Mini-Split Electrical Requirements — MCA, MOCP & Disconnects
Mini-splits are wired differently than most appliances: you don’t size the circuit from a generic table, you size it from two numbers stamped on the unit’s nameplate — Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOCP). Get those two right, add a disconnect within sight of the outdoor unit, and most of Article 440 falls into place.
Worth knowing
- MCA and MOCP often look odd together — an MCA of 19A with an MOCP of 30A is normal. Wire for 19A (12 AWG typically qualifies), breaker at up to 30A. The compressor’s overload protection is inside the unit; the breaker only handles faults.
- GFCI protection for outdoor HVAC outlets has been a moving target: the requirement in 210.8(F) has been delayed by code action for mini-splits and similar equipment until September 1, 2026, and some states amended it out entirely — ask your local inspector what’s enforced.
- The manufacturer-specified interconnect cable (often 14 AWG, 4-conductor stranded) is part of the listing — substituting random cable is a 110.3(B) violation and a common warranty denial.
- Mount the disconnect beside the unit, not behind it — inspectors read “readily accessible” to mean you can reach it without moving the condenser or squeezing behind refrigerant lines.
Sections cite the 2021 International Residential Code and 2023 National Electrical Code as model standards. This is BuildSpec’s own summary — not ICC or NFPA text; read the authoritative language at codes.iccsafe.org. Your state may be on a different edition with amendments — check your jurisdiction page or get an Address Report.