Range Hood Venting & Makeup Air — Duct Rules and the 400 CFM Line
Range hood rules come down to three things: the air has to go outside, the duct has to be smooth metal, and if you install a powerful hood, you may have to bring replacement air back in. That last one — makeup air above 400 cfm — is the requirement that surprises the most homeowners shopping for pro-style hoods.
Worth knowing
- The makeup air rule exists to prevent backdrafting: a 900 cfm hood in a tight house can pull combustion gases down the water heater flue. The 2021 IRC narrowed the requirement to homes that actually have atmospherically vented appliances — all-electric and direct-vent homes are off the hook, but check local amendments.
- A hood “capable of” 600 cfm triggers makeup air even if you plan to run it on low — inspectors go by the rating, not your habits.
- Where kitchen local exhaust is required for whole-house ventilation compliance, the minimum is 100 cfm intermittent or 25 cfm continuous (IRC M1505.4.4).
- Over-the-range microwaves follow their listing: most can be vented out or recirculated, but the duct rules above apply the moment you duct one outside.
Sections cite the 2021 International Residential Code and 2023 National Electrical Code as model standards. This is BuildSpec’s own summary — not ICC or NFPA text; read the authoritative language at codes.iccsafe.org. Your state may be on a different edition with amendments — check your jurisdiction page or get an Address Report.