Window and Door Flashing Requirements — Pan, Head & WRB Integration
Flashing is the part of the wall that assumes water will get in. The code doesn’t ask you to make the opening watertight — it asks you to build a path that collects whatever leaks and sends it back outside, which is why the order of the laps matters more than the amount of sealant.
Worth knowing
- Shingle fashion is the whole idea: the sill pan goes on first and laps out over the WRB below, the jamb flashing laps over the pan, the head flashing laps over the jambs, and the WRB above laps over the head flashing. Any lap installed backwards turns the assembly into a funnel.
- A sill pan needs somewhere for water to go. Site-built pans usually get a back dam at the interior edge and end dams at the jambs, and the sill is left unsealed at the bottom so the pan can drain — sealing all four sides of a window is a common and expensive mistake.
- The most frequent failure points inspectors and forensic investigators find are unflashed sills, head flashing tucked under the trim instead of over it, and WRB slit above the opening and taped rather than lapped.
- Self-adhered membranes are temperature- and substrate-sensitive. Cold-weather versions, primers, and roller pressure are all specified by the manufacturer, and a membrane applied outside its listed conditions may not be considered installed per instructions.
- Flashing only works if the drainage plane behind it is continuous — see the housewrap and water-resistive barrier guide (/guides/code/house-wrap) for how the WRB laps, seams, and terminations tie into these details.
Common questions
What does the code say about where flashing is required for Window & Door Flashing?
Approved corrosion-resistant flashing is required at exterior window and door openings, and it has to drain water either to the exterior wall finish or out onto the water-resistive barrier so the wall can shed it. (IRC R703.4)
What does the code say about which method you may use for Window & Door Flashing?
Flashing at openings must follow the fenestration manufacturer’s instructions, the flashing manufacturer’s instructions, details from a registered design professional, or an approved flashing standard — the code lets you pick, but you have to actually follow one of them. (IRC R703.4)
What does the code say about pan flashing at sills for Window & Door Flashing?
A pan flashing is required at the sill of exterior window and door openings, and it must be sealed or sloped so water is directed out to the wall finish or the WRB rather than pooling in the rough opening. (IRC R703.4.1)
Adopted edition by state
Base-code year from BuildSpec’s adoption records. States often amend the base code, and your city or county may differ, so confirm with your building department.