Effective with the December 2018 Letting 435 2019 Standard Spec ifications Section 641 Sign Bridges and Overhead Sign Supports
641.1Description
641.2Materials
641.2.1 General
641.2.2 Steel Bolts 641.2.2.1 High-Strength Bolts
as follows: - Use the size, number, type, and configuration of hardened fla t washers the DTI manufacturer recommends for bolt diameters greater than 1 1/8 inches. - Ensure that the supplier pre-assembles each bolt/nut/washer a ssembly before shipping. - Ensure that bolt/nut/washer assemblies are accompanied by a certified report of test o r analysis giving the results of the supplier's rotati onal-capacity testing. No field rotational-capacity testing is required. - Ensure that bolt/nut/washer assemblies are shipped in sealed and labeled containers. - Furnish 3 or more additional bolt/nut/washer assemblies of ea ch rotational-capacity lo t for pre-installation testing. - Submit 2 or more additional bo lts and 3 or more additional nu ts and washers from each lot and heat for department mechanical testing. T he contractor need not submit c omponents from a lot and heat the department previously approved. 641.2.2.2 Direct Tension Indicating Washers
Ensure that DTIs have identifyi ng marks applied by the manufacturer. Provide the engineer with 2 copies of the DTI manufacturer's instructions showing acceptable installation configurations. Provide 3 or more additional DTIs as required for pre-installation testin g. Also provide the engineer with at least two 0.005-inch metal feeler gauges. 641.2.2.3 Anchor Rods
ASTM A563 heavy hex nuts, and ASTM F436 washers all hot-dip galvanized according to ASTM A153, class C, supplemented by ASTM F2329. Over-tap galvanized nuts according to ASTM F2329.
the rods after coating the thre ads and nuts with a wax-based lu bricant. 641.2.3 Grating
641.2.4 Pipe
641.2.5 Steel Chain
accessories the plans show. 641.2.6 Certification
pipes, anchor rods, high-strength bolts, nuts, and washers, and structural sections. The engineer must approve the material before the c ontractor may install in the w ork.
expense to the department. 641.2.7 Aluminum Components
structural shapes for catwal k supports conforming to ASTM B308, alloy 6061-T6. Furnish plate and sheet aluminum conforming to ASTM B209, alloy 6061-T6. Ensure material is free from d iscoloration, nicks, and blemishes.
conforming to 513.2.1 .
Effective with the December 2018 Letting 436 2019 Standard Spec ifications 641.2.8 Steel Sign Bridges
Structural Steel and Mi scellaneous Metals ..................... ............................................................................. 506.2
zinc coating must withstand 8 one-minute dips in the Preece tes t solution, ASTM A239. Revise 641.2.8 to clarify submittal requirements and re quire steel sign bridges from a fabricator on the APL.
APL. Also ensure that the fabricator submits a fabrication progress report on department form DT2334 electronically to the department’s fabrication library. Update this form weekly for each sign bridge in fabrication.
library under 105.2.2 . Certify that shop drawings con form to quality control standar ds by submitting department form DT2326 with each set of shop drawings. 641.2.9 Overhead Sign Supports
specifications and fatigue categor y the plans show in the overh ead sign support layout details. Revise 641.2.9(2) to allow non-tapered poles and arms unl ess the plans show otherwise. This change was implemented in ASP 6 effective with the December 2017 letting.
A123. The contractor may provide either straight or tapered pole and arm shafts unless the plans specify otherwise. Provide bolts and other hardware conforming to 641.2.2 . Revise 641.2.9 to clarify submittal requirements & require overhead sign supports from a fabricator on the APL.
department’s APL. Also ensure that the fabricator submits a fabrication progress report on department form DT2334 electronically to the department’s fabrication library. Update this form weekly for each overhead sign support in fabrication.
to the engineer conforming to 105.2 with electronic submittal to t he fabrication library under 105.2.2 . Certify that shop drawings confor m to quality control standards by submitting department form DT2326 with each set of shop drawings. Provide tightening procedures fo r mast arm or luminaire arm to pole shaft connections on the shop drawings. Hav e a professional eng ineer registered in the state of Wisconsin sign, seal, and date the shop drawings and certify th at the design conforms to AASHTO standards and the contract.
