644-1 Description
644-1.01 General. Under this work the Contractor shall fabricate, furnish and erect sign structures for
overhead signs in accordance with the contract documents. The Contractor shall notify the Deputy Chief Engineer, Structures (DCES) of the name and address of the fabricator of all overhead sign structures in accordance with §106 -01 Sources of Supply.
644-1.02 Definitions. Overhead Sign Structures (OSS) are structures with vertical supports and
horizontal arms or chords used to support signs over any portion of the roadway, including the shoulders. Span Wire Assemblies supporting overhead signs, and structures supporting both traffic signal equipment and overhead signs are covered under Section 680, Traffic Signals. Bridge fascia mounted signs, where the signage is intended for the under roadway, are also not covered in this Section. OSS are classified into the following three standard types (See Figure 644 -1):
644-2 Materials
644-2.01 Steel for Sign Structures. Steel for component parts of sign structures shall meet the
requirements of the New York State Steel Construction Manual and the following: All material greater than 1/2 inch thick shall meet the Charpy V -Notch toughness requirements of §715 -01, Structural Steel. Chords, cantilevered arms, end posts, base plates, end and face plates for cantilever arm to post connections, and flange splice pl ates shall be considered main members. Diagonals, struts and gusset or tab plates shall be considered secondary members. Upon receipt at the fabrication plant, all main member material shall be traceable to a mill test report and traceability shall be maintained throughout the duration of the fabrication. All main member material thickness shall be a minimum of 1/4 inch.
644-2 01
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 Single -Arm Cantilever Structure Single -Arm Butterfly Structure Trussed -Arm Cantilever Structure Trussed -Arm Butterfly Structure Single Span Structure End Frame
644-2 01
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 FIGURE 644 -1
644-2 02
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 Washers, and the galvanizing requirements of §719 -01, Galvanized Coatings and Repair Methods. Additionally, the Contractor shall provide documentation that the zinc coated fastener assemblies have satis fied the requirements of ASTM A3125 Annex 2 Rotational Capacity testing . Fasteners in main members shall be sampled and tested in accordance with Section 1001.5 of the New York State Steel Construction Manual, with the exception that the waiver for lot sizes less than 20 bolts shall not apply.
644-2.02 Concrete. All overhead sign structure foundations shall meet the requirements of Class A
concrete in Section 501, Portland Cement Concrete - General. The Contractor may submit, for approval by Director, Materials Bureau, a mix at least equivalent to the specifie d Class A Concrete. All precast concrete overhead sign structure foundations shall meet the requirements of §704 -03, Precast Concrete - General. For situations which require depositing structural concrete under water, provide Class G concrete as described in Table 501 -3 Concrete Mixtures and Table 501 -3A Pozzolan Substitutions . For design and construction purposes, the minimum compressive strength of concrete used in the foundations shall be 3000 psi @ 28 days .
644-3 Construction Details
644-3.01 Drawings. Shop drawings shall be required for all OSS in the contract documents. The
Contractor must submit shop drawings in accordance with the requirements of Section 2 in the New York State Steel Construction Manual.
644-3.02 Fabrication. All fabrication shall be performed in accordance with the requirements of the New
York State Steel Construction Manual.
644-3 03
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 inches high, with the corners cut to a 1 1/2 inch radius. The numbers shall be cut out from White, Class A, Engineer Grade reflective sheeting and shall be 3 inches high. The sheeting and numbers shall be applied in accordance with the manufacturer’s rec ommendations. The numbers shall be placed on the right near post, 45 degrees from the viewing direction of traffic, approximately 6 feet above the base plate, so as to be visible to the traveling public. For structures spanning more than one direction of traffic, or structures that span non -contiguous travel lanes, two posts shall be marked to facilitate identification by inspectors. The following information shall be stamped into the base plate in 1/2 inch letters to such a depth as to be clearly visible through subsequent galvanizing: Required Information Example Manufacturer’s name or logo ABC Fabricating Month and year of manufacture 06/2003 D Number D123456 SIN Number SIN 12345 For span type structures the marked base plate shall correspond to the marked posts, except that only one end of the span must be marked.
644-3.03 Transportation. Sign structures (including posts and post assemblies) shall be shipped by flat
bed trailer or other similar means. Structures shall be shimmed, braced, blocked, and tied down to prevent distortion or other damage from occurring during transportation. The use of any device which does not support the member for its entire length, as described below, shall not be permitted. This prohibition includes, but is not limited to, dolly wheels and pole trailers. Sections less than 50 feet in length shall be, at a minimum, supported at the midspan and end points. Sections 50 feet and longer shall be, at a minimum, supported at the ends and at the quarter points.
