Mini-Split Electrical Requirements — MCA, MOCP & Disconnects
Mini-splits are wired differently than most appliances: you don’t size the circuit from a generic table, you size it from two numbers stamped on the unit’s nameplate — Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOCP). Get those two right, add a disconnect within sight of the outdoor unit, and most of Article 440 falls into place.
Worth knowing
- MCA and MOCP often look odd together — an MCA of 19A with an MOCP of 30A is normal. Wire for 19A (12 AWG typically qualifies), breaker at up to 30A. The compressor’s overload protection is inside the unit; the breaker only handles faults.
- GFCI protection for outdoor HVAC outlets has been a moving target: the requirement in 210.8(F) has been delayed by code action for mini-splits and similar equipment until September 1, 2026, and some states amended it out entirely — ask your local inspector what’s enforced.
- The manufacturer-specified interconnect cable (often 14 AWG, 4-conductor stranded) is part of the listing — substituting random cable is a 110.3(B) violation and a common warranty denial.
- Mount the disconnect beside the unit, not behind it — inspectors read “readily accessible” to mean you can reach it without moving the condenser or squeezing behind refrigerant lines.
Common questions
What does the code say about conductor sizing for Mini-Split Circuits?
Branch-circuit conductors must have an ampacity at least equal to the MCA on the unit’s nameplate — the manufacturer has already done the 125% compressor math for you. (NEC 440.4, 440.32)
What does the code say about breaker/fuse sizing for Mini-Split Circuits?
The overcurrent device must not exceed the nameplate MOCP (sometimes labeled “max fuse/breaker”), and if the nameplate specifies fuses or HACR-type breakers, that requirement is part of the listing. (NEC 440.4(B), 440.22)
What does the code say about disconnect location for Mini-Split Circuits?
A disconnecting means is required within sight of the outdoor unit and readily accessible — a locked breaker across the yard doesn’t qualify. (NEC 440.14)
Adopted edition by state
Base-code year from BuildSpec’s adoption records. States often amend the base code, and your city or county may differ, so confirm with your building department.