641.3Construction
641.3.1 General 641.3.1.1 Methods
and to 506.3.25 for field inspection. Provide mill inspection a nd test reports conforming to 506.3.21.
specified in 502.3.8.1 . Wait until the concrete has attained 3500 psi compressive str ength or 7 equivalent days as specified in 502.3.10 before erecting any portion of the structure on the footing. 641.3.1.2 High-Strength Bolts 641.3.1.2.1 Handling and Storage
from dirt and moisture until us ed. Maintain fastener system components as nearly as possible in the as-manufactured condition until installed. Remove from storage only as needed and pr omptly return unused components to storage. 641.3.1.2.2 Pre-installation Testing
assemblies with DTIs in all the configurations used for installation.
form DT2322 for bolt/nut/washer assemblies of each rotational-capacity lot with DTIs in each
Effective with the December 2018 Letting 437 2019 Standard Spec ifications installation configuration. Provide the engineer with the test results by submitting 2 copies of department form DT2322 . 641.3.1.2.3 Bolt Installation
from the connected materials. Install bolt/nut/washer assemblies with DTI washers in the same configuration used for pre-installation testing.
operation, ensure no rotation o f the part not turned by the wrench. Snug systematically from the most rigid part of the connection to the free edges. Repeat until th e full connection is in a snug condition and the faying surfaces are in firm contact. Systematically tig hten the connection required number of refusals is achieved. If the gaps on the DTI are completely clo sed, discontinue tightening.
QC testing frequency, the engineer may decide to observe QC tes ting at a reduced frequency. The engineer may verify bolt installation by periodically testing w ith a feeler gauge. 641.3.1.3 Anchor Assembly
DT2321 . Complete department form DT2321 for each structure. Indicate t he parties resp onsible for the installation and submit t he form to the engineer for inclusion in the permanent project record. 641.3.1.4 Sign Installation
available, install sign blanks to control vibration. Fasten to the supporting structure conforming to 637.3.3.3 .
the permanent signs.
blanks that are at a minimum 24 inches larger than the truss de pth and project an equal distance beyond the top and bottom chord members.
plan details show. 641.3.2 Steel Sign Bridges 641.3.2.1 General
supports with attachments for signs facing in one direction.
sign supports with attachments for signs facing in opposite dir ections.
supporting structure.
overhead roadway bridges.
641.3.2.2 Welding
1.1, Structural Welding Code - Steel.
welding for repairs in noncritical locations and when a departm ent-approved individual competent to perform inspections is present during the welding. Perform fiel d welding using personnel qualified under AWS D 1.5, Bridge Welding Code.
members subject to tension or str ess reversal by radiographic o r ultrasonic methods over the entire length of the weld. Test other butt welds in these members by t he same methods, except the engineer will determine the length of weld to test. Use either the dye p enetrant method, or the magnetic particle method to test the fillet welds connecting columns to bases and main chord members, including the associated flanges, gussets, or main load carrying brackets or members, and on fillet welds
Effective with the December 2018 Letting 438 2019 Standard Spec ifications connecting flanges to the main truss chord members. Perform the dye penetrant test according to ASTM E165 and perform the magnetic par ticle method according to ASTM E709.