644-3 04
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 Adhering to these requirements does not relieve the Contractor of the responsibility for damage to the structure en route.
644-3.04 Excavation. All excavation shall conform to Section 206, Trench, Culvert and Structure
Excavation. Excavation shall not be performed until immediately before installation of the footings, or any other appurtenances. The excavated material shall be placed in a location or locations selected by the Contractor so as to cause the least inconvenience to vehi cular and pedestrian traffic and to avoid interference with surface drainage. All surplus excavated material shall be removed and disposed of by the Contractor as specified in Section 203, Disposal of Surplus Excavated Material Excavation shall be backfilled as specified in Section 203, Select Structure Fill The outline of all areas to be removed in sidewalks, driveways, and pavement shall be saw cut to a depth of at least 3 inches prior to removal. Cuts shall be neat and true along score lines with no shatter outside the removal area. Damaged saw cut areas s hall be recut. Pavement, shoulder, sidewalks, curbs, driveways, lawns, plants and other such features shall be replaced in kind with material of equal quality or as shown in the contract documents. For transverse sidewalk, curb or gutter cuts in concrete the entire squa re or section shall be removed and replaced with the same kind and quality of material. For longitudinal cuts in concrete sidewalks only the area removed between sawcuts shall be replaced unless specified otherwise in the contract documents. Whenever a part of a square or slab of existing concrete sidewalk, curb, gutter or driveway is broken or damaged by this work, the entire square, section or slab shall be removed and replaced with the same kind and quality of material, at no additional cos t to the State.
644-3.05 Concrete Foundations. Foundations shall be constructed as shown in the contract documents.
The Contractor shall establish the location and elevation of foundation, prior to the start of construction, based on the information shown in the contract documents and data derived f rom field surveys. Locations and elevations will be verified by the Engineer prior to the start of construction. The Contractor has the option, unless specifically disallowed in the contract documents, to use either Drilled Shafts or Rectangular Footings for Overhead Sign Structures, if both types are detailed in the contract plans. When both foundation types are de tailed and permitted, the Department has prepared the contract documents based on the presumed less expensive foundation type. If the Contractor elects to change from one type of foundation to the other under this option, it shall be done at no additional cost to the State. The Contractor shall notify the Engineer of the decision to change foundation type. Excavation for these items shall be as specified in §644 -3.04. All concreting operations shall conform to Section 555, Structural Concrete. Reinforcing steel shall conform to Section 556, Reinforcing Steel for Concrete Structures. The allowable tolerance from verticality for the drilled shaft or pedestal shall be 2.5%. The allowable tolerance for the top of shaft elevation or pedestal elevation shall be + 1/4 inch, -0 inch. Stripping of forms and subsequent loading of foundations shall be in accordance with §555 -3, in Table 555 -4, under “Pier Columns”. Placing the sign panels on an overhead sign structure is assumed to be equivalent to placing superstructure loads on a bridge.
644-3 06
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 concrete due to the presence of groundwater and loose cohesionless soil at the base of the drilled shaft, proceed with the installation by not dewatering the shaft excavation and place Class G tremie concrete in accordance with §555 -3.05 Depositing Structu ral Concrete Under Water. The bottom of the shaft excavation shall be cleaned of loose material to the satisfaction of the Engineer immediately prior to concreting. Where a temporary casing is used to assist in pouring a concrete shaft, the casing shall be removed as the concrete is placed. Precast shafts shall not be permitted.
644-3.06 Erection of Sign Structures
644-3 06
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 2. Anchor bolts shall be set vertical, within 2.5%, and shall not be realigned by bending to fit the base plate. Anchor bolts that do not fit the base plate, or anchor bolts that are more than 2.5% out of plumb, shall be rejected. The Contractor may propos e a remediation method for rejected anchor bolts, subject to the approval of the Engineer. Rejected anchor bolts, and the concrete they are embedded in shall be replaced by new materials at no cost to the State.
644-4 01
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 FIGURE 644 -2
644-4 Method of Measurement
644-4.01 Sign Structure. The work will be measured as the number of sign structures installed without
sign panels.
