9-227 Section 923. Water M ain Materials
923.01 General
Materials for water main work must meet the requirements of this section, American Water Works Association (AWWA ) specifications, and the requirements of the water main owner ( municipality).
923.02 Pipe
The Department considers lines 2 inches or less in diameter to be water services, not water mains . Water service pipe must be Type K copper . The minimum water service size is 1 inch. Water main must be ductile iron pipe manufactured in accordance with ANSI/AWWA C150/A21.50 and C151/A21.51. Pipe must be lined with a standard thickness , cement -mortar lining sealed with a bituminous seal coat in accordance with ANSI/AWWA C104/A21.4. The outside of the pipe must be coated with the standard bituminous seal , and each length of pipe must be marked w ith the following information:
923.03 Gate Valves
Provide resilient wedge valves for use in water distribution systems with a nominal diameter from 6 to 12 inches, rated for at least 200 psi . Valves must meet the requirements of AWWA C509.