Code - Aluminum. Do not weld aluminum in the field. 641.3.2.3 Fabrication
after completing cutting, punching, drilling, and welding.
and zinc coated in one piece in t he shop, adjust to the proper shape and alignment, and tighten the high-strength bolts to the require d tension. Provide a certificate of compliance certifying that high- strength bolts within truss sections are tensioned conforming t o 506.3.12 . Then, assemble the truss sections that make up any one sign bridge in the shop, and adju st to proper alignment and camber as the plans show. Matchmark all tru ss sections and shims before d isassembling for shipment. 641.3.2.4 Handling and Field Assembly
erection. Paint areas of damaged zinc coating with 2 coats of z inc dust/zinc oxide paint. Clean damaged and adjacent areas by sanding, scraping, chipping, or wire brushing. Apply a profile to the bare metal surface using a needle gun before painting. For areas of damage larger than 10 square inches metalize according to AASHTO M36 or, for field repairs, using an engineer-approved high- temperature application of zinc powder and flux in paste or sti ck form.
641.3.3 Overhead Sign Supports
fabricated from steel. Construct according to the shop drawings .
641.4Measurement
acceptably completed.
overhead sign support acceptably completed.
641.5Payment
items: ITEM NUMBER DESCRIPTION UNIT
641.0100 Sign Bridge Si ngle Pole Sign Supp ort One Sign (structu re) LS
641.0600 Sign Bridge Single PoleS ign Support Two Signs (structure) LS
641.1200 Sign Bridge Cantile vered (structure) LS
641.5100 Sign Bridge Structure Mounted (structure) LS
641.6600 Sign Bridge (structure) LS
641.8100 Overhead Sign Support (structure) LS
assemblies and templates; for high-strength bolt/nut/washer ass emblies and DTIs including those required for testing; and for sign blanks. Concrete footings ar e paid for separately under 636.5 .
structure; for providing the sign support; for excavating and backfilling; for providing concrete footings including reinforcing steel; for providing anchor assemblies an d templates; for high-strength bolt/nut/washer assemblies and DTIs including those required fo r testing; and for sign blanks.
luminaires under 659.5 .
Effective with the December 2018 Letting 439 2019 Standard Spec ifications Section 642 Field Facilities
642.1Description
laboratories as required in the contract at engineer-approved l ocations.
642.2Materials
642.2.1 General
engineer-approved types that are floored, roofed, and weatherpr oofed, and have a minimum ceiling height of 6 feet-9 inches.
necessary fuel to maintain a mini mum temperature of 68 F during the hours occupied.
requirements, in clean and good working condition, and stock wi th sanitary supplies for the duration of the contract.
are readily accessible to proje ct personnel. Check the contents of each kit at least once each week and replenish expended items. Ensure each kit contains, at a mi nimum, a supply of latex or nitrile gloves, CPR masks, adhesive tape , pressure and cling bandages, antiseptic wipes, bite/sting swabs, cold packs, and safety goggles.
materials, provide emergency use facilities capable of flushing the eyes, or drenching the body of an exposed worker with water for 15 minutes.
screens. Securely fasten heavy screening over all windows. Use screening made of No. 2 mesh, 14- gauge or heavier, steel wire clot h, zinc coated after weaving.
padlocks. 642.2.2 Field Office 642.2.2.1 General Revise 642.2.2.1 to require a dditional technology to support in creased remote access & printing needs in the field. This change was implemented in ASP 6 effective with the December 2017 letting.
each room has a separate exteri or door and its own air conditio ner. Locate the office where a quality internet connection can be achieved.
- Two programmable touch-tone phones, one of which is cordless. Ensure that phone operations will not interfere with other telecommunications equipment. - Voice mail service or an answering machine.
connection with a modem/router and capable of supporting cloud enabled file sharing, voice over internet protocol (VoIP), video conferencing, and web based app lications. Ensure that system meets the following: - Includes a wireless netwo rk for the field office. - Can accommodate IPSec based VPN products. - Has a bandwidth range as follows: Field office with 1-5 staff: A minimum connection speed of 5 Mbps download and 1 Mbps upload. If a cable or DSL option is not available the contractor may provide a personal hotspot using cell phone tethering or other device able to achieve the specified mini mum speeds inside the field o ffice. Field office with 6 or more staff: A minimum connection speed of 10 Mbps + 1/2 Mbps per user download and 5 Mbps upload.