644-4.02 Drilled Shafts for Overhead Sign Structures. The payment quantity shall be the concrete
volume shown for the shaft in the table in the contract documents, multiplied by the number of drilled Anchor Bolt Star Pattern Tightening Sequence 6 Bolt Pattern 8 Bolt Pattern
644-4 03
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 shafts in the contract, unless the Engineer orders a modification to the details shown in the contract documents. If the Engineer orders a modification to the details shown in the contract documents, the payment quantity shall be the volume of concrete o rdered by the Engineer. If the Engineer orders a change from a drilled shaft to a rectangular footing, an order -on-contract shall be negotiated. No adjustment shall be made for the Contractor's election to use a rectangular footing, unless the Engineer orders a change to the details shown in the contract documents.
644-4.03 Rectangular Footing for Overhead Sign Structures. The payment quantity shall be the
concrete volume shown for the footing and pedestal in the table in the contract documents, multiplied by the number of footings in the contract, unless the Engineer orders a modification to the details shown in the contr act documents. If the Engineer orders a modification to the details shown in the contract documents, the payment quantity shall be the volume of concrete ordered by the Engineer. If the Engineer o rders a change from a rectangular footing to a drilled shaft, an order -on-contract shall be negotiated. No adjustment shall be made for the Contractor’s election to use a drilled shaft, unless the Engineer orders a change to the details shown in the contr act documents.
644-4.04 Anchor Bolts. The payment quantity shall be the mass shown in the anchor bolt table in the
contract documents times the number of bolts installed.
644-5 Basis of Payment
644-5.01 Sign Structure. The unit price bid for each structure for supporting sign panels shall be
compensation in full for fabricating, furnishing and erecting the structure complete as specified including upright support(s), span and/or cantilever arm or truss assemblies, diag onal bracing, all necessary hardware, nuts, bolts, and washers, and all other material, equipment and labor necessary to properly complete the work as shown in the contract documents and called for in the specifications. Footings a nd anchor bolts shall be paid for under separate items or will be furnished by others. The cost of all shop drawings, prints and reproducible prints required by the New York State Steel Construction Manual shall be included in the unit price bid for this item.
644-5.02 Foundations for Overhead Sign Structures. The unit price bid per cubic yard shall include
the excavation, any protective system(s) required to ensure the safety of the workers and the public, dewatering, backfill (select granular backfill or concrete), formwork, concrete, bar reinforcement for concrete, excavation and backfilling of test holes, conduit and fittings, restoration of surfaces in kind, disposal of excess excavated material, and saw cutting.
644-5.03 Anchor Bolts. The unit price bid pound shall include the furnishing and installing the anchor
bolts and all necessary hardware, including galvanizing, as shown in the contract documents and called for in the specifications. This includes the anchor bolts, all templat es used to ensure the proper alignment of the anchor bolt system, all nuts, and all washers necessary to complete the work as shown in the contract documents. Payment will be made under: Item No. Item Pay Unit 644.11 Anchor Bolts Pound 644.20 Drilled Shaft for Overhead Sign Structures Cubic Yard 644.30 Rectangular Footing for Overhead Sign Structures Cubic Yard 644.41xxyy Single Arm Cantilever Sign Structure Each 644.42xxyy Trussed Arm Cantilever Sign Structure Each 644.43xxyy Single Span Sign Structure Each 644.44nn Non-Standard Sign Structure Each NOTE:
645-1 01
NEW YORK STATE DEPARTMENT OF TRANSPORTATION Section 600 STANDARD SPECIFICATIONS (USC) January 1, 202 4 VOLUME 3 1. xx, yy and nn denote serialized pay items. See §101 -02, Definition of Terms, under “Specifications”.
645-1 DESCRIPTION. This work shall consist of fabricating, installing and covering traffic sign
panels, sign support systems, sign posts, and illuminated sign panels in accordance with the contract documents, standard sheets, the MUTCD and as directed by the Engineer.
645-1.01 Definitions. The following definitions shall apply to all work equipment and materials included
under this section:
645-2 Materials
645-2.01 General. Materials shall meet the requirements of the following subsections of Section 700
Materials and Manufacturing : Wood Preservative - Water Borne 708-31 Stress Graded Timber and Lumber 712-14 Stainless Steel Connecting Products 715-16 Rubber Impregnated Woven Cotton -Polyester Fabric 728-01 Rubber Impregnated Random Fiber Pad 728-02 Aluminum Sign Panels 730-01 Retro -Reflective Sign Sheeting 730-05 Stiffeners, Overhead Brackets, and Miscellaneous Hardware 730-22 Fiberglass Reinforced Plastic Sign Panels 730-23 Type A Sign Supports 730-24 Type B Sign Posts 730-25 Breakaway Bases and Hinge Assemblies 730-26 U-Bolts ASTM F1554, Grade 36