plans show. 656.2.6 Breaker Disconnect Box Service
single circuit breaker (22, 000 AIC or larger as required by po wer companies), conduit fittings, grounding electrodes, and conne ctions and necessary conductors and equipment required to provide power to the cabinet.
656.3Construction 656.3.1 General
affidavit, certifying that the se rvice was installed conforming to the WSEC.
656.3.2 Service Lateral
service lateral, unless specified otherwise in the contract doc uments. Arrange and assume responsibility for the timely i nstallation of the service lateral by the utility. Terminate the lateral at a meter socket, meter breaker pedes tal, a NEMA 3R Breaker Enclosu re, or a main lugs only meter pedestal, as the plans show. 656.3.3 Meter Socket Service
the termination point. Run a gr ounding conductor, from groundin g electrode to grounding electrode if
Effective with the December 2018 Letting 482 2019 Standard Spec ifications more than one is required. Then , connect to the meter socket an d terminate at the grounding lug in the NEMA 3R Breaker Enclosure. Provi de connections and wiring to pr ovide 120 volt AC power, or as the plans show, to the circuit breakers in the cabinets. If only on e grounding electrode is required, exothermically weld the stranded copper wire to it and then con nect to the grounding lug in the NEMA 3R Breaker Enclosure.
3R Breaker Enclosure to an equipment grounding bus mounted in t he control cabinet.
from a separate circuit breaker. U se a common trip breaker rate d at 15 amps or more. 656.3.4 Meter Breaker Pedestal Service
concrete base and near the electrical service meter breaker pedestal. Run a grounding conductor, from grounding electrode to grounding electrode if more than on e is required. Then, terminate at the grounding lug in the meter breaker pedestal. Provide connections and wiring to provide 120 volt AC power, or as the plans show, to t he circuit breakers in the cab inet. If only one grounding electrode is required, exothermically weld the stranded copper wire to it an d then connect to the grounding lug in the meter breaker pedestal.
grounding lug in the meter breaker pedestal to an equipment grounding bus mounted in the control cabinet.
from a separate circuit breaker . Use a common trip breaker for 240 volt AC installations. Size the breaker conforming to code requi rements, 15 amp, minimum. 656.3.5 Unmetered Service
656.3.6 Main Lugs Only Meter Pedestal Service
656.3.7 Breaker Disconnect Box Service
the bus located within the breaker disconnect box.
breaker pedestal to the 50 amp single circuit breaker within th e breaker disconnect box and then to the circuit breaker in the control cabinet.
656.4Measurement
acceptably completed.
656.5Payment
items: ITEM NUMBER DESCRIPTION UNIT
656.0100 Electrical Service Meter Socket (location) LS
656.0200 Electrical Service Meter Breaker Pedestal (location) LS
656.0300 Electrical Service Unmetered (location) LS
656.0400 Electrical Service Main Lugs Only Meter Pedestal (location) LS
656.0500 Electrical Service Breaker Disconnect Box (location) LS
for manual bypass meter socke t, NEMA 3R breaker enclosure, cond uit and fittings, circuit breakers, grounding electrodes and connections.
including the meter breaker pedestal, manual bypass meter socke t, conduit and fittings, circuit breakers, grounding electrodes and connections.
Effective with the December 2018 Letting 483 2019 Standard Spec ifications (4) Payment for Electrical Service Unmetered is full compensation for providing materials including the NEMA 3R breaker enclosure, co nduit and fittings, circuit breake rs, grounding electrodes and connections.
materials including the main lugs only meter pedestal, disconne ct, manual bypass meter socket, grounding electrodes and connections.
including the breaker box, circu it breakers, 10 AWG wire, groun ding electrodes, cadwelding, conduit, fittings, wiring, connections, grounding electrodes and connections; for excavating, bedding, backfilling, and restoration of g round to original condition in cluding any sand, concrete, or other required materials; for disposing of surplus materials.
If the electrical utility bills the contractor directly, pay th e utility promptly. The department will reimburse the contractor for invoice costs under the Electrical Service L ateral administrative item.
Effective with the December 2018 Letting 484 2019 Standard Spec ifications Section 657 Poles, Arms, Standards, and Bases
657.1Description
657.2Materials
Revise 657.2 to require contractor furnished monotube poles and arms. 657.2.1 Poles 657.2.1.1 General
compliance certifying that the poles incorporated into the work conform to the specified design criteria and other contract requirements.
directly opposite the hand hole on the in side wall of the pole.
stamped under the hand-hole bef ore galvanizing steel poles.
to ensure they are free of loose rust and mill scale, dirt, oil or grease, and other contaminants before zinc coating. Zinc coat as specified in 641.2.8 . Ensure that the coating is tight, free from rough areas or slag, and presents a uniform appearance. Clean after manufac turing is complete to remove loose and foreign material.
657.2.1.2 Monotube Poles
of AASHTO design specifications and fatigue category the plans show. 657.2.1.3 Type 2 and 3 Poles
for Structural Supports for High way Signs, Luminaires, and Traffic Signals as published in the 1994, - A wind speed of 80 mph with a 1.3 gust factor. - Dead and live load related to a 25-foot trombone mast arm wit h 5-section signal head and a pair of twin 15-foot luminaire arms mounted on the pole as the plans show. 657.2.1.4 Other Pole Types
plan details show and to AASHTO Standard Specifications for Str uctural Supports for Highway Signs, Luminaires and Traffic Signals, 6th Edition, and Interim Revisi ons. Use a design life of 50 years. Design to withstand a 3 second gu st wind speed of 90 mph. Do no t use the alternative method for wind pressures described in appe ndix C of those AASHTO standard specifications. No fatigue analysis is required.
centerline of the shaft is vertical. Ensure that lighting poles nominally 40 feet or less in length are made of one piece and round in cross-section.
657.2.2 Monotube Arms
of AASHTO design specifications and fatigue category the plans show.
certificate of compliance cert ifying that the arms incorporated into the work conform to the specified design criteria and other contract requirements.
arm to a pole as the plans show.
adequate strength to resist side loads.
required.