639-1 Description.
Power service assemblies are utilized for signals, lighting, ITS, and other roadway applications. Install electrical power service assemblies for either overhead service or underground service in accordance with the details shown in Standard Plans, Index 639-001 or 639-002. Coordinate with the power company to provide electrical service to the locations shown in the Plans. Consult and c ooperate with the power company when power is needed at the service point. Furnish and install only those parts of the met ering equipment or co nnections that are required by the power company in the locality involved.
639-2 Definitions.
639-3 Materials.
639-3.1 Weatherhead: Use a weatherhead made of a copper free aluminum alloy with
three electrical service wire entrance holes, meeting National Electric Code ( NEC) requirements.
639-3.2 Conduit: Use conduit meeting the requirements of Section 630. Meet the
requirements of Section 562 for coat ing all field cut and threaded galvanized pipe.
639-3.3 Electrical Service Wire: For signal and ITS service points, u se stranded copper
wire with XHHW (cross -linked polyethylene (XLPE) high heat -resistant, water -resistant) insulation, rated at 600 V in dry and wet condition s, no smaller than No. 6 AWG for connection s between service disconnect and traffic and ITS cabinets, unless otherwise shown in the Plans. For lighting service points, use single-conductor cable Type THWN-2 no smaller than No. 6 AWG fo r connections between service disconnect and load center .
639-3.4 Meter Base: Use meter bases approved by the local electric power company.
639-3.5 Service Disconnect:
FY 2023-24 Return to Table of Contents
639-3.5 1 Enclosure (Cabinet): Use an enclosure conforming to National
Electrical Manufacturers Association ( NEMA) Standards for Type 3R, Type 3S or Type 4, made of galvanized steel, aluminum, stainless steel or other materials approved by the Engineer. Ensure that the enclosure has a hinged door which can be locked with a pa dlock. Provide padlock and two keys. Do not use external handles or switches. Ensure that the inside dimensions meet NEC requirements.
639-3.5 2 Circuit Breaker: Use a manually resettable circuit breaker which has a
current rating above the current ratin g of the circuit breaker to which electrical power is provided. Do not use less than a 40A circuit breaker.
639-3.6 Surge Protective Device: Use a lightning arrester rated for a maximum
permissible line to ground voltage of 175 VAC.
639-3.7 Electrical Po wer Transformer: Provide a dry type , air-cooled, factory
assembled transformer. All units must be UL listed under the requirements of UL 5085 and UL 1561, IEEE Standard 259, and meet the requirements of NEMA ST-20. Provide transformers for the primary and secondary voltages indicated on the Plans. Provide two 2.5% full capacity below normal taps and two 2.5% above normal taps on the primary side . All taps are full capacity taps.
639-3.7 1 Enclosure: Use an enclosure conforming to NEMA Standards for
Type 3R, made of hot-dip galvanized steel , aluminum , stainless steel or other materials approved by the Engineer.
639-3.7 2 Electrical Rating: Transformer electrical ratings may range from
3 KVA to 300 KVA, 120V to 600 V, single phase or three phase, pri mary or secondary, as shown in the plans.
639-3.7 3 Temperature classifications: Transformers rated less than 15 KVA
shall utilize Class 180 or 185 insulation systems , with a 115°C or lower winding temperature rise. Transformers rated 15 KVA and greater shall utilize Class 220 insulation systems , with a 150°C or lower winding temperature rise. The transformer shall utilize an insulation system that has been properly temperature classified in accordance with NEMA ST-20. Encapsulated transformers rated 15KV A to 25KV A using a Class 180 or 185 insulation system with a 115°C or lower winding temperature rise may be utilized if appro ved by the Engineer. Transformer windings shall be all aluminum or all copper.
639-3.7 4 Load rating: Furnish and ins tall transformers with load ratings as
described in the Plans. Transformers shall be capable of operating continuously at 100 percent of nameplate rating in an ambient temperature not exceeding 40°C . Transformers 5 KVA and above shall be capable of meeting overload requirements per ANSI C57.96 with normal life maintained.
639-3.7 5 Sound rating: Sound levels shall not exceed the following:
Table 639-1 Transformer Rating (KVA) Average Sound Level Decibels per NEMA ST -20
0-9 40
10-50 45
51-150 50 150-300 55 FY 2023-24 Return to Table of Contents
639-3.8 Attachment Hardware: Use attachment hardware that meets the requirements
of Section 603.
639-4 Installation Requirements.
639-4.1 General: Meet the following requirements for the installation of individual
components of the electrical power service assembly: Use extreme care and caution in the installation of all components of the electrical power service assembly. Follow installation pr ocedures recommended by NEC and National Electrical Safety Code (NESC). Consider the location of electrical power service assemblies as shown in the Plans to be approximate, and coordinate with the appropriate electrical power company authority to determine the exact locations of each assembly. Do not use transformers or spliced electrical wire on a traffic signal power service.
639-4.2 Weatherhead: Securely attach the weatherhead to the upper end of the conduit
which extends upward from the meter base (or service disconnect if a meter base is not required) to a minimum height of 22 feet above grade.
639-4.3 Conduit: Securely attach all conduit to the pole or cabinet with a maximum
distance of 5 feet between conduit attachment hardware.
639-4.4 Electr ical Service Wire: Install the electrical service wire in a manner which
will ensure that damage to the installation will not occur. Ensure that the service wire is of sufficient length after installation in the conduit to provide for attachment to the p ower company service and for termination within the cabinet for which power is required. Use waterproof gel -filled splices to splice electrical wires in pull boxes only when the length of the cable run prohibits use of continuous wire. Wire nuts and elec trical tape splicing are not acceptable.
