ITEM 613 LOW STRENGTH MORTAR BACKFILL
613.01 Description. This work consists of placing a low strength mortar backfill around conduits
and at other locations. Perform the work for this item according to Items 611 and 499, except as modified below.
613.02 Materials. Furnish materials conforming to:
Cement ............................. 701.01 or 701.04 Fly Ash ............................................. 701.13 Furnish fine aggregate consisting of foundry sand, natural sand, sand manufactured from stone, gravel, or air -cooled blast furnace slag. Conform to the fine aggregate gradation requirements of
703.05 Use fine aggregate that is fine enough to stay in suspension in the mixture to ensure proper
flow. Furnish an air -entraining admixture that is designed for use in low strength mortar mixtures (also called controlled density fill or flowable fill).
613.03 Mix Proportioning. Furnish a low strength mortar mixture listed below or provide an
alternate mix conforming to 613.05. TABLE 613.03-1 Type 1[1] Type 2 Type 3 lb/yd³ kg/m³ lb/yd³ kg/m³ lb/yd³ kg/m³ Cement 50 30 100 59 0 0 Fly Ash, Class F 250 148 [2] [2] 1500 890 Fly Ash, Class C [4] 0 0 0 0 500 297 Fine Aggregate [3] 2910 1726 2420 1436 0 0 Water (Target) 500 297 210-300 125-178 850 504 [1] The Contractor may add an air-entraining agent specifically designed for the use in the low strength mortar mixture. [2] Entrained air is substituted for fly ash in this mix. (Approximately 25 percent) [3] Saturated Surface Dry [4] Class C Fly Ash may be substituted for Class F Fly ash in Type 1 mixes with an approved mix design meeting the alternate mix design criteria of this specification. These mixtures of materials are expected to yield approximately 1 cubic yard (1 m3) of material of a flowable consistency. Make small adjustments, as necessary, in the amounts of the materials in a mix to achieve the final product.
613.04 Mix Adjustment. Make one or more 1 cubic yard (1 m3) trial batches at different water
contents to ensure a flowable material. The mixture is too dry if cracks develop in the mixture as it flows into place. Adjust the proportions to maintain the total absolute volume. For large adjustments, see 613.05. In order to expedite the settlement of a Type 1 mixture without entrained air, bleed water may appear on the surface immediately after the material is struck off. A delay in bleeding indicates there are too many fines in the mixture. The Contractor may reduce the fly ash quantity in increments of 50 pounds (30 kg) until the mixture is bleeding freely. Add approximately 60 pounds (36 kg) of sand to replace each 50 pounds (30 kg) increment of fly ash to maintain the original yield.
613.05 Alternate Mixes. The Contractor may submit alternate mixes for approval. Furnish the
mix design and test data from an independent test laboratory 30 days before the intended usage for approval. Submit an alternate mix design for all mixes that:
613.06 Mixing Equipment. Provide the mixing capacity and delivery equipment to place the
material without interruption as much as practical. Deliver and place Type 1 and 2 mixes or Type 1 and 2 alternate mixes from ready mixed concrete trucks, or deliver them from a batch plant. Deliver and place Type 3 mix using volumetric mobile mixers. Calibrate volumetric mixers properly and sufficiently mix the materials in the mixer to produce a uniform material.
613.07 Mixing the Materials. Discharge the mixture within 2.5 hours after adding water.
613.08 Placing Mortar. Unless specifically shown on the plans, do not place the mortar within
3 feet (1 m) of the subgrade elevation. Discharge the flowable material from the mixer by any reasonable means into the space of the plan intended usage. Bring the fill material up uniformly to the fill line shown on the plans. The Contractor may begin placing the other fill material over low strength mortar backfill material as soon as the surface water is gone. The Engineer reserves the right to reject the mix if a flowable mixture is not produced. Before placing the low strength mortar backfill as backfill for 611 Conduit , secure the conduit to prevent it from floating during placement of the flowable material.
613.09 Method of Measurement. The Department will measure Low Strength Mortar Backfill
by the number of cubic yards (cubic meters) completed and accepted in place, computed from the plan lines. The Department will not pay additional compensation for over excavated areas or for a change in the material blends.
613.10 Basis of Payment. The Department will pay for accepted quantities at the contract prices
as follows: Item Unit Description 613 Cubic Yard Low Strength Mortar Backfill (Cubic Meter) 613 Cubic Yard Low Strength Mortar Backfill (Cubic Meter) (Type ___)