639-4.5 Meter Base: When a meter base is required, securely fasten the meter base to the
pole or cabinet. Install pole mounted meter bases at a minimum height of 5 -1/2 feet above grade when measured from the center of the meter base or meet the local electric power company requirement, whichever is greater.
639-4.6 Service Disconnect: Securely fasten the service disconnect to the pole (or
cabinet with the Engineers approval), and electrically position the service d isconnect between the service meter and the traffic control device cabinet to which electrical service is being supplied. Install pole mounted service disconnects a minimum of 4 feet above grade when measured from the bottom of the disconnect. For cabinet installations, mount the service disconnect at a height approved by the Engineer or as shown in the Plans.
639-4.7 Electrical Power Transformer: Follow installation procedures recommended
by NEMA ST-20, National Electric Code (NEC) , and National Electrical Safety Code (NESC). Set the ground mount transformer unit level on the pad and secured to the pad with bolts. Pole mount transformers are required to be fastened securely to the pole using bolts , stainless steel straps, or galvanized strut channel. Conduct field acceptance testing in accordance with Section 611. Perform local field inspection at each site to verify and confirm the following:
639-5 Method of Measurement.
639-5.1 General: Measurement for payment will be in accordance with the following
work tasks. Payment for electrical service wire between service disconnect and traffic cabinet is based upon the distance of the cable run and includes payment for all conductors used in t he run. For lighting applications, payment for service conductors will be made in accordance with Section 715. Payment for conduit and electrical service wire which is vertically attached to the electrical power assembly is considered incidental and paid under item 639 -1.
639-5.2 Furnish and Install: The Contract unit price per foot of electrical service wire,
or the Contract unit price each for electrical service disconnect, furnished and installed, will include furnishing all materials and hardware as specified in the Contract Documents, and all labor, equipment, and miscellaneous materials necessary for a complete and accepted installation.
639-5.3 Furnish: The Contract unit price per foot of electrical service wire, or the
Contract unit p rice each, for electrical service disconnect, furnished, will include the cost of the required materials and hardware as specified in the Contract Documents, plus all shipping and handling costs involved in delivery as specified in the Contract Documents.
639-5.4 Install : The Contract unit price per foot of electrical service wire, or the Contract
unit price each, for electrical service disconnect, installed, will include all labor, equipment, and miscellaneous materials necessary for a complete and accept ed installation. The Engineer will supply electrical service wire or electrical service disconnect.
639-5.5 Electrical Power Service : The Contract unit price per assembly for electrical
power service will include furnishing and installing all material and hardware as specified in the Contract Documents, and all labor and equipment necessary to make a complete and accepted installation.
639-5.6 Electrical Power Transformer : The Contract unit price for each Electrical
Power Transformer will include furnishi ng, installing , and testing all materials and hardware as specified in the Contract Documents, and all labor, equipment, and miscellaneous materials necessary for a complete and accepted installation.
639-6 Basis of Payment.
Prices and payments will be fu ll compensation for all work specified in this Section. Payment will be made under: Item No. 639 - 1- Electrical Power Service - per assembly. Item No. 639 - 2- Electrical Service Wire - per foot. Item No. 639 - 3- Electrical Service Disconnect - each. Item No. 639 - 6- Electrical Power Transformer - each. FY 2023-24 Return to Table of Contents SECTION 641 PRESTRESSED CONCRETE POLES
641-1 Description.
Furnish and install prestressed concrete poles as shown in the Plans . Obtain precast, prestressed concrete poles from a manufacturing plant that is currently on the Department’s Production Facility Listing. Producers seeking inclusion on the list shall meet the requirements of Section 105. Ensure that each pole is constructed and permanently and legibly marked in accordance with Standard Plans, Index 641-010, including the date c ast. Concrete closed circuit television (CCTV) poles must be constructed and permanently and legibly marked in accordance with Standard Plans , Index 641-020, unless shown otherwise in the Plans. The marking shall be visible after installation. Ensure that the shipment of the products to the job site meets the requirements of
450-16.3 and Section 105.
641-2 Materials.
641-2.1 Poles: Meet the following requirements:
Portland Cement Concrete * ............................... Section 346 Reinforcing Steel ................................ ......................... 931-1 Prestressed Strands ................................ ....................... 933-1 Spiral Reinforcing ................................ ...........ASTM A1064 * Class VI
641-2.2 Camera Lowering Device : Use lowering devices that meet the requirements of
Section 996 and are listed on the Department’s Approved Product List (APL).
641-2.2 1 Connector Block: Lubricate all components, including the connector
block and contacts, in accordance with the manufacturer’s recommendation s.
641-2.2 2 Lowering Tool: Provide a min imum of one lowering tool and any
additional tools as required in the Plans. Deliver the lowering tool to the Department before final acceptance.
641-2.2 3 Wiring: All wiring must meet NEC requirements and be installed in
accordance with the equipment ma nufacturers’ recommendations for each device connected on the pole, at the lowering device, and in the field cabinet.
641-2.2 4 External-Mount Lowering System Enclosure for Mounting to
Existing Structures: The cabinet must allow for unobstructed operatio n of the winch, access for servicing and provide sufficient clear area for operation of the winch manually and with an electric drill. Include a pin tumbler lock keyed for use with a No. 2 key and two keys, unless otherwise directed by the Plans. Provide all necessary mounting hardware, conduits, standoffs, and conduit mounts required for a complete and functional system.
641-3 Concrete Pole Construction.
Construct concrete poles in accordance with Section 450. Assume responsibility for performance of all quality control testing and inspections required by Sections 346 and 450; however, the PCI personnel certifications are not required. Plant certification, in accordance with Section 105, is not required for plants that manufacture prestressed concrete pol es. FY 2023-24 Return to Table of Contents